LIFEBREATH 205 MAX and BROAN-NUTONE V160H75RS, HRV air exchangers

Home / Comparisons / Air exchangers

Comparison · HRV air exchanger · 150 to 170 CFM at 0.4 in. w.c.

LIFEBREATH 205 MAX and BROAN-NUTONE V160H75RS: what each one moves, recovers and draws

Two heat recovery ventilators (HRVs) for houses, both listed in the HVI directory. They are not the same size: at 0.4 in. w.c., the directory publishes 170 CFM for the 205 MAX and 150 CFM for the V160H75RS. At 0 °C, the two share one test point, 64 CFM, and that is where their numbers compare directly. This page follows the HVI directory and shows the manufacturer sheets alongside.

At 0.4 in. w.c.: 170 and 150 CFM (HVI) At 0 °C and 64 CFM: SRE 82% and 77% At the same point: 66 W and 28 W LIFEBREATH at 64 CFM: 76% (sales sheet 1124), 82% (HVI and sheet 0826)
LIFEBREATH 205 MAX (AirGreen image)
LIFEBREATH

205 MAX

HRV, top ports · HVI 2505460

Sheet 205 MAX - 0826 · MAX Series sales sheet 1124

See the product page
BROAN-NUTONE V160H75RS (AirGreen image)
BROAN-NUTONE

V160H75RS

HRV, side ports · HVI 2505433

Sheet 1109196G · also listed in the directory under vänEE (2505311) and Venmar (2505348), same HVI values

See the product page
Estimated running cost

What the fans cost, in dollars per year

An air exchanger does not heat or cool: what it uses is fan power. The HVI directory publishes the watts at each test point. At 0 °C, both units are tested at 64 CFM; we start with that shared point, then show each unit's highest test airflow.

HVI test point, at 0 °C
Price per kWh (Rate D, April 1, 2026)
How this amount is calculated
  1. Power: the watts in the HVI directory at each 0 °C test point. Shared point, 64 CFM: 66 W (205 MAX) and 28 W (V160H75RS). Highest test airflow: 86 W at 95 CFM (205 MAX) and 100 W at 129 CFM (V160H75RS).
  2. Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
  3. Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.

At the shared point, the two amounts compare two units moving the same fresh-air flow. At the highest test airflow, the flows differ (95 and 129 CFM): the amount then compares two test points, not two units set the same way. The amount covers the fans only; recovered heat is covered in the next section.

AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the settings and how the unit is used; this amount is not a promise.

One hour, counted

One hour of ventilation, counted with the HVI directory numbers

Over one hour at its test airflow, each unit replaces a certain volume of air, uses a certain amount of electricity and recovers part of the heat that was leaving. All three numbers come from the same line of the directory. Choose the test temperature.

SRE: sensible recovery efficiency. Per HVI, it is the net sensible energy recovered by the fresh air, adjusted for electricity consumed, case losses, leakage, airflow imbalance and, at very low temperature, defrost energy, as a percentage of the sensible energy that could be recovered. HVI states that units should be compared only at equivalent outdoor conditions and net airflow. The drawing of the two airstreams is a diagram.

Airflow and pressure

The more the ducts resist, the less air gets through: the two curves cross at 0.8 in. w.c.

External static pressure adds up the resistance of ducts, elbows, grilles and outdoor hoods. The HVI directory publishes each unit's net fresh-air flow at each step. Up to 0.7 in. w.c., the 205 MAX shows the higher number; at 0.8 in. w.c., both are at 127 CFM; at 0.9 and 1.0 in. w.c., it is the V160H75RS.

LIFEBREATH 205 MAX HVI 2505460BROAN-NUTONE V160H75RS HVI 2505433
Net airflow, gross airflowNet airflow is the fresh air actually delivered, once leakage between the two airstreams is taken out. It is the number HVI intends for sizing a unit to a required ventilation rate. Gross airflow is used for duct design.
What the curve does not sayThe actual pressure of an installation depends on its ducts; it is measured on site. LIFEBREATH sheet 0826 publishes the 205 MAX airflow up to 0.9 in. w.c.; the HVI directory adds the 1.0 in. w.c. step.
Construction

What is inside each cabinet, per the sheets

The manufacturer sheets describe two different builds: a counter-flow core and a PSC motor on one side, a cross-flow core and two ECM motors on the other. Each card says which document publishes it.

