Échangeur d'Air Fantech ERV FIT 120E-D | Montréal, Laval, Longueuil, Rive Sud et Rive Nord
Is it the right size for your home?
It delivers 127 cfm net, enough to ventilate 1,500 to 2,400 sq ft. Choose your home's living area.
It's the right size.
For a 1,500 to 2,500 sq ft home, about 105 cfm of air needs to be renewed continuously. This unit delivers 127 cfm net — enough for the house, with extra capacity to boost ventilation for the bathroom and kitchen.
Calculation: 0.35 air changes per hour over the living volume, with 9 ft ceilings. Our estimator sets the exact airflow room by room, following CSA F326.
What it does, in numbers
$53.68
Electricity per year
Less than a 60 W light bulb
Bulbs left on day and night. Same calculation for every line: wattage × 8,760 h × 11.142 ¢/kWh.
Meets the Québec Construction Code everywhere in the province. The Code requires 54% at −25 °C below 6,000 degree-days (Montréal, Laval, Longueuil and both shores) and 60% above that. This unit is rated at 61% at 51 cfm.
Airflow and efficiency at 0 °C and −25 °C: HVI directory, Section III. Cost: 55 W over 8,760 h at Hydro-Québec's Rate D second tier (11.142 ¢/kWh).
What you should know about this one
Published, verifiable facts, not brochure claims.
-DBuilt-in motorized outdoor air damper
The -D suffix means the FIT 120E-D has a built-in motorized damper. When the unit is tied to a furnace return, it can block the unconditioned outdoor air the blower would otherwise pull in while the unit is off, which Fantech recommends for that type of installation. The damper brings the width to 25 in, versus 24 5/8 in for the FIT 120E.
8.5 inCore comes out with 8 1/2 in of clearance
Core, filters, fans and electronic panel are reached through the door, held by two latches under the unit. Fantech calls for 8 1/2 in (216 mm) free in front of the door to remove the core, and 2 3/8 in above the electrical box for wiring.
61%What it still recovers at −25 °C
The only efficiency figure that matters for a Québec winter, and the one the Code uses. An efficiency quoted without its temperature means nothing; this one is measured at a test airflow of 51 cfm.
ExhaustIt defrosts by pausing the fresh air for a few minutes
In cold weather, the supply fan stops for a few minutes while the exhaust keeps running, so warm indoor air thaws the core. During the cycle the house is briefly under negative pressure; if you have a fireplace or a naturally vented combustion appliance, mention it to our estimator.
ERVIt moves moisture too, not just heat
An ERV transfers some moisture between the two airstreams. Useful in a house that gets too dry in winter or takes on a lot of humidity in summer. The trade-off: it generally recovers less heat than a comparable HRV.
2005017Its HVI certification number
Listed in Section III of the Home Ventilating Institute's certified products directory. Anyone can check it, and it's the first condition for the Rénoclimat grant.
−19 cfmWhat the ducts cost it
Between a nearly unrestricted test bench (0.2 in) and a real duct system (0.4 in), it drops from 146 to 127 cfm. Most spec sheets show only the first number, precisely because it looks better.
55 WMeasured at the airflow it actually runs at
Its 74% at 0 °C is certified at 51 cfm, the continuous airflow of a typical home. At that setting it draws 55 W, or about 482 kWh a year.
5 yearsThe core warranty
The core does the work and is the most expensive part to replace. Motors: 7 years. Parts: 5 years. We register the warranty in your name at commissioning.
5 inWhat it needs on site
5 in ducts, side connection. It weighs 35 lb, and it needs enough clearance to slide the core out once a year.
Rénoclimat: $500 to install or replace an HRV or ERV
First condition met: HVI Section III certified, No. 2005017. Second: your EnerGuide rating must improve between the two evaluations. Québec warns that an air exchanger installed on its own can increase a home's energy use; that's why we balance it to the calculated airflow rather than running it at full speed.
What it needs on site
In a condo with no floor drain, or with little ceiling clearance, we usually look at a side-port model instead. Our estimator checks the location, the drain and the duct route before ordering.
Complete spec sheetData and cited sources
- Net airflow at 0.2 in. w.g.
- 146 cfm
- Net airflow at 0.4 in. w.g.
- 127 cfm
- SRE at 0 °C (51 cfm)
- 74%
- SRE at −25 °C (51 cfm)
- 61%
- ASE at 0 °C
- 81%
- Power draw
- 55 W
- Efficacy
- 0.9 cfm/W
- Type
- ERV
- Connection
- Side ports
- Duct collars
- 5 in
- Defrost cycle
- Exhaust only (supply fan off)
- Filters
- 2 washable electrostatic MERV 3 panel filters (11 5/16 × 8 1/8 in); optional MERV 8 (461674) and MERV 13 (461675)
- Dimensions (L × D × H)
- 23.16 × 20.75 × 10.06 in
- Weight
- 35 lb
- Power supply
- 120 V
- HVI certification (Section III)
- 2005017
- Warranty — core
- 5 years
- Warranty — motors
- 7 years
- Warranty — parts
- 5 years
- Spec sheet (French)
- Spec sheet (English)
Net airflow, efficiency at 0 °C and −25 °C, and power draw: Home Ventilating Institute certified products directory, Section III (HVID 2005017). Annual consumption calculated at 55 W running continuously for 8,760 h, at Hydro-Québec's Rate D second tier (11.142 ¢/kWh), in effect since April 1, 2026.
