Home / Comparisons / Air exchangers
GREENTEK SOLACE 1.5H-EC and vänEE V160H75RT: two recirculation defrosts, with the numbers
Two heat recovery ventilators (HRVs) with top ports, both listed in the HVI directory and both fitted with electronically commutated motors. At 0.4 in. w.c., the directory publishes 172 CFM for the SOLACE 1.5H-EC and 150 CFM for the V160H75RT. In winter, core defrost changes how they run: both do it by recirculation from −5 °C, and HVI tested them at −25 °C at the same airflow, 66 CFM.
Three measurements, one source
HVI directory, section III · SOLACE 1.5H-EC V160H75RT
SOLACE 1.5H-EC
HRV, top ports · HVI 2505389
Sheet 445723 · manual 445712 · also listed in the directory as FANTECH HERO 150H-EC (2505258), same HVI values
See the product page
V160H75RT
HRV, top ports · HVI 2505306
Sheet 1109196G · guide 23831WEB · same HVI values as the BROAN-NUTONE V160H75RS (2505433): its other names
See the product pageWhat the fans cost, in dollars per year
An air exchanger does not heat or cool: what it uses is fan power. The HVI directory publishes the watts at each test point. At 0 °C, the two units share no test airflow: we show each unit's lowest test airflow, then its highest, with both airflows each time.
How this amount is calculated
- Power: the watts in the HVI directory at each 0 °C test point. Lowest test airflow: 23 W at 70 CFM (SOLACE 1.5H-EC) and 28 W at 64 CFM (V160H75RT). Highest test airflow: 89 W at 157 CFM (SOLACE 1.5H-EC) and 100 W at 129 CFM (V160H75RT).
- Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
- Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.
The test airflows differ at both points (70 and 64 CFM, then 157 and 129 CFM): the amount compares two test points, not two units set to the same airflow. At −25 °C, where both are tested at 66 CFM, the directory publishes 47 W and 43 W; that point is used in the defrost section, not in the yearly calculation. The amount covers the fans only.
AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the settings and how the unit is used; this amount is not a promise.
Below −5 °C, two recirculation defrosts: what each document puts a number on
When it freezes outside, moisture in the air leaving the house frosts up in the core. Both units defrost by recirculation: for a few minutes, air from the house passes through the core again. The V160H75RT sheet publishes the length of each cycle by outdoor temperature and set airflow. The SOLACE 1.5H-EC sheet describes a preset sequence that adjusts itself, without giving its durations.
1. The principle, and what each sheet says
Choose the state of the unit. The drawing is a diagram of the recirculation defrost principle, not the layout of a unit.
- Type: internal recirculation defrost which, per the sheet, does not depressurize the home during the cycle.
- Start: when the outdoor temperature falls below −5 °C (23 °F).
- Sequence: preset, and it adjusts itself to operating conditions; fan speed is also adjusted between ventilation and defrost.
- Damper: the manual mentions a defrost damper on the fresh-air intake.
- Durations: neither the sheet nor the manual gives them.
- Type: Homeshield recirculation defrost; stale air is recirculated into the house, which, per the sheet, reduces negative pressure.
- Start: at −5 °C (23 °F) and below, read by a thermistor inside the unit, next to the fresh-air port.
- Sequence: two modes in the unit's CFG OPT menu, Discretion (DIS, factory setting) and Plus (PLU, extended defrost for colder areas).
- Damper: the sheet does not describe damper positions during the cycle.
- Durations: published by temperature range and airflow, below.
2. One hour of operation, minute by minute
Choose the outdoor temperature. For the V160H75RT, sheet 1109196G also gives a different cycle depending on the set airflow and the defrost mode.
3. What HVI measured at −25 °C, at the same airflow
The very low temperature test lasts 72 hours and includes each unit's defrost cycles. Both are tested at 66 CFM (31 L/s) of net fresh air: their numbers compare directly.
