GREENTEK SOLACE 1.5H-EC and vänEE V160H75RT, HRV air exchangers

Home / Comparisons / Air exchangers

Comparison · HRV air exchanger · 150 to 172 CFM at 0.4 in. w.c.

GREENTEK SOLACE 1.5H-EC and vänEE V160H75RT: two recirculation defrosts, with the numbers

Two heat recovery ventilators (HRVs) with top ports, both listed in the HVI directory and both fitted with electronically commutated motors. At 0.4 in. w.c., the directory publishes 172 CFM for the SOLACE 1.5H-EC and 150 CFM for the V160H75RT. In winter, core defrost changes how they run: both do it by recirculation from −5 °C, and HVI tested them at −25 °C at the same airflow, 66 CFM.

At 0.4 in. w.c.: 172 and 150 CFM (HVI) At −25 °C and 66 CFM: SRE 68% and 67% At the same point: 47 W and 43 W Defrost: starts at −5 °C for both; minutes given in the V160H75RT sheet
GREENTEK SOLACE 1.5H-EC (AirGreen image)
GREENTEK

SOLACE 1.5H-EC

HRV, top ports · HVI 2505389

Sheet 445723 · manual 445712 · also listed in the directory as FANTECH HERO 150H-EC (2505258), same HVI values

See the product page
vänEE V160H75RT (AirGreen image)
vänEE

V160H75RT

HRV, top ports · HVI 2505306

Sheet 1109196G · guide 23831WEB · same HVI values as the BROAN-NUTONE V160H75RS (2505433): its other names

See the product page
Estimated running cost

What the fans cost, in dollars per year

An air exchanger does not heat or cool: what it uses is fan power. The HVI directory publishes the watts at each test point. At 0 °C, the two units share no test airflow: we show each unit's lowest test airflow, then its highest, with both airflows each time.

HVI test point, at 0 °C
Price per kWh (Rate D, April 1, 2026)
How this amount is calculated
  1. Power: the watts in the HVI directory at each 0 °C test point. Lowest test airflow: 23 W at 70 CFM (SOLACE 1.5H-EC) and 28 W at 64 CFM (V160H75RT). Highest test airflow: 89 W at 157 CFM (SOLACE 1.5H-EC) and 100 W at 129 CFM (V160H75RT).
  2. Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
  3. Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.

The test airflows differ at both points (70 and 64 CFM, then 157 and 129 CFM): the amount compares two test points, not two units set to the same airflow. At −25 °C, where both are tested at 66 CFM, the directory publishes 47 W and 43 W; that point is used in the defrost section, not in the yearly calculation. The amount covers the fans only.

AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the settings and how the unit is used; this amount is not a promise.

Defrost

Below −5 °C, two recirculation defrosts: what each document puts a number on

When it freezes outside, moisture in the air leaving the house frosts up in the core. Both units defrost by recirculation: for a few minutes, air from the house passes through the core again. The V160H75RT sheet publishes the length of each cycle by outdoor temperature and set airflow. The SOLACE 1.5H-EC sheet describes a preset sequence that adjusts itself, without giving its durations.

1. The principle, and what each sheet says

Choose the state of the unit. The drawing is a diagram of the recirculation defrost principle, not the layout of a unit.

GREENTEK SOLACE 1.5H-ECsheet 445723 · manual 445712
  • Type: internal recirculation defrost which, per the sheet, does not depressurize the home during the cycle.
  • Start: when the outdoor temperature falls below −5 °C (23 °F).
  • Sequence: preset, and it adjusts itself to operating conditions; fan speed is also adjusted between ventilation and defrost.
  • Damper: the manual mentions a defrost damper on the fresh-air intake.
  • Durations: neither the sheet nor the manual gives them.
vänEE V160H75RTsheet 1109196G · guide 23831WEB
  • Type: Homeshield recirculation defrost; stale air is recirculated into the house, which, per the sheet, reduces negative pressure.
  • Start: at −5 °C (23 °F) and below, read by a thermistor inside the unit, next to the fresh-air port.
  • Sequence: two modes in the unit's CFG OPT menu, Discretion (DIS, factory setting) and Plus (PLU, extended defrost for colder areas).
  • Damper: the sheet does not describe damper positions during the cycle.
  • Durations: published by temperature range and airflow, below.

2. One hour of operation, minute by minute

Choose the outdoor temperature. For the V160H75RT, sheet 1109196G also gives a different cycle depending on the set airflow and the defrost mode.

Outdoor temperature
Airflow set on the V160H75RT
V160H75RT defrost mode

3. What HVI measured at −25 °C, at the same airflow

The very low temperature test lasts 72 hours and includes each unit's defrost cycles. Both are tested at 66 CFM (31 L/s) of net fresh air: their numbers compare directly.

