GOODMAN//Wall air conditioners
Goodman wall air conditioners: which circuit, and how much cooling
Five Series 19 wall air conditioners, from 9,000 to 24,000 BTU/h, with no heating. Only one runs on 115 V: the 12,000 MSC121E19. The other four need a 208-230 V circuit. The tool matches your circuit to the right model, with the cooling and the amps GOODMAN publishes.
The question this page answers115 V or 208-230 V: which Goodman 19 fits my circuit, and how much does it really cool?
The five GOODMAN air conditioners we sell
Four on 208-230 V, one on 115 V, all on R-410A. Each product page opens a quote request.
Tool//My circuit
My circuit: the right model, its amps and its cooling
Pick your circuit, then the size. On 115 V, only the 12,000 exists: the other sizes grey out. The bars compare the current of all five models.
12,000 BTU/h air conditioner on 208-230 V
MSC123E19MCAA + MSC123E19AXAA
- Rated cooling
- 11,500 BTU/h500 BTU/h below the 12,000 in its name
- Input power
- 1,037 Win cooling
- Rated current
- 4.5 Ain cooling
- Minimum circuit ampacity
- 11 A
- Maximum fuse
- 15 A
Rated current of the five models, in cooling
208-230 V single-phase circuit. The minimum circuit ampacity and the maximum fuse above set that circuit. 115 V exists only at 12,000.
See the MSC123E19 product pageValues at the cooling rating point, 03-21 brochure; the 06-21 revision prints the same ones. Minimum circuit ampacity and maximum fuse are the circuit values GOODMAN gives.
GOODMAN//Specifications
The five air conditioners, side by side
Values from the 03-21 brochure (source 1, p. 4); the 06-21 revision prints the same ones unless noted (source 2, p. 4).
| Published value | 9,000 | 12,000, 115 V | 12,000 | 18,000 | 24,000 |
|---|---|---|---|---|---|
| Outdoor unit | MSC093E19MCAA | MSC121E19MCAA | MSC123E19MCAA | MSC183E19MCAA | MSC243E19MCAA |
| Power supply | 208-230 V | 115 V | 208-230 V | 208-230 V | 208-230 V |
| SEER | 19 | 16.5 | 19 | 20 | 19 |
| Indoor sound high / medium / low, dB(A) | 38 / 32 / 26.5 | 38.5 / 33 / 24.5 | 37.5 / 34.5 / 24.5 | 42 / 34.5 / 30.5 | 46 / 40.5 / 34.0 |
| Outdoor sound, dB(A) | 51.0 | 51.5 | 51.5 | 53.5 | 57.0 |
| Indoor unit W × D × H, in | 28.4 × 7.36 × 11.42 | 31.6 × 7.5 × 11.7 | 31.6 × 7.5 × 11.7 | 38 × 8.5 × 12.6 | 42.5 × 8.9 × 13.2 |
| Refrigerant lines liquid / gas, in | 1/4 / 3/8 | 1/4 / 1/2 | 1/4 / 1/2 | 1/4 / 1/2 | 3/8 / 5/8 |
| Maximum line length / maximum lift, ft | 82 / 33 | 82 / 33 | 82 / 33 | 98 / 66 | 98 / 66 |
| Precharge, ft | 20 | 20 | 20 | 20 | 30 |
Highlighted: what sets one model apart from the other four. Height of the 9,000 head: 11.3 in in the 03-21 brochure, 11.42 in in the 06-21 revision; we use the revision. SEER of the 18,000: 20, while GOODMAN's table is headed "up to 19 SEER"; we quote both. GOODMAN does not say where sound is measured.
GOODMAN//Published cooling
How much cooling, really
An air conditioner's name gives its size; the brochure gives its rated cooling (source 1, p. 4). The two do not always match.
| Model | Size in the name, BTU/h | Rated cooling, BTU/h | Difference, BTU/h (AirGreen calculation) |
|---|---|---|---|
| MSC093E19 | 9,000 | 9,000 | 0 |
| MSC121E19, 115 V | 12,000 | 12,000 | 0 |
| MSC123E19 | 12,000 | 11,500 | -500 |
| MSC183E19 | 18,000 | 17,000 | -1,000 |
| MSC243E19 | 24,000 | 22,000 | -2,000 |
Highlighted: the three models out of five for which GOODMAN publishes a rated cooling below the size in the name. That rated figure is what we compare with the room's needs, not the name.
Compare//Same nominal size
Air conditioner or Series 19 heat pump, at 12,000 BTU/h
Same series, same size in the name. The air conditioner needs a lower minimum circuit ampacity; the heat pump adds heating.
