AMANA PTH R410A K PTAC Heat Pump | 12,000 BTU | Montreal

In stock
SKU: PTH123K**AXXX
11,600 BTU/h actual≈ 165 to 245 sq ftHeat pump + 5 kW max
Talk to an HVAC technician · 514 316-2973
Heat pump and a heater of up to 5 kWStandard 42 × 16 in sleeve6-year compressor warranty
01 · Your room

Is it the right size for this room?

Amana doesn't publish a room size for this unit. From its 11,600 BTU/h of cooling, we estimate ≈ 165 to 245 sq ft. Choose your room's area.

It's the right size.

For a 175 to 225 sq ft room, this is the range we estimate for this unit: 11,600 BTU/h of cooling, 10,600 BTU/h of heat-pump heating and a heater of up to 5,000 W when the cold calls for it.

AirGreen estimate: Amana publishes no room size, so we apply the application ranges Trane publishes for its PTACs of the same cooling capacity. Our estimator confirms the exact area on site.

02 · Performance

What it does, in numbers

11,600BTU/h
Cooling at 230 V11,400 at 208 V, the supply in many buildings.
10,600BTU/h
Heat-pump heatingRated at 8 °C (47 °F).
5,000W
Maximum electric heater4,100 W at 208 V. It heats when the heat pump can no longer keep up.
11.0EER
Cooling efficiencyThat's 1,055 W drawn at 230 V for 11,600 BTU/h.
What it costs per yearTypical 205 sq ft room · Rate D
Summer · cooling

$23.51

Cooling, all summer

Less than a 60 W light bulb

Bulbs left on day and night for a year. Cooling: 5 h a day for 40 days, the assumption used by Hydro-Québec's air-conditioning calculator. Same calculation for every line: wattage × hours × 11.142 ¢/kWh.

Winter · heating

≈$152

Heating, all winter

≈ $12 less than baseboard heaters

Heat pump8 °C and warmer outside · 10% of the heat≈ $5
Electric heaterBelow 8 °C · 90% of the heat≈ $146

Typical 205 sq ft room with one exterior wall, in Montréal: 1,464 kWh of heat per winter (Environment Canada 1991–2020 climate normals). The heat pump is counted only at 8 °C and warmer, where Amana rates its output; below that, the heater, at the price of a baseboard. If it keeps heating in colder weather, the bill goes down.

≈ $175 for the year, before tax. Winter is 87% of it. If your home stays in the first tier of Rate D in summer (7.065 ¢/kWh), cooling drops to $14.91.

$0.12/h
One hour of cooling
$0.11/h
One hour of heat-pump heating
$0.56/h
One hour on the 5 kW heater

Capacities and currents: Amana catalog MC-DPTAC 10-23 (October 2023) and manual IO-933A (December 2022). Power draw: 1,055 W in cooling (11,600 BTU/h ÷ EER 11.0), 970 W in heat-pump mode, 5,000 W on the 5 kW heater. Hydro-Québec Rate D in effect since April 1, 2026: 11.142 ¢/kWh second tier, before tax.

03 · Good to know

What you should know about this one

Published, verifiable facts, not brochure claims.

11,600What it really delivers in cooling

The name says 12,000 BTU: that's the unit's size class. Amana publishes 11,600 BTU/h at 230 V, and 11,400 at 208 V, the supply in many buildings. Better to read it here than on the spec sheet after installation.

5,000 WThe heater that takes over

At Amana, the two digits after the series letter (the ** in PTH123K**AXXX) set the heater when ordering: 1.5, 2.5, 3.5 or 5.0 kW at 230 V, 1.3 to 4.1 kW at 208 V. At 5.0 kW it takes a 6-30P plug on 30 A; at 3.5 kW, a 6-20P on 20 A. It heats when the heat pump can no longer keep up.

3.2The COP published at 8 °C

Amana publishes a heat-pump COP of 3.2: 10,600 BTU/h of heat at 230 V. Each kWh you pay for gives back 3.2 in heat, against 1 for the heater or a baseboard.

−7 °CWhen the heat pump hands over

Amana switches the unit from heat pump to the heater when the coil drops below 20 °F (−7 °C), or when the heat pump can't keep up on a two-stage thermostat.

1.7Pints of water it removes per hour

The dehumidification Amana publishes in cooling mode: 1.7 pints per hour. It's what keeps a room comfortable in summer without it turning clammy.

7⅝ inHow far it sticks into the room

Amana quotes a 7⅝ in deep front, one of the slimmest in the industry: the unit takes less space out of the room.

4 °CRoom freeze protection

As soon as the unit senses 40 °F (4 °C) or below, it starts the fan and the heater: an empty room won't freeze in winter.

6-30PThe outlet it needs

With the 5.0 kW heater: a NEMA 6-30P plug on a dedicated 30 A circuit. With 3.5 kW: 6-20P on 20 A. With 2.5 kW: 6-15P on 15 A. In a replacement, the outlet already in the wall dictates the heater size.

Replacement

It fits the standard 42 × 16 in sleeve

Amana sleeves have the industry-standard dimensions: 42 in wide, 16 ¹⁄₁₆ in high, 14 ⅛ in deep. Our estimator checks the sleeve and the grille in place before ordering.

42 × 16
inches, standard size
04 · Installation

What it needs on site

42 × 16 in sleeveIndustry-standard size
7⅝ in frontStandard 14 ⅛ in sleeve
Dedicated 30 A circuitFor the 5.0 kW heater (NEMA 6-30P plug)
Condensate thrown on the coilSlinger ring: the water evaporates outside
108 lbUnit weight

In a replacement, we check the outlet and the breaker first: they set the heater size you can use. Our estimator confirms the sleeve, the outlet and the slope before ordering.

