Home / Comparisons / Air exchangers
LIFEBREATH 205 MAX and BROAN-NUTONE V160H75RS: what each one moves, recovers and draws
Two heat recovery ventilators (HRVs) for houses, both listed in the HVI directory. They are not the same size: at 0.4 in. w.c., the directory publishes 170 CFM for the 205 MAX and 150 CFM for the V160H75RS. At 0 °C, the two share one test point, 64 CFM, and that is where their numbers compare directly. This page follows the HVI directory and shows the manufacturer sheets alongside.
Three measurements, one source
HVI directory, section III · 205 MAX V160H75RS
205 MAX
HRV, top ports · HVI 2505460
Sheet 205 MAX - 0826 · MAX Series sales sheet 1124
See the product page
V160H75RS
HRV, side ports · HVI 2505433
Sheet 1109196G · also listed in the directory under vänEE (2505311) and Venmar (2505348), same HVI values
See the product pageWhat the fans cost, in dollars per year
An air exchanger does not heat or cool: what it uses is fan power. The HVI directory publishes the watts at each test point. At 0 °C, both units are tested at 64 CFM; we start with that shared point, then show each unit's highest test airflow.
How this amount is calculated
- Power: the watts in the HVI directory at each 0 °C test point. Shared point, 64 CFM: 66 W (205 MAX) and 28 W (V160H75RS). Highest test airflow: 86 W at 95 CFM (205 MAX) and 100 W at 129 CFM (V160H75RS).
- Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
- Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.
At the shared point, the two amounts compare two units moving the same fresh-air flow. At the highest test airflow, the flows differ (95 and 129 CFM): the amount then compares two test points, not two units set the same way. The amount covers the fans only; recovered heat is covered in the next section.
AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the settings and how the unit is used; this amount is not a promise.
One hour of ventilation, counted with the HVI directory numbers
Over one hour at its test airflow, each unit replaces a certain volume of air, uses a certain amount of electricity and recovers part of the heat that was leaving. All three numbers come from the same line of the directory. Choose the test temperature.
SRE: sensible recovery efficiency. Per HVI, it is the net sensible energy recovered by the fresh air, adjusted for electricity consumed, case losses, leakage, airflow imbalance and, at very low temperature, defrost energy, as a percentage of the sensible energy that could be recovered. HVI states that units should be compared only at equivalent outdoor conditions and net airflow. The drawing of the two airstreams is a diagram.
The more the ducts resist, the less air gets through: the two curves cross at 0.8 in. w.c.
External static pressure adds up the resistance of ducts, elbows, grilles and outdoor hoods. The HVI directory publishes each unit's net fresh-air flow at each step. Up to 0.7 in. w.c., the 205 MAX shows the higher number; at 0.8 in. w.c., both are at 127 CFM; at 0.9 and 1.0 in. w.c., it is the V160H75RS.
What is inside each cabinet, per the sheets
The manufacturer sheets describe two different builds: a counter-flow core and a PSC motor on one side, a cross-flow core and two ECM motors on the other. Each card says which document publishes it.
205 MAX: counter-flow HEX core, thermally conductive, removable for cleaning. V160H75RS: cross-flow polypropylene, 12 × 12 × 9 in.
205 MAX: centrifugal blowers, multi-speed PSC motor; high speed factory-set to Hi3, adjustable with DIP switches. V160H75RS: two PMSM ECM motors; airflow selected from 35 to 160 CFM on the unit's LCD.
205 MAX: washable MERV 6 filters on both the fresh and stale airstreams; MERV 13 optional. V160H75RS: washable MERV 8; MERV 13 and HEPA optional.
205 MAX: recirculating damper; the sheet publishes no start temperature or cycle time. V160H75RS: recirculation from −5 °C, times published by temperature range, Discretion and Plus modes.
205 MAX: balancing ports on the door and adjustable dampers on the collars. V160H75RS: Virtuo constant-airflow and auto-balancing device, motorized dampers.