GOODMAN data, source 1, p. 4 and 5
| At 12,000 BTU/h | Air conditioner | Series 19 heat pump |
|---|---|---|
| Rated cooling | 11,500 BTU/h | 12,000 BTU/h |
| Cooling input power | 1,037 W | 1,065 W |
| Cooling rated current | 4.5 A | 4.5 A |
| Minimum circuit ampacity / maximum fuse | 11 / 15 A | 15 / 15 A |
| SEER | 19 | 19.0 |
| R-410A charge | 18.7 oz | 29.6 oz |
| Rated heating at 8.3 °C | none | 12,000 BTU/h |
For the heat pump's five sizes, see the Series 19 page.
Did you know//GOODMAN documents
Three air conditioner details from GOODMAN's brochure
The 115 V model gives less cooling per watt
GOODMAN publishes an EER of 10.0 for the 12,000 on 115 V, against 11.0 for the 12,000 on 208-230 V, or 11.1 in the 06-21 revision.
Source 1, p. 4; source 2, p. 4The narrowest wall head in the brochure: 28.4 in
The 9,000 MSC093E19 has a 28.4 in wide head. Every other wall head in the 2021 brochure, air conditioners and Series 19 and 21 heat pumps alike, is at least 31.6 in wide.
Source 1, p. 4 to 6From 12,000 to 18,000, more than twice the air
At high speed, GOODMAN publishes 242 cfm for the head of the 12,000 on 208-230 V and 530 cfm for the 18,000's. The 06-21 revision prints 241 and 529.
Source 1, p. 4; source 2, p. 4AirGreen × GOODMAN//Who brings what
What each one brings to your air conditioner
What GOODMAN brings
- Five wall air conditioners, from 9,000 to 24,000 BTU/h, on R-410A
- A 12,000 on 115 V, the other four on 208-230 V single phase
- A rated cooling published for each model, sometimes below the size in its name
- The minimum circuit ampacity and maximum fuse of each model
What AirGreen brings
- A look at your electrical panel before the circuit is chosen
- Installation by our refrigeration technicians, under AirGreen's RBQ licence 5645-9605-01
- The refrigerant line route between the head and the outdoor unit
- Sizing from the room, not from the model name
Questions//Wall air conditioners
Questions about GOODMAN wall air conditioners
Does the 115 V model plug into an outlet?
GOODMAN mentions no plug. It gives a 115 V power supply, a minimum circuit ampacity of 15 A and a maximum fuse of 20 A: those are circuit values. We look at what your panel allows during the visit.
208 V or 230 V: do I have to choose?
No. GOODMAN publishes a single power supply, 208-230 V single phase, for the 9,000, the 12,000, the 18,000 and the 24,000.
Can a wall air conditioner heat in winter?
No. The MSC…E19 units are air conditioners: GOODMAN publishes no heating value for them. To heat with a wall head, you need a wall heat pump.
Can I add a second room later?
Not on the same outdoor unit: a second room needs a second system. These air conditioners are single zone, one head per outdoor unit. In the same brochure, GOODMAN's multi-zone outdoor units are Series 21 heat pumps, like those in our 2-zone systems.
Minimum circuit ampacity and maximum fuse: what are those two figures for?
The minimum circuit ampacity sets the smallest wire size that can feed the unit; the maximum fuse is the largest protection allowed on that circuit. GOODMAN publishes both for each model.
Read next//The GOODMAN space
Related pages
A GOODMAN air conditioner in your home: we start with the panel
We open the electrical panel first, then look at the room and the wall for the outdoor unit. The panel decides between 115 V and 208-230 V; the room decides the size.
Sold and installed by AirGreen.Montreal, Laval, Longueuil, the South Shore and the North Shore.
An AirGreen technician assesses the room's cooling needs, your electrical panel, where the units will go and the refrigerant line route on site before proposing a model.
Subclasses 15.8, 15.10 and 16. Gas and oil work is done by a partner holding the required licence.
The equipment is GOODMAN-branded. AirGreen sells it, installs it and services it across Greater Montreal.
Sources
- GOODMAN, "Heat Pump and Air Conditioner Ductless Units", 19 Series and 21 Series, code CB-DL-1921S-HP 03-21, p. 4 to 6. GOODMAN document kept in AirGreen's files.
- GOODMAN, same brochure, revision CB-DL-1921S-HP 06-21, p. 4.
Read and dated by AirGreen. Capacities and limits are the ones GOODMAN publishes; a real installation can give other values.