Home / Comparisons / 3-ton central heat pumps
KINGHOME ULTRANIXX R32 and GREE UNIX R32: A-coil or air handler
Two 3-ton central heat pumps on R-32, offered by AirGreen. Each can be combined two ways: with an air handler, which replaces the furnace, or with an A-coil set on a furnace. Each combination has its own AHRI certificate. With the coil, both certificates carry the same values on every line compared; with the air handler, three lines differ.
What the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 34,000 BTU/h house, the certified rated capacity of both heat pumps with their air handler, in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the point of reference. With the A-coil, both certificates carry the same efficiencies (HSPF2 Region V 7.9 and SEER2 16.0): this calculation would then give both the same amount.
How this amount is calculated
- Heat needed over the winter. A house whose heat loss reaches 34,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (the “Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 34,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air conditioning calculator, with the seasonal SEER2 efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one offered by Hydro-Québec’s calculators. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.
One outdoor unit, two ways to connect it
Pick the combination: the drawing, the dimensions and each brand’s certificate follow. The “Extreme cold” section and the certified data sheet, further down, follow this choice too.
Scale drawing, front view; this is not a photo. Dimensions: KINGHOME Canada submittals (KD36UXI, KCAC36FI) and GREE Canada brochure 062025 (GUD36AH2/G-D(U), GCAC36F/NhA). The furnace drawn under the coil is an example: its size depends on yours. GREE Canada calls its version a “cased coil”. Certified values: NEEP records 376106, 378411, 371863 and 380937, read on November 10, 2026.
Below −15 °C: two certified points per combination
NEEP publishes for each certificate one point at −15 °C and one at −30 °C. In between, neither KINGHOME nor GREE publishes a capacity table: the page shows the range between the two certified points, with their temperature.
What each manufacturer states
KINGHOME: KINGHOME Canada submittals and ULTRANIXX R32 page. GREE: GREE Canada brochure 062025. When a document is silent, the page says so; a document’s silence does not prove a feature is absent.
ULTRANIXX R32 : heating stated from −30 to 24 °C; base pan heater and compressor electric heater listed in the submittals. NEEP specifies 160 W for the pan, on below 1 °C or during defrost.
UNIX R32 : heating stated down to −30 °C; “Ultra Heat”. The brochure does not mention a base pan heater; the NEEP record lists one of 160 W, on below 1 °C or during defrost.
ULTRANIXX R32 : rotary compressor and electronic expansion valve in the submittals; the 2026 KINGHOME Canada brochure names it “GREE G20 / Double Cylinder / 2 - Stage Inverter”.
UNIX R32 : two-stage, two-cylinder compressor; “DC Inverter” technology.
ULTRANIXX R32 : universal 24 V compatibility and RS485 communication, with 2 or 4 wires; optional smart thermostat WK-010WC01 or WK-010WD1.
UNIX R32 : compatible with 24 VAC thermostats and with RS485 communication.
ULTRANIXX R32 : R-32 sensor included with the KCAC36FI coil; not mentioned in the air handler submittal.
UNIX R32 : refrigerant leak detector listed among the brochure’s features.
ULTRANIXX R32 : 5-speed air handler; airflow table from 0 to 1.0 in w.g.; 1,000 CFM at 0.5 in w.g. on speed 3.
UNIX R32 : 1,000 CFM at a rated external static pressure of 125 Pa (0.5 in w.g.); compatible with downflow applications.
ULTRANIXX R32 : 5, 10 or 15 kW kits for the air handler in the submittal; the 2026 brochure lists two, 5 and 10 kW.
UNIX R32 : optional backup heat; the brochure gives no kW ratings and refers to the technician for the electrical calculation.
ULTRANIXX R32 : control board can be moved to the left or right; horizontal installation possible.
UNIX R32 : retrofit installation possible, per the brochure; external service valves and electrical terminals.
ULTRANIXX R32 : metal mesh filter included, 19 1/4 × 20 1/4 × 1/2 in.
UNIX R32 : not mentioned in the brochure.
Published sound, unit by unit
Both manufacturers publish 51 dB(A) for the air handler. For the outdoor unit, GREE Canada publishes 61 dB(A); KINGHOME Canada publishes 61 dB(A) in the air handler submittal and 60 dB(A) in the coil submittal and in its brochure, for the same KU36UXO unit. An A-coil has no fan: the furnace’s blower moves the air.