Same test for both: −25 °C, 66 CFM, 72 hours
GREENTEK SOLACE 1.5H-EC HVI 2505389vänEE V160H75RT HVI 2505306
Sensible recovery (SRE)defrost energy included in the calculation
68%
67%
Power consumedwatts published for this test
47W
43W
Drop in supply airflowat the end of the test, compared with frost-free operation
26.7%
19.2%
Drop in exhaust airflowat the end of the test, compared with frost-free operation
30.1%
19.4%

Ventilation reduction: per HVI, it is the drop, in percent, in supply and exhaust airflow at the end of the 72-hour test compared with frost-free operation; it comes from frost in the core and from airflow variation during defrost. HVI sets no reference value. SRE is the sensible recovery efficiency, adjusted among other things for electricity consumed and, at very low temperature, for defrost energy. The airflow-drop bars are drawn on a 0 to 100% scale.

Airflow and pressure

The more the ducts resist, the less air gets through: the two curves cross between 0.8 and 0.9 in. w.c.

External static pressure adds up the resistance of ducts, elbows, grilles and outdoor hoods. The HVI directory publishes each unit's net fresh-air flow at each step. Up to 0.8 in. w.c., the SOLACE 1.5H-EC shows the higher number; at 0.9 and 1.0 in. w.c., it is the V160H75RT.

GREENTEK SOLACE 1.5H-EC HVI 2505389vänEE V160H75RT HVI 2505306
Net airflow, gross airflowNet airflow is the fresh air actually delivered, once leakage between the two airstreams is taken out. It is the number HVI intends for sizing a unit to a required ventilation rate. Gross airflow is used for duct design.
What the curve does not sayThe actual pressure of an installation depends on its ducts; it is measured on site. GREENTEK sheet 445723 publishes the SOLACE 1.5H-EC airflow from 0.2 to 1.0 in. w.c., with the same numbers; the HVI directory adds the 0.1 in. w.c. step.
Construction

What is inside each cabinet, per the sheets

Both units have electronically commutated motors and top ports. The core, the factory filters and the way airflows are balanced are not the same. Each card says which document publishes it.

Recovery core

SOLACE 1.5H-EC: counter-flow core, thermoformed polymer plates, 14.4 × 14.4 in. by 12 in. deep. V160H75RT: cross-flow polypropylene, 12 × 12 × 9 in.

sheet 445723sheet 1109196G
Fans and motors

SOLACE 1.5H-EC: two electronically commutated (EC) motors, multiple speeds. V160H75RT: two PMSM ECM motors; airflow selected from 35 to 160 CFM on the unit's LCD.

sheet 445723sheet 1109196G
Factory filters

SOLACE 1.5H-EC: two washable electrostatic panel filters, UL 900 certified; MERV 8 and MERV 13 optional. V160H75RT: washable MERV 8; MERV 13 and HEPA optional.

sheet 445723 · catalogue E6132sheet 1109196G
Defrost

SOLACE 1.5H-EC: internal recirculation below −5 °C, preset sequence that adjusts to conditions; durations not given. V160H75RT: recirculation at −5 °C and below, times published by temperature range, Discretion and Plus modes.

sheet 445723sheet 1109196G
Airflow balancing

SOLACE 1.5H-EC: balancing done with the STS 2.0 touch screen wall control; balancing range 90 to 210 CFM. V160H75RT: Virtuo constant-airflow and auto-balancing device.

sheet 445723sheet 1109196G
Controls

SOLACE 1.5H-EC: compatible with all GREENTEK controls; ventilation, recirculation and standby modes. V160H75RT: LCD built into the unit; optional main and auxiliary wall controls.

sheet 445723 · catalogue E6132sheet 1109196G · guide 23831WEB
Condensate drain

SOLACE 1.5H-EC: drain hose kit included; a P-trap to be formed and filled with water. V160H75RT: integrated snap-in drain, hose included; a water trap loop to be formed.

manual 445712sheet 1109196G · guide 23831WEB
Cabinet

SOLACE 1.5H-EC: 22-gauge galvanized steel, prepainted steel door, 3/4 in. high-density expanded polystyrene insulation. V160H75RT: galvanized steel, one-piece molded expanded polystyrene insulation shell.

sheet 445723sheet 1109196G
Installation

Top ports on both, and seven inches apart in width

Both units have four 6 in. round ports on top. The SOLACE 1.5H-EC is 27 7/8 in. wide and 24 7/8 in. high; the V160H75RT, 21 in. wide and 21.5 in. high. Their depths are 13 3/8 in. and 16.3 in.