Complete spec sheetData and cited sources
Model
PTH123K**AXXX
Cooling capacity (208/230 V)
11,400 / 11,600 BTU/h
Heating capacity, heat pump (208/230 V)
10,500 / 10,600 BTU/h
Electric heater (options)
1.5 kW · 2.5 kW · 3.5 kW · 5.0 kW
EER (208/230 V)
11.1 / 11.0
COP (heat pump, 8 °C)
3.2
Current — compressor
6.1 A
Power — cooling (208/230 V)
1,025 / 1,050 W
Power — heat pump (230 V)
970 W
Airflow (low/high)
245 / 330 cfm
Dehumidification
1.7 pints/h
Application range
≈ 165 to 245 sq ft (AirGreen estimate)
Front
7⅝ in deep
Sleeve
42 × 16 ¹⁄₁₆ in, 14 ⅛ in deep
Net weight
108 lb
Refrigerant
R-410A
Heat pump → heater
coil below 20 °F (−7 °C)
Power supply
208/230 V · 1 ph · 60 Hz

All values: Amana catalog MC-DPTAC 10-23 (October 2023) and manual IO-933A (December 2022). Operating cost: cooling at 1,055 W for 200 h per summer; heating estimated for a typical 205 sq ft room (1,464 kWh of heat per winter, heat pump counted at 8 °C and warmer); at Hydro-Québec's Rate D second tier (11.142 ¢/kWh), in effect since April 1, 2026.

05 · In the same family

The neighbouring models

Talk to an HVAC technician before you choose

We check the existing sleeve, the outlet and the heater size, and give you an installed price. For a building, we order the same series for every room.

The perfect ally for hotel chains for optimal comfort and centralized management

At AirGreen, we know that a successful hotel is not only measured by the quality of its welcome, but also by the consistency and comfort of its indoor environment. That's why we offer the AMANA PTH R410A K | 12,000 BTU PTAC Heat Pump , an ideal HVAC solution for large-scale hotel establishments in Montreal, Laval, Longueuil, on the North Shore and the South Shore . Robust, quiet and equipped with advanced technology, it offers managers the possibility of controlling the entire room fleet from a central point , while maximizing energy savings.

Remarkable energy efficiency

With EERs up to 14.0 and COPs as high as 3.9 , this heat pump is among the most efficient models in its class. For hotel chains, this means lower energy bills while improving guest comfort. In addition, this performance can allow you to benefit from subsidies offered by Quebec electricity companies .

Quiet operation for peaceful sleep

Thanks to a redesigned design with two fan motors (inside and outside) and an inside tangential fan , the noise level is significantly reduced. With an STC rating of 29 , each room benefits from a quiet environment, conducive to rest, even when the machine is running at full capacity.

Smart connectivity for simplified management

  • Built-in Bluetooth® : Configure, adjust and diagnose each unit from the Amana mobile app, available on iOS and Android.

  • Integrated RF Communication : Directly connect each PTAC to the Eden thermostat (sold separately) and the Eden Concierge energy management system, capable of reducing consumption by up to 35% or more .

  • Centralized Control : With the Eden system, manage the temperature, ventilation and operating modes of all rooms from a single station, ideal for large hotels.

A simple and functional design

The Quiet White front panel adds a modern and elegant touch that complements any decor style, from classic to contemporary. At only 7 ⅝" deep , the unit maximizes space in the bedroom while remaining discreet.

Components designed to last

  • Assembled in the USA for over 45 years, with 100% full functional testing before shipping.

  • Full manufacturer's warranty : 6 years on the compressor, 6 years on parts and 6 years on labor.

  • Built-in Filter Dryer : Protects the compressor and extends the life of the unit.

Comfort and safety in all seasons

  • Frost Protection : Automatically activates the fan and heater when the temperature drops to 4°C or lower.

  • Automatic emergency heat : Switches to electric heating if the heat pump is not sufficient to meet demand.

  • Condensate Dispersion System : Quickly removes water produced by cooling, improving efficiency and reducing maintenance.

Turnkey installation for hotels

At AirGreen, we don't just sell a product:

  • Free on-site analysis to assess your needs.

  • Optimized deployment plan to equip all your rooms with a fast and coordinated installation.

  • Centralized configuration so your teams can manage the entire system easily, without moving from room to room.

  • Training and monitoring : We train your maintenance staff to ensure optimal operation and maintenance of the units.

Examples of successful installations

We have already supported several hotel chains in the Montreal area, installing AMANA PTH R410A K PTACs in hundreds of rooms. The result: reduced energy costs, improved guest reviews on thermal comfort, and simplified technical management for staff.


Why choose AirGreen for your hotel HVAC project?

  • A team of experienced, RBQ-certified refrigeration engineers.

  • Transparent prices, communicated before work begins.

  • No deposit: you only pay when you are 100% satisfied.

  • Fast and reliable after-sales service, always available for your technical needs.


Key technical features :

  • Cooling capacity : 12,000 BTU

  • Refrigerant : R-410a

  • Dimensions (W x D x H) : 42 x 21.5 x 16 in

  • Voltage : 220 V

  • Warranty : 6-6-6 (compressor-parts-labor)


AirGreen – Your HVAC Partner for Hotels
We help major hotel chains achieve optimal guest comfort while simplifying technical management and reducing energy consumption. The AMANA PTH R410A K | 12,000 BTU PTAC Heat Pump is the ideal choice for combining performance, reliability, and centralized control.

📞 Contact us today to discuss your project and get a free on-site estimate .

Warranty: 6 years on the compressor, 6 years on parts and 6 years on labor, straight from the distributor.