Same test for both: −25 °C, 66 CFM, 72 hoursVentilation reduction: per HVI, it is the drop, in percent, in supply and exhaust airflow at the end of the 72-hour test compared with frost-free operation; it comes from frost in the core and from airflow variation during defrost. HVI sets no reference value. SRE is the sensible recovery efficiency, adjusted among other things for electricity consumed and, at very low temperature, for defrost energy. The airflow-drop bars are drawn on a 0 to 100% scale.
The more the ducts resist, the less air gets through: the two curves cross between 0.8 and 0.9 in. w.c.
External static pressure adds up the resistance of ducts, elbows, grilles and outdoor hoods. The HVI directory publishes each unit's net fresh-air flow at each step. Up to 0.8 in. w.c., the SOLACE 1.5H-EC shows the higher number; at 0.9 and 1.0 in. w.c., it is the V160H75RT.
What is inside each cabinet, per the sheets
Both units have electronically commutated motors and top ports. The core, the factory filters and the way airflows are balanced are not the same. Each card says which document publishes it.
SOLACE 1.5H-EC: counter-flow core, thermoformed polymer plates, 14.4 × 14.4 in. by 12 in. deep. V160H75RT: cross-flow polypropylene, 12 × 12 × 9 in.
SOLACE 1.5H-EC: two electronically commutated (EC) motors, multiple speeds. V160H75RT: two PMSM ECM motors; airflow selected from 35 to 160 CFM on the unit's LCD.
SOLACE 1.5H-EC: two washable electrostatic panel filters, UL 900 certified; MERV 8 and MERV 13 optional. V160H75RT: washable MERV 8; MERV 13 and HEPA optional.
SOLACE 1.5H-EC: internal recirculation below −5 °C, preset sequence that adjusts to conditions; durations not given. V160H75RT: recirculation at −5 °C and below, times published by temperature range, Discretion and Plus modes.
SOLACE 1.5H-EC: balancing done with the STS 2.0 touch screen wall control; balancing range 90 to 210 CFM. V160H75RT: Virtuo constant-airflow and auto-balancing device.
SOLACE 1.5H-EC: compatible with all GREENTEK controls; ventilation, recirculation and standby modes. V160H75RT: LCD built into the unit; optional main and auxiliary wall controls.
SOLACE 1.5H-EC: drain hose kit included; a P-trap to be formed and filled with water. V160H75RT: integrated snap-in drain, hose included; a water trap loop to be formed.
SOLACE 1.5H-EC: 22-gauge galvanized steel, prepainted steel door, 3/4 in. high-density expanded polystyrene insulation. V160H75RT: galvanized steel, one-piece molded expanded polystyrene insulation shell.
Top ports on both, and seven inches apart in width
Both units have four 6 in. round ports on top. The SOLACE 1.5H-EC is 27 7/8 in. wide and 24 7/8 in. high; the V160H75RT, 21 in. wide and 21.5 in. high. Their depths are 13 3/8 in. and 16.3 in.


Left, the manufacturer photo, in perspective. Right, the outline of the front, width × height, to the same scale for both (diagram). Dimensions and weight per the manufacturer documents.
| Installation, per the manufacturer | GREENTEK SOLACE 1.5H-EC | vänEE V160H75RT |
|---|---|---|
| Portsround | 4 metal connections, 6 in. (152 mm), on toprubberized seal | 4 ports, 6 in., on top |
| Dimensions W × D × H | 27 7/8 × 13 3/8 × 24 7/8 in.707 × 341 × 626 mm · sheet 445723 | 21 × 16.3 × 21.5 in.broan-nutone.com product page |
| Unit weight | 51 lb22.96 kg, core included | 35 lb15.9 kg, core included |
| Service clearancein front of the unit | 14 in. (355 mm)to slide the core out | 8 in. (20.3 cm)in front of the door, required |
| Mounting | Wall-mounted with the bracket supplied or hung by chains (supplied) | Suspended by chains (included) or wall-mounted with 2 or 4 brackets (included) |
| Power supply | 120 V, single phase, 3.0 A3 ft cord | 120 V, 60 Hz, 2.4 A6 ft cord |
| Power stated on the sheet | 110 Wrated power on the sheet; not comparable to the HVI test watts | 163 Welectrical rating on the sheet; not comparable to the HVI test watts |
What people ask us about these two units
Why the SOLACE 1.5H-EC, and not the SOLACE 1.5H?