GREENTEK SOLACE 1.5H-EC27 7/8 × 13 3/8 × 24 7/8 in. (W × D × H) · 51 lb
GREENTEK SOLACE 1.5H-EC
vänEE V160H75RT21 × 16.3 × 21.5 in. (W × D × H) · 35 lb
vänEE V160H75RT

Left, the manufacturer photo, in perspective. Right, the outline of the front, width × height, to the same scale for both (diagram). Dimensions and weight per the manufacturer documents.

Installation, per the manufacturerGREENTEK SOLACE 1.5H-ECvänEE V160H75RT
Portsround4 metal connections, 6 in. (152 mm), on toprubberized seal4 ports, 6 in., on top
Dimensions W × D × H27 7/8 × 13 3/8 × 24 7/8 in.707 × 341 × 626 mm · sheet 44572321 × 16.3 × 21.5 in.broan-nutone.com product page
Unit weight51 lb22.96 kg, core included35 lb15.9 kg, core included
Service clearancein front of the unit14 in. (355 mm)to slide the core out8 in. (20.3 cm)in front of the door, required
MountingWall-mounted with the bracket supplied or hung by chains (supplied)Suspended by chains (included) or wall-mounted with 2 or 4 brackets (included)
Power supply120 V, single phase, 3.0 A3 ft cord120 V, 60 Hz, 2.4 A6 ft cord
Power stated on the sheet110 Wrated power on the sheet; not comparable to the HVI test watts163 Welectrical rating on the sheet; not comparable to the HVI test watts
Questions

What people ask us about these two units

Why the SOLACE 1.5H-EC, and not the SOLACE 1.5H?

In the SOLACE range, the model whose HVI airflow at 0.4 in. w.c. is closest to the V160H75RT (150 CFM) is the SOLACE 1.5H: also 150 CFM, listing 2505386. Its HVI values are the same as those of the FANTECH HERO 150H, already compared with the BROAN-NUTONE V160H75RS, which has the same HVI values as the V160H75RT: that page exists. This one therefore covers the SOLACE 1.5H-EC, the SOLACE model of this size with EC motors: 172 CFM at 0.4 in. w.c., and the same test airflow as the V160H75RT at −25 °C.

How long does a defrost last?

For the V160H75RT, sheet 1109196G publishes 8 minutes between −5 and −27 °C and 10 minutes at −27 °C and below; between two defrosts, the unit exchanges air for 12 to 50 minutes depending on temperature, set airflow and mode. For the SOLACE 1.5H-EC, sheet 445723 describes a preset sequence that adjusts to operating conditions and gives no duration. That silence does not mean the cycle is shorter or longer.

Is there fresh air during defrost?

A recirculation defrost passes house air through the core again to melt the frost. The V160H75RT sheet says stale air is recirculated into the house; the SOLACE manual mentions a defrost damper on the fresh-air intake. Neither document gives a fresh-air flow during the cycle. What HVI measures is the result over 72 hours at −25 °C: the drop in airflow at the end of the test.

Which one recovers more heat?

At the only shared test point, −25 °C and 66 CFM, the HVI directory publishes an SRE of 68% for the SOLACE 1.5H-EC and 67% for the V160H75RT; adjusted SRE is 69% for both. At 0 °C, the tests are not at the same airflow: 84% at 70 CFM for the SOLACE 1.5H-EC, 77% at 64 CFM for the V160H75RT, and HVI states that units should be compared only at equivalent net airflow.

What does the ventilation reduction at −25 °C mean?

The very low temperature test lasts 72 hours. HVI publishes by how much, in percent, supply and exhaust airflow dropped at the end of the test compared with frost-free operation; the drop comes from frost in the core and from defrost cycles. At 66 CFM for both, the directory publishes 26.7% and 30.1% for the SOLACE 1.5H-EC, 19.2% and 19.4% for the V160H75RT.

Are they ENERGY STAR certified?

The documents do not all say the same thing. GREENTEK sheet 445723 and sheet 1109196G each say the unit meets ENERGY STAR requirements only when used in Canada. The V160H75RT product page on broan-nutone.com says “no”. Current status can be checked on the Natural Resources Canada list.

What about noise and warranty?

The documents consulted publish no sound level for these two models, and this page does not compare warranties. The warranty documents for the unit chosen come with the quote.

Do these units go by other names?

The HVI directory lists a FANTECH HERO 150H-EC (listing 2505258) with the same airflows and the same recovery values as the SOLACE 1.5H-EC. It also lists a V160H75RT under the Venmar brand (2505350) and a BROAN-NUTONE V160H75RS (2505433) with the same values as the vänEE V160H75RT; sheet 1109196G carries the names Broan-NuTone LLC and Venmar Ventilation ULC.

