Home / Comparisons / ADD-ON central heat pumps, 3 tons
GREE FLEXX R32 ADD-ON and GREE UNIX R32 ADD-ON: two product pages, one AHRI certificate
An ADD-ON heat pump adds a cased coil on your furnace and an outdoor unit outside. On AirGreen’s site, both product pages carry the same model numbers and the same AHRI certificate. This page shows that certificate, where the two names come from, and above all how the coil sits on your furnace.
What the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 32,000 BTU/h house, the certificate’s rated capacity, in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Here, both product pages have the same certificate: the two amounts are therefore the same. Electric baseboards serve as the point of reference. The calculation assumes the heat pump heats all winter with the backup the standard provides for: if your furnace takes over in extreme cold, your bill will also depend on its energy.
How this amount is calculated
- Heat needed over the winter. A house whose heat loss reaches 32,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (the “Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 32,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air conditioning calculator, with the seasonal SEER2 efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one offered by Hydro-Québec’s calculators. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.
The 17 1/2 in cabinet, set on your furnace
The 3-ton coil comes in a cabinet 17 1/2 in wide, 23 in high and 21 1/4 in deep. Measure your furnace and the clear height of the basement, then set the three sliders: the drawing redraws itself to scale.
Scale drawing, front view; this is not a photo. GCAC36F/NhA cabinet dimensions: GREE Canada brochure 062025, page 3 (445 × 584 × 540 mm). The 4- and 5-ton cabinets in the same brochure are 24 1/2 in wide and 28 1/2 in high. A width difference between the furnace and the cabinet, the plenum height and the duct connection are decided on site, before installation.
Two product pages, one AHRI certificate
Both AirGreen product pages list the GCAC36F/NhA coil, the GUD36W2/NhE-D(U) outdoor unit and AHRI certificate 216765692. Here is what NEEP publishes for that certificate.
- SEER2
- 16.0
- EER2
- 11.0
- HSPF2 Region IV
- 8.5
- HSPF2 Region V
- 7.9
- Cooling at 35 °C
- 32,000
- Heating at 8.3 °C
- 35,000
- Max. at −15 °C
- 32,000
- Max. at −30 °C
- 19,600
Capacities in BTU/h. NEEP record 380937, read on November 10, 2026. Where the two names come from: GREE Canada’s brochure presents this coil and this outdoor unit under the name “UNIX R32”; GREE’s A-coil service manual, published with the FLEXX series, names the same GCAC24F/NhA to GCAC60H/NhA coils in its settings table.
Three other certificates worth knowing
Same coil and same outdoor unit, certified with this furnace:
- SEER2 16.0, EER2 10.0
- HSPF2 Region IV 8.5, Region V 6.6
- 24,600 BTU/h at maximum at −15 °C
- 16,400 BTU/h at maximum at −30 °C
- ENERGY STAR: no
Same efficiencies as the previous certificate; rated cooling of 31,800 BTU/h and 22,000 BTU/h of rated heating at −8.3 °C, instead of 20,400.
In the United States, GREE sells a 3-ton coil under these numbers, with the same published cabinet. NEEP gives it the same values as certificate 216765692, except one: 25,600 BTU/h of rated heating at −15 °C, instead of 32,000.
Below −15 °C: the certificate’s two points
NEEP publishes one point at −15 °C and one at −30 °C for certificate 216765692, the same for both product pages. In between, GREE publishes no table for this coil: the page shows the range between the two certified points.
What GREE’s documents state, under each name
Under the FLEXX name: GREE’s A-coil service manual (October 2025) and the FLEXX ULTRA documents. Under the UNIX R32 name: GREE Canada brochure 062025. Both product pages carry the same model numbers: these documents complement each other.
FLEXX documents: heating stated from −30 to 24 °C (−22 to 75 °F).
UNIX R32 brochure: heating from −30 to 24 °C; “Ultra Heat”. NEEP lists a 160 W base pan heater, on below 1 °C or during defrost.
FLEXX documents: “GREE G20”, double cylinder, two-stage inverter (FXU36 submittal).
UNIX R32 brochure: two-stage, two-cylinder compressor; “DC Inverter” technology.
FLEXX documents: 24 V connection or RS485 communication, chosen by a switch on the coil; WK-010WC1 thermostat.
UNIX R32 brochure: compatible with 24 VAC thermostats and with RS485 communication.
FLEXX documents: sensor in the coil; on a leak, code “EA”, audible alarm, fan forced on, outdoor unit and furnace gas valve shut off. Sensor lifetime: 15 years.
UNIX R32 brochure: “Leak detector on all cased coils”.
FLEXX documents: the coil passes the fan signal to the furnace and gets its 24 V from it.
UNIX R32 brochure: airflow of 760 CFM printed for the 3-ton.
FLEXX documents: “Ultra Heat with Dual Fuel”; the coil passes the heating signals to the furnace gas valve.
UNIX R32 brochure: retrofit possible “with a furnace combined with a cased coil”.
