GREE AIRY ducted and SAMSUNG PREMIUM FJM ducted: airflow and pressure, as published
Two 12,000 BTU ducted units, each with its own AHRI certificate. With a ducted unit, the question is always the same: how much air does the fan push against the resistance of the ducts? This page sets side by side what GREE and SAMSUNG publish: the static pressure settings, the airflow by speed, then the certified values down to extreme cold.
AIRY ducted 12,000 BTU
GFH(12)DA-D6DNA1A/I / GWH12AVDXE-D6DNA1B/O · AHRI 216618221
GREE Canada presents this indoor unit as the high static pressure duct of its ALL MATCH R32 range. Certified values nearly identical to those of the GREE ALL MATCH Slim Duct (AHRI 215415562), with small differences.
View the product page
PREMIUM FJM ducted 12,000 BTU
AC012DNLDCG / AC012DXSCCG · AHRI 216441744
The combination compared is a single-zone system, with its own certificate. SAMSUNG names it “Slim Duct, Single Zone (Premium)”; this page calls it Slim Duct LSP, as the manufacturer’s Technical Data Book does.
View the product pageWhat the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the point of reference.
How this amount is calculated
- Heat needed over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (the “Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air conditioning calculator, with the seasonal SEER2 efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one offered by Hydro-Québec’s calculators. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.
Two ways to set the pressure: eight notches on one side, five ranges on the other
The slider stops only on published values. At each stop, you see which GREE notch and which SAMSUNG setting match that pressure, or whether the published range is exceeded.
Dots: the GREE notches (2 to 9). Bands: the five SAMSUNG settings, chosen by option code. The pressure of your duct system is calculated from the duct layout: that is the installer’s job, and this page gives no sizing advice. Conversion: 1 in. w.g. = 249 Pa.
GREE AIRY ducted
Four published airflows, with no speed names in the document.
SAMSUNG Slim Duct LSP
Three published speeds; same airflows in cooling and in heating.
Bars on the same 500 CFM scale. Each airflow is the one its manufacturer publishes, by its own test method.
| Fan and ducts | AIRY ducted | Slim Duct LSP |
|---|---|---|
| External static pressure range | 0 to 150 Pa (0 to 0.60 in. w.g.) | 2.5 to 60 Pa (0.01 to 0.24 in. w.g.) |
| Static pressure settings | 8 notches, from notch 2 to notch 9: 0, 20, 40, 60, 80, 100, 120 and 150 PaSet at the wired controller | 5 settings by option code: up to 15, 25, 40, 50 and 60 Pa0.06, 0.10, 0.16, 0.20 and 0.24 in. w.g. in the document; standard setting: 25 Pa |
| Airflow by speed | 4 speeds: 212 / 247 / 288 / 353 CFM | 3 speeds: 325 / 385 / 456 CFM |
GREE: GREE Canada does not release to the public a submittal under the number GFH(12)DA-D6DNA1A/I. The notches, airflows, dimensions and sound of the indoor unit come from the documents GREE publishes in the United States for the Slim Duct (HS) of the same ALL MATCH R32 range, model DUC12HP230V1R32AH: submittal GREE_DUC12HP_230V_R32_SUB_08272025 and service manual JF00305639, p. 46. SAMSUNG: submittal AC012DNLDCG/AA, version 02132025A, and Technical Data Book Ver. 3.1, p. 22.
Below −15 °C: every published number, at its exact temperature
At −15 °C, both ducted units are certified at the same point: 10,500 and 11,200 BTU/h maximum. Lower down, their points do not fall at the same temperatures: the coldest certified point is at −30 °C for the AIRY ducted and at −25 °C for the Slim Duct LSP.
What each manufacturer writes, group by group
GREE: product page on the GREE Canada site and GREE documents for the Slim Duct (HS). SAMSUNG: submittal AC012DNLDCG/AA and AC012DXSCCG/AA, version 02132025A.
AIRY ducted : high, adjustable external static pressure, per GREE Canada; 8 notches from 0 to 150 Pa in the Slim Duct (HS) service manual.
Slim Duct LSP : 2.5 to 60 Pa, 5 settings chosen by option code; standard setting at 25 Pa.