How to read these figures. The dB(A) measures a noise level as the ear perceives it: the lower the figure, the quieter the unit. Each dot is a value published by the manufacturer. An air handler usually sits in a basement or a closet: what is heard in the rooms also depends on the ducts and their insulation.
Why this is not a ranking. None of the documents publishes the distance, the speed or the conditions of these measurements. A one-decibel gap between two submittals for one outdoor unit shows how much precision these figures deserve.
Indoor unit (air handler)
One value published per document, with no speed stated.
Outdoor unit
KINGHOME: one value per submittal. GREE: one value.
Measurements taken by each manufacturer with its own method, not described: these figures cannot be compared directly.
Outdoors: same published cabinets, different instructions
Both manufacturers publish the same dimensions and weights, and the same distances behind, on the sides and in front. Their documents part on two points: the space above the unit and the height at which to set it.
ULTRANIXX R32 KU36UXO
Minimum clearances from the KINGHOME Canada submittal, page 2. Above: 12 in (30 cm).
UNIX R32 GUD36W2/NhE-D(U)
Minimum clearances from the GREE data sheet for this model (greehvac.ca), page 6. Under an obstacle: 40 in above.
How high to set the outdoor unit
ULTRANIXX R32
“Unit must be placed a minimim 18in (45cm) above any surfaces to allow for snow clearance and defrost runoff”: KINGHOME Canada submittal, page 2.
UNIX R32
“Install the Outdoor Unit 2 Inches Above the Expected Snow Line”: GREE data sheet (greehvac.ca), page 6. The snow depth in the drawing is an example.





| Installation, per each document | ULTRANIXX R32 | UNIX R32 |
|---|---|---|
| Max. piping length | 100 ft (30 m)published minimum: 10 ft (3 m) | 98 ft (30 m)no minimum stated in the brochure |
| Pre-charged length | 25 ft (7.5 m)beyond: 0.3 oz per foot | 24.6 ft (7.5 m)“standard pipe length” in the brochure; top-up per foot not stated |
| Max. height difference | 50 ft (15 m) | 49 ft (15 m) |
| Liquid – gas diameters | 3/8 – 3/4 in | 3/8 – 3/4 in |
| R-32 refrigerant, factory charge | 102.3 oz | 102.3 oz2.9 kg in the brochure |
| Outdoor unit W × H × D, weight | 39 × 37 13/16 × 14 9/16 in, 187.4 lb | 39 × 37 51/64 × 14 9/16 in, 187.4 lb |
| Indoor unit, air handler: W × H × D, weight | 21 1/4 × 48 3/16 × 21 1/4 in, 163.1 lb | 21 17/64 × 48 3/16 × 21 17/64 in, 163.1 lb |
| Indoor unit, A-coil: W × H × D, weight | 17 1/2 × 23 × 21 1/4 in, 75 lb | 17 1/2 × 23 × 21 1/4 in, 75 lb |
| Electrical protection | Outdoor: 27 A (air handler submittal) or 27.7 A (coil submittal) minimum, 30 A protection. Air handler: 5.3 A, 15 A protection208-230 V, 60 Hz, single phase; values without electric backup heat. The 2026 brochure lists 21 A and 25 A for the outdoor unit | Outdoor: 27.7 A minimum, 30 A protection. Air handler: 5.3 A, 15 A protection208-230 V, 60 Hz, single phase; values without electric backup heat |
| Dehumidification | 2.85 L/hair handler: 6.02 US pints per hour in the submittal (6.02 × 0.4732 L) | Not published by the manufacturerfor the air handler, in brochure 062025 |
| Heating / cooling range, as published | −30 to 24 °C / −15 to 54 °C | −30 to 24 °C / −15 to 54 °C |
| Published clearances, single unit | 4 in behind, 4 and 12 in on the sides, 40 in in front, 12 in above | 4 in behind, 4 and 12 in on the sides, 40 in in front of an obstacle, 40 in under an obstacle |
| Clearance under the unit, for snow | 18 in (45 cm) above any surface | 2 in above the expected snow line |
Both manufacturers’ piping lengths are the same in metres (30, 7.5 and 15 m): the differences in feet come from each document’s rounding. Municipal by-laws and the building code apply on top of the published clearances.
The questions we get about these two brands
What do these two heat pumps have in common?
