Home / Comparisons / Steam humidifiers
APRILAIRE 800 and HONEYWELL HM700, from litre to steam
Both boil tap water between two electrodes and send the steam into the ducts. What they produce depends mostly on how they are wired: 120, 208 or 240 V, and for the AprilAire, 11.5 or 16 A. Here is every published setting, in litres and kilowatt-hours.
HONEYWELL HM700
HM700A1000/U · cylinder HM700ACYL2 · HumidiPRO H6062
See the product pageWhat each one produces, depending on how it is wired
Pick the house voltage and, for the AprilAire, the current setting. Both documents give output in US gallons a day and power in kilowatts; the page converts them to litres and works out the electricity per litre of steam, formula shown.
No “Cost per season” block on this page: a humidifier has no HSPF2 or SEER2, so the cost method of our heat pump comparisons does not apply.
Two electrodes in a throwaway cylinder, in both
Current flows from one electrode to the other through the water. The water resists, heats and boils. The higher the water rises on the electrodes, the more current and steam; the unit fills until the current meets demand. The minerals stay in the cylinder, which is replaced whole.
Diagram, not a photo. Principle described in both manuals; the real parts differ from one model to the other.
Model 80 canister for most installations, hard or softened water; Model 80LC for water below 300 µS/cm or a 120 V installation, never with softened water. It is replaced when the Service light flashes red.
A single approved cylinder, the HM700ACYL2. Its life depends on the water and the use; when scale has worn it out, the yellow light flashes four times and the unit stops. Resideo advises keeping a spare during the season.
The AprilAire is set by current (11.5 or 16 A) and by voltage with a jumper; it leaves the factory at 240 V and 11.5 A. The HM700 is set by voltage only (110/120 or 220/240 V) and draws 12 A either way, per its specification table.
Tap water that conducts well enough, at the right pressure
An electrode humidifier needs the minerals in the water to carry the current. Both manuals rule out demineralized and reverse-osmosis water. Each bar shows the range written by the manufacturer, on the same scale for both.
On the wall, near the duct, with a drain and a circuit of its own
Steam output drops along the way: the longer the hose, the less reaches the duct. AprilAire puts numbers on that loss; Resideo states it without numbers.
Length of the steam hose or pipe
AprilAire: Table 4 of the installation manual (supplied hose 6 ft at most; beyond that, 1 in. insulated pipe). The voltage and setting chosen above apply here too. Resideo: 5 ft hose in the HM700ADISTKIT kit, 15 ft kit optional, 20 ft at most “as a best practice”.
Both units at the same scale


Photos scaled to the height each manufacturer publishes. The HM700 photo is a three-quarter view.
| Installation | APRILAIRE 800 | HONEYWELL HM700 |
|---|---|---|
| Electrical | ||
| Power supply | 120, 208 or 240 V, 60 Hzshipped at 240 V, 11.5 A | 110/120 or 220/240 V, single phasefactory configured; Resideo advises against changing the jumpers |
| Electrical protection | Dedicated circuit, 20 A minimum at 11.5 A; 25 A minimum at 16 AInstallation manual, pp. 13–14 | Dedicated 15 A breaker, ground-fault protected circuitInstructions 33-00118EFS, p. 10 |
| Power at full output | 1.4 to 3.8 kWdepending on voltage and setting | 1.4 or 2.8 kWat 110/120 or 220/240 V |
| Water and drain | ||
| Supply water pressure | 25 to 120 psi | 30 to 100 psi |
| Water conductivity | 125 to 1,250 µS/cmspec sheet 01.26; the 2018 manual also writes 100 µS/cm on p. 7 | 150 to 1,200 µS/cmrecommended value |
| Drain | 7/8 in. ID tubing supplied; water tempered below 60 °C (140 °F) by the cold inlet water | Water cooled to 60 °C (140 °F) on automatic drains; tubing and drain rated for 93 °C (200 °F) |
| Mounting | ||
| Steam hose, length | 6 ft hose supplied; beyond that, 1 in. insulated pipe; Table 4 goes to 20 ft | 5 ft in the HM700ADISTKIT kit; 20 ft at most |
| Maximum duct static pressure | 2 in. w.c. | 3.0 in. w.c. |
| Minimum duct airflow | Not published by the manufacturer. The manual gives an absorption distance by air speed instead. | 115 CFM at 110/120 V; 230 CFM at 220/240 V |
| Clearances | 30 in. for service; 16 in. for the hose, wiring and drain (fig. 8) | On the wall, at least 24 in. above the floor; service clearances in fig. 2 |
| Dimensions W × H × D | 10 1/8 × 20 7/8 × 7 1/8 in. | 11.5 × 21.5 × 6.75 in.published L × W × H: 11.5 × 6.75 × 21.5 in. |
| Humidifier, weight | 23 lb empty, 27 lb operating | 15 lb empty, 20 lb full |
| Stated ambient range | Not below freezing, not above 60 °C (140 °F) | 5 to 40 °C, 5 to 95 % RH |
What each manufacturer writes, line by line
AprilAire: Model 62 automatic digital control with outdoor sensor, setting 10 to 45 % or off, accuracy ±3 %.
Resideo: HumidiPRO H6062 humidistat supplied in the box.
AprilAire: the control can run the blower to humidify while the furnace is idle (blower activation).
