How to read an HVI listing: airflow, static pressure and heat recovery

Home / Comparisons / Air exchangers

Guide · Air exchangers · The HVI directory

How to read an HVI listing: airflow, static pressure and heat recovery

AirGreen's comparison pages on air exchangers rely on the certified products directory of the Home Ventilating Institute (HVI). Each unit has a listing there: its airflow at ten static pressure steps, its heat recovery at 0 °C and sometimes at −25 °C, and the watts drawn in each test. This guide takes a real listing and explains it field by field, with HVI's definitions. It does not say which unit to choose.

Mandatory test: 0 °C Optional test: −25 °C, 72 hours To compare: same conditions, same net airflow
  1. Static pressureThe step that looks like your ducts.
  2. Net airflowThe fresh air delivered at that step.
  3. The testIts temperature and its airflow.
  4. SRE and wattsWhat is recovered, what is drawn.
Estimated running cost

The watts on the listing, in dollars per year

An air exchanger does not heat or cool: what it uses is fan power. The HVI listing gives the watts at each test point. Take a number from a listing, or one of the three examples, and see what it adds up to over a year.

Watts read on an HVI listing, test at 0 °C
Price per kWh (Rate D, April 1, 2026)
How this amount is calculated
  1. Power: the watts published by the HVI directory at a test point, or the value you choose. Examples: 28 W and 100 W (vänEE V160H75RT at 64 and 129 CFM), 66 W (LIFEBREATH 205 MAX at 64 CFM), all at 0 °C.
  2. Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
  3. Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.

HVI states that the watts on the listing are the average power measured during the test; they are not for sizing the electrical circuit, for which the manufacturer's electrical data is used. The amount covers the fans only.

AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the settings and how the unit is used; this amount is not a promise.

The annotated listing

A real directory listing, field by field

Here is the data of HVI directory listing 2505306, the vänEE V160H75RT. Tap a field in the listing, or a button, to see what it measures and how to use it to compare.

vänEE V160H75RTCategory: HRV · Brand owner: Venmar Ventilation ULC · HVI number: 2505306

Airflow

Static pressurein. w.c. · PaNet supply airflowCFM · L/sGross, supplyCFMGross, exhaustCFM

Energy performance

Test temperatureNet test airflowCFM · L/sPowerwattsSRE%Adjusted SRE%
0 °C6430 L/s287780
0 °C12961 L/s1006671
−25 °C6631 L/s436769

Test at −25 °C: ventilation reduction of 19.2% (supply) and 19.4% (exhaust) · airflow imbalance: 101.3%

Data: HVI directory, section III, data as of November 4, 2026. Layout by AirGreen; this table is not an HVI document.

Comparing two listings

Two lines compare when the temperature and the airflow are the same

HVI says so in the introduction to its directory: performance values should be compared only at equivalent outdoor conditions and net airflow. The airflow of each test is chosen by the manufacturer, so two listings do not always share a line. Choose one line in each listing.

vänEE V160H75RT HVI 2505306Line of the listing
LIFEBREATH 205 MAX HVI 2505460Line of the listing

The bars appear only when both lines have the same temperature and the same net airflow. They show published values, not a ranking: a higher number does not mean the same thing for recovery and for watts.

Not on the listing

What the HVI listing does not contain

The three section III tables we consult give airflows, efficiencies and watts. The rest is found in the manufacturer's documents, and our comparison pages say each time where the number comes from.

Sound level

No sound level column in the three section III tables. When a manufacturer publishes one, it appears on its specification sheet.

Defrost

The HVI listing gives the result of the very low temperature test, not the cycle itself. The start temperature and cycle times are read in the manufacturer's sheet or manual, when it publishes them.

Dimensions and ports

Width, height, weight, port diameter and position: the manufacturer's specification sheet.

Power supply

The watts on the HVI listing are a test average. Voltage, amps and circuit protection are read from the manufacturer's electrical data, as HVI points out.

Controls

Wall control included or optional, modes, timers: the manufacturer's documents.

Filters

Filter type and MERV rating: the manufacturer's specification sheet. HVI tests are run on the unit as submitted by the manufacturer.

HVI's instruction. For performance under conditions other than the test conditions, HVI refers to the equipment supplier: the listing holds for the conditions described, not beyond.
Questions

What people ask us about HVI listings

What is the HVI directory?

The Home Ventilating Institute publishes a directory of certified ventilation products. Its section III covers heat recovery ventilators (HRVs) and energy recovery ventilators (ERVs), tested to the CAN/CSA C439 standard. Each listed model has a number.