FLEXX documents: counter-flow installation possible after moving the secondary drain pan, per the service manual.
UNIX R32 brochure: not stated for the coil.
FLEXX documents: gold fins outdoors (1,500 h salt spray) and blue fins indoors (500 h), per the FXA36C32AH coil submittal.
UNIX R32 brochure: not mentioned in the brochure.
Published sound of the outdoor unit
The coil has no fan: indoors, the noise is that of your furnace and your ducts. Outdoors, the GREE Canada brochure publishes 61 dB(A) for the GUD36W2/NhE-D(U) unit, the same for both product pages. The Canadian data sheet for this unit adds “as low as 56 dB(A)”, without stating at which speed.
How to read these figures. The dB(A) measures a noise level as the ear perceives it: the lower the figure, the quieter the unit. Each dot is a value published by the manufacturer.
Why this is not a ranking. Both rows show the same outdoor unit: they cannot differ. GREE publishes neither the distance, the speed nor the conditions of the measurement.
Outdoor unit
One published value.
One outdoor unit, one published value: 61 dB(A), with no measurement method described.
Outdoors and in the piping
The outdoor unit, the piping and the clearances are those of the GUD36W2/NhE-D(U), whatever the name on the product page.
FLEXX R32 ADD-ON GUD36W2/NhE-D(U)
Minimum clearances with obstacles behind and on the sides, and an obstacle in front: GREE data sheet for this outdoor unit (greehvac.ca), page 6.
UNIX R32 ADD-ON GUD36W2/NhE-D(U)
Same outdoor unit, same minimums. The data sheet also asks for the unit to sit 2 in above the expected snow line, and for 40 in clear under an obstacle.


| Installation, per GREE Canada brochure 062025 | FLEXX R32 ADD-ON | UNIX R32 ADD-ON |
|---|---|---|
| Max. piping length | 98 ft (30 m) | 98 ft (30 m) |
| Pre-charged length | 24.6 ft (7.5 m)“standard pipe length” in the brochure | 24.6 ft (7.5 m)“standard pipe length” in the brochure |
| Max. height difference | 49 ft (15 m) | 49 ft (15 m) |
| Liquid – gas diameters | 3/8 – 3/4 in | 3/8 – 3/4 in |
| R-32 refrigerant, factory charge | 102.3 oz2.9 kg | 102.3 oz2.9 kg |
| Outdoor unit W × H × D, weight | 39 × 37 51/64 × 14 9/16 in, 187.4 lb | 39 × 37 51/64 × 14 9/16 in, 187.4 lb |
| Indoor unit, cased coil: W × H × D, weight | 17 1/2 × 23 × 21 1/4 in, 75 lb | 17 1/2 × 23 × 21 1/4 in, 75 lb |
| Electrical protection | Outdoor unit: 27.7 A minimum, 30 A protection208-230 V, 60 Hz, single phase. The coil is supplied with 24 V by the furnace | Outdoor unit: 27.7 A minimum, 30 A protection208-230 V, 60 Hz, single phase. The coil is supplied with 24 V by the furnace |
| Dehumidification | 5.33 L/h11.26 US pints per hour in the brochure (11.26 × 0.4732 L) | 5.33 L/h11.26 US pints per hour in the brochure (11.26 × 0.4732 L) |
| Heating / cooling range, as published | −30 to 24 °C / −15 to 54 °C | −30 to 24 °C / −15 to 54 °C |
| Published clearances, single unit | 4 in behind, 4 and 12 in on the sides, 40 in in front of an obstacle | 4 in behind, 4 and 12 in on the sides, 40 in in front of an obstacle |
Both columns carry the same values: same model numbers. The GREE submittal for the coil sold in the United States under the number FXA36C32AH publishes other lengths (164 ft maximum, 31 ft pre-charged) and 7.75 pints per hour: those figures belong to the other certificate. Municipal by-laws and the building code apply on top of the published clearances.
The questions we get about the ADD-ON versions
What is the difference between the FLEXX R32 ADD-ON and the UNIX R32 ADD-ON?
On AirGreen’s site, both product pages carry the same numbers: GCAC36F/NhA coil, GUD36W2/NhE-D(U) outdoor unit, AHRI certificate 216765692. No certified value sets them apart. The two names come from the documents: GREE Canada presents this system under the name UNIX R32, and the GREE service manual published with the FLEXX series names the same coils.
Will the coil fit on my furnace?
It comes down to four checks. Width: the cabinet is 17 1/2 in. Height: it adds 23 in to your furnace, before the plenum. Heat exchanger: the GREE submittal asks for 2 in between the pan and a gas furnace’s heat exchanger, 4 to 6 in for oil. Blower: your furnace’s blower moves the air, and the brochure prints 760 CFM for the 3-ton. GREE Canada publishes no list of compatible furnaces.
Does the certificate change with the furnace?