In the SOLACE range, the model whose HVI airflow at 0.4 in. w.c. is closest to the V160H75RT (150 CFM) is the SOLACE 1.5H: also 150 CFM, listing 2505386. Its HVI values are the same as those of the FANTECH HERO 150H, already compared with the BROAN-NUTONE V160H75RS, which has the same HVI values as the V160H75RT: that page exists. This one therefore covers the SOLACE 1.5H-EC, the SOLACE model of this size with EC motors: 172 CFM at 0.4 in. w.c., and the same test airflow as the V160H75RT at −25 °C.
How long does a defrost last?
For the V160H75RT, sheet 1109196G publishes 8 minutes between −5 and −27 °C and 10 minutes at −27 °C and below; between two defrosts, the unit exchanges air for 12 to 50 minutes depending on temperature, set airflow and mode. For the SOLACE 1.5H-EC, sheet 445723 describes a preset sequence that adjusts to operating conditions and gives no duration. That silence does not mean the cycle is shorter or longer.
Is there fresh air during defrost?
A recirculation defrost passes house air through the core again to melt the frost. The V160H75RT sheet says stale air is recirculated into the house; the SOLACE manual mentions a defrost damper on the fresh-air intake. Neither document gives a fresh-air flow during the cycle. What HVI measures is the result over 72 hours at −25 °C: the drop in airflow at the end of the test.
Which one recovers more heat?
At the only shared test point, −25 °C and 66 CFM, the HVI directory publishes an SRE of 68% for the SOLACE 1.5H-EC and 67% for the V160H75RT; adjusted SRE is 69% for both. At 0 °C, the tests are not at the same airflow: 84% at 70 CFM for the SOLACE 1.5H-EC, 77% at 64 CFM for the V160H75RT, and HVI states that units should be compared only at equivalent net airflow.
What does the ventilation reduction at −25 °C mean?
The very low temperature test lasts 72 hours. HVI publishes by how much, in percent, supply and exhaust airflow dropped at the end of the test compared with frost-free operation; the drop comes from frost in the core and from defrost cycles. At 66 CFM for both, the directory publishes 26.7% and 30.1% for the SOLACE 1.5H-EC, 19.2% and 19.4% for the V160H75RT.
Are they ENERGY STAR certified?
The documents do not all say the same thing. GREENTEK sheet 445723 and sheet 1109196G each say the unit meets ENERGY STAR requirements only when used in Canada. The V160H75RT product page on broan-nutone.com says “no”. Current status can be checked on the Natural Resources Canada list.
What about noise and warranty?
The documents consulted publish no sound level for these two models, and this page does not compare warranties. The warranty documents for the unit chosen come with the quote.
Do these units go by other names?
The HVI directory lists a FANTECH HERO 150H-EC (listing 2505258) with the same airflows and the same recovery values as the SOLACE 1.5H-EC. It also lists a V160H75RT under the Venmar brand (2505350) and a BROAN-NUTONE V160H75RS (2505433) with the same values as the vänEE V160H75RT; sheet 1109196G carries the names Broan-NuTone LLC and Venmar Ventilation ULC.