205 MAX: DXPL03 digital wall control included. V160H75RS: LCD built into the unit; optional wall controls, described in the manufacturer's wall control sheet.
205 MAX: two 1/2 in. (12 mm) drain connections. V160H75RS: integrated snap-in drain, hose included.
205 MAX: 22-gauge prepainted galvanized steel, insulated. V160H75RS: galvanized steel, one-piece molded expanded polystyrene insulation shell.
Ports on top or on the side, and ten inches apart in width
The 205 MAX has its four 6 in. round collars on top and is 33 5/8 in. wide. The V160H75RS has its 6 in. ports on the side and is 23.5 in. wide. The two heights are close: 18 3/4 in. and 19.13 in.


Left, the manufacturer photo, in perspective. Right, the outline of the front, width × height, to the same scale for both (diagram). Dimensions and weight per the manufacturer documents.
| Installation, per the manufacturer | LIFEBREATH 205 MAX | BROAN-NUTONE V160H75RS |
|---|---|---|
| Portsround | 4 collars, 6 in. (150 mm), on top | 4 ports, 6 in., on the side |
| Dimensions W × D × H | 33 5/8 × 15 × 18 3/4 in.854 × 381 × 476 mm · sheet 0826 | 23.5 × 16.3 × 19.13 in.broan-nutone.com product page |
| Unit weight | 57 lb25.8 kg | 35 lb15.9 kg, core included |
| Service clearance, in front of the door | 25 in. (635 mm), recommended | 8 in. (20.3 cm), required |
| Mounting | Suspended: four threaded inserts, S hooks and straps supplied | Suspended by chains (included) or wall-mounted with 2 or 4 brackets (included) |
| Power supply | 120 V, 60 Hz, 1.4 AMCA 2.0 A · MOP 15 A | 120 V, 60 Hz, 2.4 A6 ft cord |
| Power stated on the sheet | 66 W at 64 CFMsame value as the HVI directory | 163 Welectrical rating on the sheet; different method, not comparable |
What people ask us about these two units
Why compare two units that do not have the same airflow?
Because they often end up on the same short list for a house, and the HVI directory gives enough to read them side by side: each unit's airflow at the same static pressure, and a shared test point at 0 °C, 64 CFM. The page says throughout when the conditions are the same and when they are not.
Which one recovers more heat?
At the only shared test point, 0 °C and 64 CFM, the HVI directory publishes an SRE of 82% for the 205 MAX and 77% for the V160H75RS. At −25 °C, the two tests are not at the same airflow (70 and 66 CFM): the directory publishes 69% and 67%, and HVI states that units should be compared only at equivalent net airflow.
Why does the LIFEBREATH sales sheet say 76%?
The MAX Series sales sheet, code 1124, publishes for the 205 MAX an SRE of 76% at 64 CFM and 193, 182 and 170 CFM at 0.2, 0.3 and 0.4 in. w.c. The HVI directory (listing 2505460) and technical sheet 205 MAX - 0826 publish 82% at 64 CFM and 191, 180 and 170 CFM. This page follows the HVI directory.
What does the ventilation reduction at −25 °C mean?
The very low temperature test lasts 72 hours. HVI publishes by how much, in percent, supply and exhaust airflow dropped at the end of the test compared with frost-free operation; the drop comes from frost in the core and from defrost cycles. The directory publishes 37.5% and 43.8% for the 205 MAX at 70 CFM, 19.2% and 19.4% for the V160H75RS at 66 CFM.
Are they ENERGY STAR certified?
The documents do not all say the same thing. For the 205 MAX, sales sheet 1124 says “no”. For the V160H75RS, sheet 1109196G says the unit meets ENERGY STAR requirements only when used in Canada, and the broan-nutone.com product page says “no”. Current status can be checked on the Natural Resources Canada list.
What about noise and warranty?
The documents consulted publish no sound level for these two models, and this page does not compare warranties. The warranty documents for the unit chosen come with the quote.
Does the V160H75RS go by other names?