Resideo: no steam until the fan safety loop is closed; optional 50027910-001 air-proving switch, advised on every installation.
AprilAire: drain cycle of about 4 minutes; cold inlet water tempers the drain water.
Resideo: automatic drains keep the conductivity in range; water cooled to 60 °C.
AprilAire: canister replaced, not cleaned; yearly care of the O-ring, drain valve and screen; electrode wires every 3 years.
Resideo: clean the drain valve at every cylinder change; only the HM700ACYL2 is approved.
AprilAire: it can take several days to reach rated output, depending on the water.
Resideo: 5 to 10 minutes to boil; with low-conductivity water, full output can take several hours.
AprilAire: running during cooling calls is not advised, because of condensation risk; lockout advised.
Resideo: if condensation appears, check supply air temperature and humidity (troubleshooting, p. 21).
Questions about these two humidifiers
Which one makes more steam?
It depends on the wiring. At 240 V, the AprilAire 800 publishes 23.3 gal/day at 11.5 A and 34.6 gal/day at 16 A; the HM700 publishes 22 gal/day. At 120 V, 11.5 or 16 gal/day against 11 gal/day. The selector at the top of the page gives each case, in litres too.
And at 208 V, common in many buildings?
AprilAire publishes 20.5 gal/day at 11.5 A and 30 gal/day at 16 A at 208 V. Resideo's HM700 document gives its values at 110/120 V and 220/240 V; it does not put a number on output at 208 V.
What size of house?
The two manufacturers do not measure the same way. AprilAire gives an area in sq ft for a tight, average or loose house with 8 ft ceilings: at 208 or 240 V and 16 A, up to 4,000 sq ft for an average house. Resideo asks for a calculation in cu ft and refers to the AHRI table: for 32,000 cu ft of average construction, 33 gal/day, which is two HM700 units at 240 V. The two tables do not compare line by line.
My water is softened: is that a problem?
AprilAire accepts softened water with the Model 80 canister, not with the 80LC. Resideo's HM700 document does not mention it; it requires water between 150 and 1,200 µS/cm and rules out demineralized and reverse-osmosis water.
Do these units work with a heat pump?
Neither document mentions heat pumps. AprilAire's manual asks that the absorption distance in the duct be based on the lowest temperature expected in that duct (p. 8). Its Table 3 gives, at 300 fpm and for 25 to 35 gal/day, 31 in. at 21 °C (70 °F) and 45 % humidity, against 60 in. at 7 °C (45 °F) and 45 %. Our steam versus evaporative comparison comes back to duct temperature.
Is the HM700 still made?
Resideo's documents for the HM700A1000 carry the note “legacy product… no longer manufactured”. AirGreen lists it on its site; ask our team about the availability of the unit and of HM700ACYL2 cylinders. Document checked November 10, 2026.
Why not compare the warranties?
Our comparisons do not compare warranties. Each manufacturer's warranty documents come with the quote.
Every published value, in one place
| Value | APRILAIRE 800 | HONEYWELL HM700 |
|---|---|---|
| Published steam output | ||
| Steam output at 120 V | 11.5 gal/day at 11.5 A; 16 gal/day at 16 A | 11 gal/day (110/120 V) |
| Steam output at 208 V | 20.5 gal/day at 11.5 A; 30 gal/day at 16 A | Not published by the manufacturer at 208 V |
| Steam output at 240 V | 23.3 gal/day at 11.5 A; 34.6 gal/day at 16 A | 22 gal/day (220/240 V)7.7 lb/h (3.5 kg/h), Table 6 |
| Electrical | ||
| Power at 240 V | 2.8 kW at 11.5 A; 3.8 kW at 16 A | 2.8 kWthe wiring label on p. 2 shows 2.9 kW |
| Power at 120 V | 1.4 kW at 11.5 A; 1.9 kW at 16 A | 1.4 kW |
| Current | 11.5 or 16 A11.5 A ±10 %; size the circuit for 12.7 A | 12 A |
| Cylinder and control | ||
| Electrode cylinder | Model 80 or 80LC depending on the water | HM700ACYL2 |
| Humidistat supplied | Model 62, with outdoor sensor | HumidiPRO H6062 |
| Size | ||
| Dimensions W × H × D | 10 1/8 × 20 7/8 × 7 1/8 in. | 11.5 × 21.5 × 6.75 in. |
| Humidifier, weight | 23 lb empty, 27 lb operating | 15 lb empty, 20 lb full |
| Status with the manufacturer | Spec sheet dated January 2026 (form 251, 01.26) | Document marked “legacy product, no longer manufactured” by Resideo |
US gallons. Values per the manufacturers' documents, cited below; none is certified by a third party the way heat pumps are.
Both are on AirGreen's site.
To choose, talk with our team: bring your panel voltage, the duct location and the distance to a drain.
Documents checked
Data checked November 10, 2026. Outputs, power, water, drain and dimensions: per the manufacturers' documents cited. Litres and kWh per litre: AirGreen's arithmetic on those values, formula shown. When two documents from the same manufacturer differ, the page says which one it follows.
Trademarks. AprilAire, Honeywell, Honeywell Home, Resideo and HumidiPRO are trademarks of their respective owners. The logos serve only to identify the products compared. AirGreen is a dealer of both brands; this page is not produced, sponsored or approved by the manufacturers.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong? Write to us: every figure reported is checked again.