Every value in the HVI directory
HVI directory, section III, data as of November 4, 2026. Airflows at the same static pressure and the values of the −25 °C test, run at the same airflow, compare directly; the 0 °C test points do not.
| Measurement | GREENTEK SOLACE 1.5H-EC | vänEE V160H75RT |
|---|---|---|
| Net supply airflow, same static pressure | ||
| Airflow at 0.1 in. w.c. (25 Pa) | 197 CFM | 163 CFM |
| Airflow at 0.2 in. w.c. (50 Pa) | 189 CFM | 159 CFM |
| Airflow at 0.3 in. w.c. (75 Pa) | 180 CFM | 155 CFM |
| Airflow at 0.4 in. w.c. (100 Pa) | 172 CFM | 150 CFM |
| Airflow at 0.5 in. w.c. (125 Pa) | 161 CFM | 144 CFM |
| Airflow at 0.6 in. w.c. (150 Pa) | 153 CFM | 140 CFM |
| Airflow at 0.7 in. w.c. (175 Pa) | 142 CFM | 133 CFM |
| Airflow at 0.8 in. w.c. (200 Pa) | 131 CFM | 127 CFM |
| Airflow at 0.9 in. w.c. (225 Pa) | 119 CFM | 121 CFM |
| Airflow at 1.0 in. w.c. (250 Pa) | 106 CFM | 114 CFM |
| Very low temperature test, −25 °C, same test airflow: 66 CFM (31 L/s) | ||
| Sensible recovery efficiency (SRE) | 68 % | 67 % |
| Adjusted sensible recovery efficiency | 69 % | 69 % |
| Power consumed | 47 W | 43 W |
| Ventilation reduction, supplyat the end of the 72 h test | 26.7% | 19.2% |
| Ventilation reduction, exhaustat the end of the 72 h test | 30.1% | 19.4% |
| Test points at 0 °C, different airflows | ||
| Lowest test airflownet fresh air | 70 CFM (33 L/s), 23 WSRE 84%, adjusted 86% | 64 CFM (30 L/s), 28 WSRE 77%, adjusted 80% |
| Highest test airflownet fresh air | 157 CFM (74 L/s), 89 WSRE 77%, adjusted 81% | 129 CFM (61 L/s), 100 WSRE 66%, adjusted 71% |
| Defrost, per the manufacturer | ||
| Defrost: type and start | Internal recirculation, below −5 °Csheet 445723 | Homeshield recirculation, at −5 °C and belowsheet 1109196G |
| Defrost: length of one cycle | Not published by the manufacturerpreset sequence, adjusted to operating conditions | 8 min from −5 to −27 °C, 10 min at −27 °C and below12 to 50 min of air exchange between two cycles |
| Certification | ||
| HVI directory, section III | Yes, listing 2505389 | Yes, listing 2505306 |
| ENERGY STAR | Sheet 445723: yes, in Canada only | Sheet 1109196G: yes, in Canada onlybroan-nutone.com page: no |
“Higher” marks the higher value of the same measurement, under the same conditions. It is not a recommendation: for power or for ventilation reduction, the higher number is not an advantage. Only airflows at the same static pressure and the values of the −25 °C test are marked. The SOLACE 1.5H-EC is also tested at 106 CFM at 0 °C (37 W, SRE 80%, adjusted 83%). The Venmar listing of the V160H75RT (2505350) also publishes points at 36 CFM (18 W, SRE 82%, adjusted 85%) and 47 CFM (22 W, SRE 79%, adjusted 82%).
Both are on the AirGreen website.
The right choice depends on the ventilation rate the house needs, the resistance of its ducts and the room available on the wall or ceiling. Talk it over with our team.
Where each number comes from
Data verified on November 10, 2026. Airflow, heat recovery, power and ventilation reduction: HVI directory. Defrost, dimensions, weight, construction and controls: per the manufacturer. When a manufacturer document contradicts the HVI directory, the directory prevails.
Trademarks. GREENTEK, SOLACE, FANTECH, HERO, vänEE, Venmar, BROAN-NUTONE, Broan, Virtuo and Homeshield are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer for both brands; this page is not produced, sponsored or approved by the manufacturers. Data colours: the green of the vänEE logo; AirGreen teal for GREENTEK, whose logo green would be confused with vänEE's.