Recovery core

205 MAX: counter-flow HEX core, thermally conductive, removable for cleaning. V160H75RS: cross-flow polypropylene, 12 × 12 × 9 in.

sheet 0826sheet 1109196G
Fans and motors

205 MAX: centrifugal blowers, multi-speed PSC motor; high speed factory-set to Hi3, adjustable with DIP switches. V160H75RS: two PMSM ECM motors; airflow selected from 35 to 160 CFM on the unit's LCD.

sheet 0826sheet 1109196G
Factory filters

205 MAX: washable MERV 6 filters on both the fresh and stale airstreams; MERV 13 optional. V160H75RS: washable MERV 8; MERV 13 and HEPA optional.

sheet 0826sheet 1109196G
Defrost

205 MAX: recirculating damper; the sheet publishes no start temperature or cycle time. V160H75RS: recirculation from −5 °C, times published by temperature range, Discretion and Plus modes.

sheet 0826sheet 1109196G
Airflow balancing

205 MAX: balancing ports on the door and adjustable dampers on the collars. V160H75RS: Virtuo constant-airflow and auto-balancing device, motorized dampers.

sheet 0826sheet 1109196G
Controls

205 MAX: DXPL03 digital wall control included. V160H75RS: LCD built into the unit; optional wall controls, described in the manufacturer's wall control sheet.

sheet 0826sheet 1109196G
Condensate drain

205 MAX: two 1/2 in. (12 mm) drain connections. V160H75RS: integrated snap-in drain, hose included.

sheet 0826sheet 1109196G
Cabinet

205 MAX: 22-gauge prepainted galvanized steel, insulated. V160H75RS: galvanized steel, one-piece molded expanded polystyrene insulation shell.

sheet 0826sheet 1109196G
Installation

Ports on top or on the side, and ten inches apart in width

The 205 MAX has its four 6 in. round collars on top and is 33 5/8 in. wide. The V160H75RS has its 6 in. ports on the side and is 23.5 in. wide. The two heights are close: 18 3/4 in. and 19.13 in.

LIFEBREATH 205 MAX33 5/8 × 15 × 18 3/4 in. (W × D × H) · 57 lb
LIFEBREATH 205 MAX
BROAN-NUTONE V160H75RS23.5 × 16.3 × 19.13 in. (W × D × H) · 35 lb
BROAN-NUTONE V160H75RS

Left, the manufacturer photo, in perspective. Right, the outline of the front, width × height, to the same scale for both (diagram). Dimensions and weight per the manufacturer documents.

Installation, per the manufacturerLIFEBREATH 205 MAXBROAN-NUTONE V160H75RS
Portsround4 collars, 6 in. (150 mm), on top4 ports, 6 in., on the side
Dimensions W × D × H33 5/8 × 15 × 18 3/4 in.854 × 381 × 476 mm · sheet 082623.5 × 16.3 × 19.13 in.broan-nutone.com product page
Unit weight57 lb25.8 kg35 lb15.9 kg, core included
Service clearance, in front of the door25 in. (635 mm), recommended8 in. (20.3 cm), required
MountingSuspended: four threaded inserts, S hooks and straps suppliedSuspended by chains (included) or wall-mounted with 2 or 4 brackets (included)
Power supply120 V, 60 Hz, 1.4 AMCA 2.0 A · MOP 15 A120 V, 60 Hz, 2.4 A6 ft cord
Power stated on the sheet66 W at 64 CFMsame value as the HVI directory163 Welectrical rating on the sheet; different method, not comparable
Questions

What people ask us about these two units

Why compare two units that do not have the same airflow?

Because they often end up on the same short list for a house, and the HVI directory gives enough to read them side by side: each unit's airflow at the same static pressure, and a shared test point at 0 °C, 64 CFM. The page says throughout when the conditions are the same and when they are not.

Which one recovers more heat?

At the only shared test point, 0 °C and 64 CFM, the HVI directory publishes an SRE of 82% for the 205 MAX and 77% for the V160H75RS. At −25 °C, the two tests are not at the same airflow (70 and 66 CFM): the directory publishes 69% and 67%, and HVI states that units should be compared only at equivalent net airflow.

Why does the LIFEBREATH sales sheet say 76%?

The MAX Series sales sheet, code 1124, publishes for the 205 MAX an SRE of 76% at 64 CFM and 193, 182 and 170 CFM at 0.2, 0.3 and 0.4 in. w.c. The HVI directory (listing 2505460) and technical sheet 205 MAX - 0826 publish 82% at 64 CFM and 191, 180 and 170 CFM. This page follows the HVI directory.

What does the ventilation reduction at −25 °C mean?