What can be checked in the documents: NEEP files all four certificates under a series called “E Series”; with the A-coil, the 17 certified lines compared carry the same values in both certificates; with the air handler, 14 lines out of 17; the published dimensions and weights are the same. KINGHOME Canada’s 2026 brochure names the compressor “GREE G20”, and the ENERGY STAR directory lists Gree Electric Appliances Inc. of Zhuhai as the partner for both KINGHOME records. The page concludes nothing more: the model numbers, certificates and documents remain each brand’s own.
A-coil or air handler: what is the difference?
The A-coil sits on a furnace, which keeps its blower and its heat. The air handler replaces the furnace: it contains its own fan and can take electric backup heat. The certificates are not the same: with the coil, a SEER2 of 16.0 and an HSPF2 Region V of 7.9 for both brands; with the air handler, a SEER2 of 18.0 or 18.2 and an HSPF2 Region V of 7.6.
Which one costs less to run?
With the air handler, our estimate gives both the same heating amount (HSPF2 Region V of 7.6) and a difference of about one dollar a summer, because of SEER2 (18.0 and 18.2). With the A-coil, the certified efficiencies are the same for both brands. The full method is under the calculator.
Down to what temperature do they heat?
Both manufacturers state heating down to −30 °C. With the air handler, both certificates give 34,000 BTU/h at maximum at −15 °C and 20,400 BTU/h at −30 °C (COP of 1.31). With the A-coil: 32,000 BTU/h at −15 °C and 19,600 BTU/h at −30 °C (COP of 1.21). Below −30 °C, none of the documents consulted publishes a capacity.
Why do the data sheets not always show the same figures as this page?
Because this page follows the AHRI certificates. The KINGHOME air handler submittal prints a SEER2 of 16 and an HSPF2 of 9.5; the certificate lists 18 and 10. The coil submittal prints 22,000 BTU/h at −8.3 °C; the certificate lists 26,000. The table in the GREE Canada brochure gives the 3-ton a SEER2 of 18.0 and an EER2 of 12.0; the certificate lists 18.2 and 11.2.
How high should the outdoor unit be set?
The two manufacturers do not give the same instruction. KINGHOME Canada asks for 18 in (45 cm) above any surface, for snow and defrost water. The GREE data sheet asks for 2 in above the expected snow line. In both cases, the final height is decided on site, according to the location and local rules.
Are they eligible for financial assistance?
All four certificates are listed as ENERGY STAR cold climate in the NEEP directory; the ENERGY STAR directory lists all four. Eligibility for a program such as LogisVert is checked by AHRI number in Hydro-Québec’s tool, on the day of the quote, because the lists change. This page gives no amount and promises no eligibility.
The certified values, combination by combination
| Certified value, with the air handler | ULTRANIXX R32 | UNIX R32 |
|---|---|---|
| Identification | ||
| AHRI certificate · NEEP record | 217194945 · 376106KD36UXI + KU36UXO | 217120760 · 378411GUD36AH2/G-D(U) + GUD36W2/NhE-D(U) |
| Series in the NEEP directory | E Series | E Series |
| Refrigerant | R-32GWP 675 (IPCC AR4); class A2L (ASHRAE 34) | R-32GWP 675 (IPCC AR4); class A2L (ASHRAE 34) |
| ENERGY STAR | Yes, cold climate | Yes, cold climate |
| Seasonal efficiency | ||
| SEER2 | 18.0 | 18.2 |
| EER2 | 11.2 | 11.2 |
| HSPF2 Region IV | 10.0 | 10.0 |
| HSPF2 Region V | 7.6 | 7.6 |
| Cooling at 35 °C (95 °F) | ||
| Rated capacity at 35 °C | 34,000 BTU/h | 34,000 BTU/h |
| Capacity at 35 °C, min. / rated / max. | 11,800 / 34,000 / 34,500 BTU/h | 11,800 / 34,000 / 34,500 BTU/h |