All the values

Every value in the HVI directory

HVI directory, section III, data as of November 4, 2026. Airflows at the same static pressure and the values of the −25 °C test, run at the same airflow, compare directly; the 0 °C test points do not.

MeasurementGREENTEK SOLACE 1.5H-ECvänEE V160H75RT
Net supply airflow, same static pressure
Airflow at 0.1 in. w.c. (25 Pa)197 CFM163 CFM
Airflow at 0.2 in. w.c. (50 Pa)189 CFM159 CFM
Airflow at 0.3 in. w.c. (75 Pa)180 CFM155 CFM
Airflow at 0.4 in. w.c. (100 Pa)172 CFM150 CFM
Airflow at 0.5 in. w.c. (125 Pa)161 CFM144 CFM
Airflow at 0.6 in. w.c. (150 Pa)153 CFM140 CFM
Airflow at 0.7 in. w.c. (175 Pa)142 CFM133 CFM
Airflow at 0.8 in. w.c. (200 Pa)131 CFM127 CFM
Airflow at 0.9 in. w.c. (225 Pa)119 CFM121 CFM
Airflow at 1.0 in. w.c. (250 Pa)106 CFM114 CFM
Very low temperature test, −25 °C, same test airflow: 66 CFM (31 L/s)
Sensible recovery efficiency (SRE)68 %67 %
Adjusted sensible recovery efficiency69 %69 %
Power consumed47 W43 W
Ventilation reduction, supplyat the end of the 72 h test26.7%19.2%
Ventilation reduction, exhaustat the end of the 72 h test30.1%19.4%
Test points at 0 °C, different airflows
Lowest test airflownet fresh air70 CFM (33 L/s), 23 WSRE 84%, adjusted 86%64 CFM (30 L/s), 28 WSRE 77%, adjusted 80%
Highest test airflownet fresh air157 CFM (74 L/s), 89 WSRE 77%, adjusted 81%129 CFM (61 L/s), 100 WSRE 66%, adjusted 71%
Defrost, per the manufacturer
Defrost: type and startInternal recirculation, below −5 °Csheet 445723Homeshield recirculation, at −5 °C and belowsheet 1109196G
Defrost: length of one cycleNot published by the manufacturerpreset sequence, adjusted to operating conditions8 min from −5 to −27 °C, 10 min at −27 °C and below12 to 50 min of air exchange between two cycles
Certification
HVI directory, section IIIYes, listing 2505389Yes, listing 2505306
ENERGY STARSheet 445723: yes, in Canada onlySheet 1109196G: yes, in Canada onlybroan-nutone.com page: no

“Higher” marks the higher value of the same measurement, under the same conditions. It is not a recommendation: for power or for ventilation reduction, the higher number is not an advantage. Only airflows at the same static pressure and the values of the −25 °C test are marked. The SOLACE 1.5H-EC is also tested at 106 CFM at 0 °C (37 W, SRE 80%, adjusted 83%). The Venmar listing of the V160H75RT (2505350) also publishes points at 36 CFM (18 W, SRE 82%, adjusted 85%) and 47 CFM (22 W, SRE 79%, adjusted 82%).

Both are on the AirGreen website.

The right choice depends on the ventilation rate the house needs, the resistance of its ducts and the room available on the wall or ceiling. Talk it over with our team.

Sources and documents

Where each number comes from

HVI, Certified Products Directory, section IIIPublication 911, data as of November 4, 2026 · listings 2505389, 2505306, 2505386, 2505381, 2505258, 2505350 and 2505433 · consulted November 10, 2026
HVI, section III cover pagesRev. 20171229 · definitions of net airflow, SRE, the very low temperature test and ventilation reduction · consulted November 9, 2026
GREENTEK SOLACE 1.5H-EC specification sheetLiterature item 445723, rev. 2025-11-25, greentek.ca · defrost, construction, dimensions, airflows · consulted November 10, 2026
SOLACE Series installation, operation and maintenance manualGREENTEK, item 445712, rev. 2022-12-12 · defrost damper, drain, mounting, controls · consulted November 10, 2026
GREENTEK catalogue, residential HRVs and ERVsArt. E6132, June 2025 · SOLACE model table, optional filters, operating modes · consulted November 10, 2026
V160H75RT and V160H75RS sheetBroan-NuTone LLC / Venmar Ventilation ULC, 1109196G, undated · Discretion and Plus defrost tables · consulted November 10, 2026
Installation and user guide, HRVs and ERVsBroan-NuTone LLC / Venmar Ventilation ULC, 23831WEB, rev. W, undated · DEF option (DIS, PLU), CFG OPT menu, drain · consulted November 10, 2026
V160H75RT product page, broan-nutone.comDimensions, weight, ENERGY STAR: no · consulted November 10, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · fan running cost