AIRY ducted : built-in condensate drain pump, per GREE Canada.
Slim Duct LSP : integral condensate pump, maximum 29 in lift from the bottom of the unit.
AIRY ducted : wired thermostat included, per GREE Canada; Wi-Fi not included in the Slim Duct (HS) submittal.
Slim Duct LSP : built-in Wi-Fi as standard, SmartThings app; wired controllers and wireless remote optional.
AIRY ducted : refrigerant sensor, per GREE Canada.
Slim Duct LSP : R-32 alarm output plug on the indoor unit and the outdoor unit; optional MRS-L32U leak detector.
AIRY ducted : washable filter; return air from the bottom or the rear; outside air intake possible, per GREE Canada.
Slim Duct LSP : optional FB-SLIM2 filter box; return air direction: not published in the submittal.
AIRY ducted : low ambient temperature cooling and heating, per GREE Canada; heated pan: not published by the manufacturer.
Slim Duct LSP : base pan heater as standard; published heating range down to −25 °C.
Two hidden cabinets, different airflows and methods
GREE publishes four values without describing the test conditions. SAMSUNG publishes three, measured in an anechoic room per its Technical Data Book.
How to read these numbers. dB(A) measures a noise level the way the ear perceives it: the lower the number, the quieter the unit. Each dot is a published fan speed, from slowest to fastest.
Why this is not a ranking. The airflows are not the same: 212 to 353 CFM for the AIRY ducted, 325 to 456 for the Slim Duct LSP. A ducted unit is hidden: what you hear in the room also depends on the ducts, the grilles and the pressure the fan works against.
Indoor unit, at the cabinet
Every published speed
Outdoor unit, outside
Published values
Measurements taken by each manufacturer using its own method: read them separately, not as a ranking.
The two systems, line by line
Indoor units, photos at the same width scale


Three-quarter photos: the dimension line gives each cabinet’s published width. Height cannot be read from these perspective photos: 300 mm for the AIRY ducted, 198 mm for the Slim Duct LSP.
| Installation | AIRY ducted | Slim Duct LSP |
|---|---|---|
| Indoor unit H × W × D, weight | 300 × 830 × 754 mm, 70.6 lb11 13/16 × 32 43/64 × 29 11/16 in, per the GREE submittal for the Slim Duct (HS) | 198 × 900 × 440 mm, 42.3 lb7 13/16 × 35 7/16 × 17 5/16 in |
| Drain pump | YesBuilt-in condensate drain pump, per GREE Canada | Yes, maximum 29 in lift |
| Maximum piping length | Not published by the manufacturer | 66 ft |
| Precharged length | Not published by the manufacturer | 24.6 ft |
| Maximum height difference | Not published by the manufacturer | 49 ft |
| Outdoor unit W × H × D, weight | 34 3/8 × 21 27/32 × 14 51/64 in, 78.3 lb | 31 1/8 × 21 5/8 × 11 3/16 in, 67.2 lb |
| Electrical protection | Not published by the manufacturer | Maximum protection: 15 A; minimum circuit ampacity (MCA): 13.9 A |
| Heated base pan | Not published by the manufacturer | Yes, as standard |
| Advertised heating / cooling range | −30 to 30 °C / −29 to 50 °CGREE EXTRÊME R32 brochure, same outdoor unit | −25 to 24 °C / −5 to 50 °CCooling down to −18 °C with a wind baffle, per the submittal |
GREE: the outdoor unit GWH12AVDXE-D6DNA1B/O is that of the GREE EXTRÊME R32; its dimensions, weight and ranges come from GREE Canada brochure no. 032025. For the wall-mounted version, that brochure gives a maximum of 131.2 ft of piping, 82 ft of height difference and a maximum protection of 15 A: GREE does not publish these values for the ducted combination, and they are to be confirmed with the quote. SAMSUNG: submittal version 02132025A; ranges published in °F: −13 to 75 °F and 23 to 122 °F.
What people ask about these two ducted units
Is the airflow at each pressure published?
Not as numbers. GREE and SAMSUNG publish their fan curves as graphs. What is given as numbers are the pressure settings (8 notches from 0 to 150 Pa, 5 settings from 2.5 to 60 Pa) and the airflow by speed: 212 to 353 CFM and 325 to 456 CFM.