| Heating at 8.3 °C (47 °F) | ||
| Capacity, min. / rated / max. | 11,200 / 34,000 / 34,400 BTU/h | 11,200 / 34,000 / 34,400 BTU/h |
| COP, min. / rated / max. | 4.62 / 3.20 / 3.20 | 4.62 / 3.20 / 3.17 |
| Heating at −8.3 °C (17 °F) | ||
| Capacity, min. / rated / max. | 9,200 / 28,200 / 29,600 BTU/h | 9,200 / 32,600 / 32,200 BTU/h |
| COP, min. / rated / max. | 2.64 / 2.50 / 2.47 | 2.64 / 2.50 / 2.47 |
| Heating at −15 °C (5 °F) | ||
| Capacity, min. / rated / max. | 16,000 / 34,000 / 34,000 BTU/h | 16,000 / 34,000 / 34,000 BTU/h |
| COP, min. / rated / max. | 2.29 / 2.00 / 2.00 | 2.29 / 2.00 / 2.00 |
| Coldest point on the certificate | ||
| Test temperature | −30 °C (−22 °F) | −30 °C (−22 °F) |
| Capacity, min. / max. | 15,000 / 20,400 BTU/h | 15,000 / 20,400 BTU/h |
| COP, min. / max. | 1.40 / 1.31 | 1.40 / 1.31 |
| Certified value, with the A-coil | ULTRANIXX R32 | UNIX R32 |
|---|---|---|
| Identification | ||
| AHRI certificate · NEEP record | 217603525 · 371863KCAC36FI + KU36UXO | 216765692 · 380937GCAC36F/NhA + GUD36W2/NhE-D(U) |
| Series in the NEEP directory | E Series | E Series |
| Refrigerant | R-32GWP 675 (IPCC AR4); class A2L (ASHRAE 34) | R-32GWP 675 (IPCC AR4); class A2L (ASHRAE 34) |
| ENERGY STAR | Yes, cold climate | Yes, cold climate |
| Seasonal efficiency | ||
| SEER2 | 16.0 | 16.0 |
| EER2 | 11.0 | 11.0 |
| HSPF2 Region IV | 8.5 | 8.5 |
| HSPF2 Region V | 7.9 | 7.9 |
| Cooling at 35 °C (95 °F) | ||
| Rated capacity at 35 °C | 32,000 BTU/h | 32,000 BTU/h |
| Capacity at 35 °C, min. / rated / max. | 10,600 / 32,000 / 32,000 BTU/h | 10,600 / 32,000 / 32,000 BTU/h |
| Heating at 8.3 °C (47 °F) | ||
| Capacity, min. / rated / max. | 12,200 / 35,000 / 35,400 BTU/h | 12,200 / 35,000 / 35,400 BTU/h |
| COP, min. / rated / max. | 4.11 / 3.20 / 3.17 | 4.11 / 3.20 / 3.17 |
| Heating at −8.3 °C (17 °F) | ||
| Capacity, min. / rated / max. | 6,800 / 26,000 / 26,000 BTU/h | 6,800 / 26,000 / 26,000 BTU/h |
| COP, min. / rated / max. | 2.10 / 2.00 / 2.00 | 2.10 / 2.00 / 2.00 |
| Heating at −15 °C (5 °F) | ||
| Capacity, min. / rated / max. | 15,000 / 32,000 / 32,000 BTU/h | 15,000 / 32,000 / 32,000 BTU/h |
| COP, min. / rated / max. | 2.13 / 1.80 / 1.80 | 2.13 / 1.80 / 1.80 |
| Coldest point on the certificate | ||
| Test temperature | −30 °C (−22 °F) | −30 °C (−22 °F) |
| Capacity, min. / max. | 14,500 / 19,600 BTU/h | 14,500 / 19,600 BTU/h |
| COP, min. / max. | 1.38 / 1.21 | 1.38 / 1.21 |
higher marks the higher value of the same measure, under the same conditions. It is not a recommendation. Capacities and COPs by point are not highlighted. With the A-coil, nothing is marked: both certificates carry the same values. The data sheets and brochures sometimes print other efficiencies (see the questions): this page follows the AHRI certificates.
Both are on AirGreen’s site.
To choose for your house, talk it over with our team: bring the heated area, the state of your ducts, the age and width of your furnace if you are keeping it, and the planned spot outdoors.
Documents consulted
Data verified on November 10, 2026. Performance: AHRI certificates and the NEEP database. Dimensions, sound, piping and features: per the manufacturer. When a source contradicts the AHRI certificate, the certificate prevails.
Trademarks. KINGHOME, ULTRANIXX, GREE and UNIX are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer of both brands; this page is not produced, sponsored or approved by the manufacturers.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong to you? Write to us: any figure reported is rechecked.