The next model down and up
Talk to an HVAC technician before you choose
We calculate the airflow room by room, check the location and the drain, and give you an installed price. Balancing is measured at commissioning, not estimated.
Le format 120 de la série FIT, prêt pour une fournaise
Le Fantech FIT 120E-D est le grand format de la série FIT, équipé d'un volet motorisé sur l'air extérieur. Son débit net homologué atteint 127 pcm à 0,4 po et 146 pcm à 0,2 po, alors que le FIT 80 plafonne à 78 pcm. Ce ventilateur récupérateur d'énergie (VRE) vise les logements de plusieurs chambres et les maisons de ville dont les besoins dépassent un format 80, tout en gardant un boîtier de 10,06 po d'épaisseur.
Le suffixe -D en fait l'appareil à retenir quand l'échangeur d'air sera raccordé au retour d'une fournaise ou d'un appareil de traitement d'air.
Pourquoi un volet sur l'air extérieur
Raccordé au plénum de retour, un VRE à l'arrêt devient un passage libre : la soufflerie continue d'aspirer et tire de l'air extérieur non tempéré jusque dans la maison. Fantech recommande un appareil avec volet pour les installations partiellement dédiées et simplifiées. Le FIT 120E-D l'intègre d'origine. Sur un modèle sans -D, il faudrait ajouter un volet accessoire, dont le moteur est vendu séparément, et le brancher au connecteur auxiliaire du boîtier électrique.
Plus de débit, même logique
Par rapport au FIT 80, les raccords passent à 5 po et le boîtier grandit un peu : 23,16 × 20,75 × 10,06 po, pour 35 lb. La plage de débit va de 40 à 127 pcm. L'efficacité de récupération sensible est de 74 % à 0 °C (51 pcm) et de 81 % en valeur ajustée. À −25 °C, elle reste à 61 % au même débit, bien au-dessus du seuil de 54 % de la section 9.32 du Code pour le Grand Montréal. En été, la récupération totale est de 64 % à 35 °C, un net progrès par rapport au format 80.
Consommation
Les moteurs à courant alternatif consomment 55 W au débit d'essai de 51 pcm, soit 0,9 pcm/W, et 104 W en haute vitesse selon le guide de sélection Fantech. L'estimation annuelle de la fiche ci-dessus est d'environ 482 kWh. Si la facture d'électricité est votre priorité, le FIT 120E-D-EC, à moteurs EC, descend à 23 W au même débit.
Choisir entre le format 80 et le format 120
Nous ne choisissons pas le format à l'œil. Le calcul de ventilation donne un débit par pièce; s'il dépasse ce qu'un FIT 80 livre à la pression de votre réseau, le FIT 120E-D prend le relais. Le format 120 gagne aussi en efficacité, avec 74 % contre 70 % à 0 °C. En contrepartie, il demande des conduits de 5 po et un peu plus d'espace au plafond.
Les commandes
Le FIT 120E-D accepte les commandes murales Fantech. L'EDF8, par exemple, offre quatre réglages de vitesse : basse, moyenne, haute et 20 minutes par heure. Sa touche AUTO permet à l'occupant de choisir un taux d'humidité; au-delà, l'appareil passe en haute vitesse, puis revient à son mode d'origine. Sans commande murale, le sélecteur MIN, AUTO, MAX près du boîtier électrique suffit à faire fonctionner l'appareil. Fantech souligne qu'une commande accessible à l'occupant améliore le confort et peut réduire nettement la consommation de l'appareil.
Installation
- Raccordement latéral, quatre raccords ronds de 5 po.
- Largeur avec le volet : 25 po, contre 24 5/8 po sans volet.
- Aucun drain requis.
- 8 1/2 po libres devant la porte, 2 3/8 po au-dessus du boîtier électrique.
- Soufflerie de la fournaise en continu, ou asservie par les bornes NO, C et NC.
- Montage exclu avec un système multizone ou plusieurs systèmes à air pulsé.
Filtres
L'appareil est livré avec deux filtres MERV 3 électrostatiques, lavables, de 11 5/16 × 8 1/8 po. Pour filtrer plus fin, Fantech propose des MERV 8 (461674) et MERV 13 (461675).
Garantie
Garantie Fantech : 7 ans sur les moteurs de ventilateur; 5 ans sur le noyau, sur les composants électriques et sur le moteur du volet.
Installation par AirGreen dans le Grand Montréal
À Montréal, à Laval, à Longueuil, sur la Rive-Nord ou sur la Rive-Sud, nous calculons d'abord les débits requis par pièce selon la norme CSA F326. C'est ce calcul qui dit si un format 120 est nécessaire ou si un format 80 suffit. Nous raccordons ensuite le FIT 120E-D au retour de la fournaise et nous équilibrons les deux ventilateurs au débit calculé, soufflerie en marche.
Au répertoire HVI, le FIT 120E-D est homologué à la section III sous le no 2005017. Votre projet peut donc être admissible à l'aide Rénoclimat de 500 $, à la condition que la cote ÉnerGuide s'améliore entre les deux évaluations. L'évaluation doit être faite avant le début des travaux, jamais après.
Pour obtenir une soumission gratuite, téléphonez au 514 316-2973 ou écrivez à sales@airgreen.ca.