The HVI directory also lists a V160H75RS under the vänEE (listing 2505311) and Venmar (2505348) brands, with the same airflows and the same recovery values as Broan listing 2505433. Sheet 1109196G carries the names Broan-NuTone LLC and Venmar Ventilation ULC.
Every value in the HVI directory
HVI directory, section III, data as of November 4, 2026. Airflows at the same static pressure and the values at the shared test point compare directly; the other points do not.
| Measurement | LIFEBREATH 205 MAX | BROAN-NUTONE V160H75RS |
|---|---|---|
| Net supply airflow, same static pressure | ||
| Airflow at 0.1 in. w.c. (25 Pa) | 199 CFM | 163 CFM |
| Airflow at 0.2 in. w.c. (50 Pa) | 191 CFM | 159 CFM |
| Airflow at 0.3 in. w.c. (75 Pa) | 180 CFM | 155 CFM |
| Airflow at 0.4 in. w.c. (100 Pa) | 170 CFM | 150 CFM |
| Airflow at 0.5 in. w.c. (125 Pa) | 159 CFM | 144 CFM |
| Airflow at 0.6 in. w.c. (150 Pa) | 148 CFM | 140 CFM |
| Airflow at 0.7 in. w.c. (175 Pa) | 138 CFM | 133 CFM |
| Airflow at 0.8 in. w.c. (200 Pa) | 127 CFM | 127 CFM |
| Airflow at 0.9 in. w.c. (225 Pa) | 114 CFM | 121 CFM |
| Airflow at 1.0 in. w.c. (250 Pa) | 102 CFM | 114 CFM |
| Test at 0 °C, same test airflow: 64 CFM (30 L/s) | ||
| Sensible recovery efficiency (SRE) | 82 % | 77 % |
| Adjusted sensible recovery efficiency | 89 % | 80 % |
| Power consumed | 66 W | 28 W |
| Other test points at 0 °C, different airflows | ||
| Lowest test airflownet fresh air | 49 CFM, 58 WSRE 83%, adjusted 91% | 36 CFM, 18 WSRE 82%, adjusted 85% |
| Highest test airflownet fresh air | 95 CFM, 86 WSRE 79%, adjusted 85% | 129 CFM, 100 WSRE 66%, adjusted 71% |
| Very low temperature test, −25 °C, different test airflows | ||
| Test airflownet fresh air | 70 CFM (33 L/s), 117 W | 66 CFM (31 L/s), 43 W |
| Sensible recovery efficiency (SRE) | 69%adjusted 74% | 67%adjusted 69% |
| Ventilation reduction during the testsupply · exhaust | 37.5% · 43.8% | 19.2% · 19.4% |
| Certification | ||
| HVI directory, section III | Yes, listing 2505460 | Yes, listing 2505433 |
| ENERGY STAR | Sales sheet 1124: no | Sheet 1109196G: yes, in Canada onlybroan-nutone.com page: no |
“Higher” marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Only airflows at the same static pressure and the values at the shared test point are marked. The V160H75RS is also tested at 47 CFM (22 W, SRE 79%, adjusted 82%).
Both are on the AirGreen website.
The right choice depends on the ventilation rate the house needs, the resistance of its ducts and the room available for the ports. Talk it over with our team.
Where each number comes from
Data verified on November 9, 2026. Airflow, heat recovery and power: HVI directory. Dimensions, weight, construction and controls: per the manufacturer. When a manufacturer document contradicts the HVI directory, the directory prevails.
Trademarks. LIFEBREATH, BROAN-NUTONE, Broan, vänEE, Venmar, Virtuo and Homeshield are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer for both brands; this page is not produced, sponsored or approved by the manufacturers. Data colours: the blue of the LIFEBREATH logo; AirGreen teal for BROAN-NUTONE, whose logo blue would be confused with LIFEBREATH's.
Photos: AirGreen and manufacturers, for identification.
Does a number look inaccurate? Write to us at sales@airgreen.ca: every number reported is checked again.