The very low temperature test lasts 72 hours. HVI publishes by how much, in percent, supply and exhaust airflow dropped at the end of the test compared with frost-free operation; the drop comes from frost in the core and from defrost cycles. The directory publishes 37.5% and 43.8% for the 205 MAX at 70 CFM, 19.2% and 19.4% for the V160H75RS at 66 CFM.

Are they ENERGY STAR certified?

The documents do not all say the same thing. For the 205 MAX, sales sheet 1124 says “no”. For the V160H75RS, sheet 1109196G says the unit meets ENERGY STAR requirements only when used in Canada, and the broan-nutone.com product page says “no”. Current status can be checked on the Natural Resources Canada list.

What about noise and warranty?

The documents consulted publish no sound level for these two models, and this page does not compare warranties. The warranty documents for the unit chosen come with the quote.

Does the V160H75RS go by other names?

The HVI directory also lists a V160H75RS under the vänEE (listing 2505311) and Venmar (2505348) brands, with the same airflows and the same recovery values as Broan listing 2505433. Sheet 1109196G carries the names Broan-NuTone LLC and Venmar Ventilation ULC.

All the values

Every value in the HVI directory

HVI directory, section III, data as of November 4, 2026. Airflows at the same static pressure and the values at the shared test point compare directly; the other points do not.

MeasurementLIFEBREATH 205 MAXBROAN-NUTONE V160H75RS
Net supply airflow, same static pressure
Airflow at 0.1 in. w.c. (25 Pa)199 CFM163 CFM
Airflow at 0.2 in. w.c. (50 Pa)191 CFM159 CFM
Airflow at 0.3 in. w.c. (75 Pa)180 CFM155 CFM
Airflow at 0.4 in. w.c. (100 Pa)170 CFM150 CFM
Airflow at 0.5 in. w.c. (125 Pa)159 CFM144 CFM
Airflow at 0.6 in. w.c. (150 Pa)148 CFM140 CFM
Airflow at 0.7 in. w.c. (175 Pa)138 CFM133 CFM
Airflow at 0.8 in. w.c. (200 Pa)127 CFM127 CFM
Airflow at 0.9 in. w.c. (225 Pa)114 CFM121 CFM
Airflow at 1.0 in. w.c. (250 Pa)102 CFM114 CFM
Test at 0 °C, same test airflow: 64 CFM (30 L/s)
Sensible recovery efficiency (SRE)82 %77 %
Adjusted sensible recovery efficiency89 %80 %
Power consumed66 W28 W
Other test points at 0 °C, different airflows
Lowest test airflownet fresh air49 CFM, 58 WSRE 83%, adjusted 91%36 CFM, 18 WSRE 82%, adjusted 85%
Highest test airflownet fresh air95 CFM, 86 WSRE 79%, adjusted 85%129 CFM, 100 WSRE 66%, adjusted 71%
Very low temperature test, −25 °C, different test airflows
Test airflownet fresh air70 CFM (33 L/s), 117 W66 CFM (31 L/s), 43 W
Sensible recovery efficiency (SRE)69%adjusted 74%67%adjusted 69%
Ventilation reduction during the testsupply · exhaust37.5% · 43.8%19.2% · 19.4%
Certification
HVI directory, section IIIYes, listing 2505460Yes, listing 2505433
ENERGY STARSales sheet 1124: noSheet 1109196G: yes, in Canada onlybroan-nutone.com page: no

“Higher” marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Only airflows at the same static pressure and the values at the shared test point are marked. The V160H75RS is also tested at 47 CFM (22 W, SRE 79%, adjusted 82%).

Both are on the AirGreen website.

The right choice depends on the ventilation rate the house needs, the resistance of its ducts and the room available for the ports. Talk it over with our team.

Sources and documents

Where each number comes from

HVI, Certified Products Directory, section IIIPublication 911, data as of November 4, 2026 · listings 2505460 and 2505433 · consulted November 9, 2026
HVI, section III cover pagesRev. 20171229 · definitions of net airflow, SRE and the very low temperature test · consulted November 9, 2026
LIFEBREATH 205 MAX specification sheet“205 MAX - 0826” and French version “205 MAX FRE - 0826”, lifebreath.com · consulted November 9, 2026
LIFEBREATH MAX Series sales sheetCode 1124 · model table (205 MAX: 76% at 64 CFM) · consulted November 9, 2026
BROAN-NUTONE V160H75RT and V160H75RS sheetBroan-NuTone LLC / Venmar Ventilation ULC, 1109196G, undated · consulted November 9, 2026
V160H75RS product page, broan-nutone.comDimensions, weight, ENERGY STAR: no · consulted November 9, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · fan running cost