Is the −25 °C test mandatory?

No. Per HVI, the heating season test, at 0 °C, is mandatory. The very low temperature test is optional; it is usually run at −25 °C, but the manufacturer may choose another temperature below freezing. A listing with no −25 °C line means that test is not published there.

Why are two units not tested at the same airflow?

Because the net airflow of each test is chosen by the manufacturer. The vänEE V160H75RT is listed at 64 and 129 CFM at 0 °C; the LIFEBREATH 205 MAX at 49, 64 and 95 CFM. Their only shared point at 0 °C is 64 CFM.

What is the difference between SRE and adjusted SRE?

Both measure the sensible energy recovered by the fresh air. SRE accounts for the electricity the unit uses; HVI intends it for predicting and comparing heating season performance. Adjusted SRE removes that adjustment; HVI intends it for energy modelling, when fan watts are counted separately.

And the “apparent sensible effectiveness” on manufacturer sheets?

The section III cover pages we consulted do not define it. Manufacturer sheets that publish it, such as sheet 1109196G for the V160H75RT and sheet 205 MAX - 0826, state that this value is not HVI certified. Our pages do not use it.

What if the manufacturer's sheet and the directory disagree?

Our pages follow the directory and show the gap. Example: the LIFEBREATH MAX Series sales sheet, code 1124, publishes an SRE of 76% at 64 CFM for the 205 MAX; the HVI directory and technical sheet 205 MAX - 0826 publish 82%.

Glossary

Every field of the listing, in one line

Definitions drawn from the section III cover pages of the HVI directory, revision of December 29, 2017, summarized in our own words.

Field of the listingWhat HVI measuresHow to use it
External static pressureTotal static pressure loss through the supply or exhaust ductwork.Read both units at the same step.
Net supply airflowGross supply airflow minus measured cross-leakage: gross × (1 − EAT ÷ 100).It is the outdoor air actually delivered; it is used to size the unit for the required ventilation rate.
Gross airflowAirflow measured at the ports; it may include leakage between the two airstreams.Used for duct design, not for comparing delivered ventilation.
Test temperature0 °C: heating season, mandatory. −25 °C: very low temperature, optional, 72 hours. Indoor air at 22 °C and 40% relative humidity.Compare only lines at the same temperature.
Net test airflowNet airflow at which performance was measured; it is chosen by the manufacturer.Compare only lines at the same net airflow.
Power consumedwattsAverage power measured during the test.Used to estimate fan energy use; not to size the electrical circuit.
SREsensible recovery efficiencyNet sensible energy recovered by the fresh air, adjusted for electricity consumed, case losses, leakage, airflow imbalance and, at very low temperature, defrost.Used to predict and compare heating season performance.
Adjusted SRELike SRE, without the adjustment for electricity consumed.Used for energy modelling, when fan watts are counted separately.
Ventilation reductionvery low temperature testDrop, in percent, of supply and exhaust airflow at the end of the 72-hour test, compared with frost-free operation.Tells how much frost and defrost reduced ventilation during the test.
Airflow imbalancevery low temperature testImbalance, in percent, of supply airflow relative to exhaust airflow, averaged over the last 60 hours.HVI's pages give no reference value.
TRE and adjusted TREcooling seasonTotal energy recovered, sensible and latent, in the optional 35 °C test.Replaces SRE for cooling comparisons; it appears, for example, on the listing of the vänEE V160E75RT ERV (listing 2005455).

Both are on the AirGreen website.

A listing reads better with the house's ducts in front of you. Talk it over with our team: bring the floor area, the number of bedrooms and, if you have it, the model of the unit in place.

Sources and documents

Where each definition and each number comes from

HVI, section III cover pages“Rev. December 29, 2017” · definitions, test conditions, comparison rule · consulted November 9, 2026
HVI, Certified Products Directory, section IIIPublication 911, data as of November 4, 2026 · listings 2505306 (vänEE V160H75RT) and 2505460 (LIFEBREATH 205 MAX) · consulted November 9, 2026
V160H75RT and V160H75RS sheetBroan-NuTone LLC / Venmar Ventilation ULC, 1109196G, undated · “not HVI certified” note on apparent effectiveness · consulted November 9, 2026
LIFEBREATH 205 MAX sheetsTechnical sheet “205 MAX - 0826” and MAX Series sales sheet, code 1124 · consulted November 9, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · fan running cost