Certificate 216765692 is the one for the coil and the outdoor unit, with no named furnace. NEEP also lists this pair with two named furnaces, C60-2-V and C75-2-V: HSPF2 Region V then goes from 7.9 to 6.6, maximum capacity at −15 °C from 32,000 to 24,600 BTU/h, and the ENERGY STAR listing is absent. The number on your quote shows which combination is certified.
How much does it cost to run?
Our estimate is the same for both product pages, since the certificate is the same. It assumes the heat pump heats all winter. If your furnace takes over in extreme cold, part of the heating will run on its energy, and the electricity bill will not tell the whole story. The full method is under the calculator.
Down to what temperature does it heat?
GREE states heating down to −30 °C. The certificate gives 32,000 BTU/h at maximum at −15 °C and 19,600 BTU/h at maximum at −30 °C, with a COP of 1.21 at that last point. Below −30 °C, none of the documents consulted publishes a capacity.
What happens if the refrigerant leaks?
The coil contains an R-32 sensor. Per the GREE service manual, when it detects a leak, the board shows code “EA” and sounds an alarm, the fan is forced on, and the outdoor unit and the furnace gas valve are shut off. The manual gives the sensor a lifetime of 15 years.
Is it eligible for financial assistance?
Certificate 216765692 is listed as ENERGY STAR cold climate in the NEEP directory and in ENERGY STAR’s own. Eligibility for a program such as LogisVert is checked by AHRI number in Hydro-Québec’s tool, on the day of the quote, because the lists change. This page gives no amount and promises no eligibility.
The certified values, all in one place
| Certified value (AHRI, published by NEEP) | FLEXX R32 ADD-ON | UNIX R32 ADD-ON |
|---|---|---|
| Identification | ||
| AHRI certificate · NEEP record | 216765692 · 380937GCAC36F/NhA + GUD36W2/NhE-D(U) | 216765692 · 380937GCAC36F/NhA + GUD36W2/NhE-D(U) |
| Series in the NEEP directory | E Series | E Series |
| Refrigerant | R-32GWP 675 (IPCC AR4); class A2L (ASHRAE 34) | R-32GWP 675 (IPCC AR4); class A2L (ASHRAE 34) |
| ENERGY STAR | Yes, cold climate | Yes, cold climate |
| Seasonal efficiency | ||
| SEER2 | 16.0 | 16.0 |
| EER2 | 11.0 | 11.0 |
| HSPF2 Region IV | 8.5 | 8.5 |
| HSPF2 Region V | 7.9 | 7.9 |
| Cooling at 35 °C (95 °F) | ||
| Rated capacity at 35 °C | 32,000 BTU/h | 32,000 BTU/h |
| Capacity at 35 °C, min. / rated / max. | 10,600 / 32,000 / 32,000 BTU/h | 10,600 / 32,000 / 32,000 BTU/h |
| Heating at 8.3 °C (47 °F) | ||
| Capacity, min. / rated / max. | 12,200 / 35,000 / 35,400 BTU/h | 12,200 / 35,000 / 35,400 BTU/h |
| COP, min. / rated / max. | 4.11 / 3.20 / 3.17 | 4.11 / 3.20 / 3.17 |
| Heating at −8.3 °C (17 °F) | ||
| Capacity, min. / rated / max. | 6,800 / 26,000 / 26,000 BTU/h | 6,800 / 26,000 / 26,000 BTU/h |
| COP, min. / rated / max. | 2.10 / 2.00 / 2.00 | 2.10 / 2.00 / 2.00 |
| Heating at −15 °C (5 °F) | ||
| Capacity, min. / rated / max. | 15,000 / 32,000 / 32,000 BTU/h | 15,000 / 32,000 / 32,000 BTU/h |
| COP, min. / rated / max. | 2.13 / 1.80 / 1.80 | 2.13 / 1.80 / 1.80 |
| Coldest point on the certificate | ||
| Test temperature | −30 °C (−22 °F) | −30 °C (−22 °F) |
| Capacity, min. / max. | 14,500 / 19,600 BTU/h | 14,500 / 19,600 BTU/h |
| COP, min. / max. | 1.38 / 1.21 | 1.38 / 1.21 |
higher marks the higher value of the same measure, under the same conditions. It is not a recommendation. Here, nothing is marked: both columns repeat the same AHRI certificate, 216765692. The GREE Canada brochure prints for this system 32,000 BTU/h in cooling, 35,000 BTU/h in heating, a SEER2 of 16.0, an EER2 of 11.0 and an HSPF2 of 8.5: the same values as the certificate.
Both are on AirGreen’s site.
To find out whether the coil fits on your furnace, talk it over with our team: bring the furnace’s brand, model and age, its width and height, the clear height of the basement and the planned spot outdoors.
Documents consulted
Data verified on November 10, 2026. Performance: AHRI certificates and the NEEP database. Dimensions, sound, piping and features: per the manufacturer. When a source contradicts the AHRI certificate, the certificate prevails.
Trademarks. GREE, FLEXX and UNIX are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer of the brand; this page is not produced, sponsored or approved by the manufacturer.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong to you? Write to us: any figure reported is rechecked.