Do the GREE AIRY ducted and the GREE ALL MATCH Slim Duct have the same values?
Nearly. They are two separate certificates, AHRI 216618221 and 215415562, with two different outdoor units. The certified values are the same with small differences: SEER2 of 21.5 against 21 and, at −8.3 °C, 10,300 against 10,000 BTU/h of rated capacity (COP of 2.80 against 2.79). GREE Canada lists the indoor unit GFH(12)DA-D6DNA1A/I in its ALL MATCH R32 range.
Is the SAMSUNG PREMIUM FJM ducted a multi-zone unit?
The combination compared here is a single-zone system: indoor unit AC012DNLDCG with outdoor unit AC012DXSCCG, under AHRI certificate 216441744. The values on this page apply to that combination only.
Which one has a setting for my ducts?
It depends on the pressure calculated for your duct system. Up to 60 Pa, both have a published setting. Beyond that, only the GREE notches continue, up to 150 Pa. The calculation is done during the estimate, from the duct layout.
Why do some lines say “Not published by the manufacturer”?
Because the document consulted does not give that value for this combination. It is not a missing feature: the document is silent. These points are confirmed with the quote, using the unit’s documents.
Are they eligible for grants?
Eligibility depends on the official list in effect on the purchase date. This page promises no amount; the current list is checked when the quote is prepared.
All AHRI and NEEP values for the two systems
| Certified value | AIRY ducted | Slim Duct LSP |
|---|---|---|
| Cooling | ||
| 35 °C: min. / rated / max.BTU/h | 2,700 / 12,000 / 15,354 | 3,200 / 12,000 / 14,000 |
| SEER2 | 21.5 | 19.6 |
| EER2 | 13 | 11.8 |
| Heating, same conditions | ||
| HSPF2 Region IV | 9 | 9.5 |
| HSPF2 Region V | 8 | 7.6 |
| 8.3 °C: min. / rated / max.BTU/h | 3,070 / 12,000 / 14,160 | 3,000 / 14,000 / 17,000 |
| 8.3 °C: COP min. / rated / max. | 5.29 / 3.78 / 3.61 | 5.17 / 3.60 / 2.37 |
| −8.3 °C: min. / rated / max.BTU/h | 2,700 / 10,300 / 12,000 | 6,000 / 8,800 / 14,200 |
| −8.3 °C: COP min. / rated / max. | 3.04 / 2.80 / 2.20 | 2.75 / 2.69 / 2.46 |
| −15 °C: min. / rated / max.BTU/h | 2,600 / 10,500 / 10,500 | 4,500 / 11,200 / 11,200 |
| −15 °C: COP min. / rated / max. | 2.54 / 1.90 / 1.90 | 1.81 / 1.80 / 1.79 |
| Coldest point — different temperatures, not highlighted | ||
| Test temperature | −30 °C (−22 °F) | −25 °C (−13 °F) |
| Capacity min. / max. | 2,000 / 6,500 BTU/h | 3,300 / 7,000 BTU/h |
| COP at maximum capacity | 1.42 | 1.77 |
| Certifications and refrigerant | ||
| ENERGY STAR / cold climate (NEEP) | Yes / Yes | Yes / Yes |
| Certificate type (NEEP) | Single-zone, compact ducted | Single-zone, centrally ducted |
| AHRI certificate · NEEP record | 216618221 · 382316 | 216441744 · 406922 |
| RefrigerantGWP per the IPCC (AR4); ASHRAE 34 class | R-32 · GWP 675 · A2L | R-32 · GWP 675 · A2L |
higher marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Capacities and COPs at each point are not highlighted: the order changes depending on the point.
Your duct system decides the setting.
Talk to our team: bring a sketch of the rooms to serve, the free depth in the ceiling and the planned outdoor location. AirGreen sells both systems.
Where each number comes from
Data verified on November 10, 2026. Performance: AHRI certificates and the NEEP database. Dimensions, static pressure, airflows, sound, piping and features: according to the manufacturer, with the document named in each section. When a source contradicts the AHRI certificate, the certificate prevails.