In HAXXAIR’s HVHM-36T2D table, a four-head combination never has more than two 18,000 BTU/h heads, and only with two 9,000 heads: 9,000 + 9,000 + 18,000 + 18,000.
HAXXAIR catalogue, combination table
Sold and installed by AirGreen.Montreal, Laval, Longueuil, South Shore and North Shore
HAXXAIR 4-zone heat pump · HVHM-36T2D or HVHM-42T2D
Four rooms: the HVHM-36T2D or the HVHM-42T2D. At full output, the HVHM-42T2D adds hardly any heat in the cold: the same maximums at −8.3 °C and at −15 °C on the NEEP list, a 500 BTU/h gap at −25 °C. It delivers more in cooling and in mild weather, with a better COP at full output but a lower EER2 at rated output (10.5 vs 12.5), and it is the only one we also offer in 5 zones.
For each NEEP test condition, we work out the electrical power the two 4-zone units draw at full output, from their maximum and the COP at that maximum. COP: kWh of heat delivered (or removed, in cooling) per kWh of electricity. Starting point: −8.3 °C.
At −8.3 °C, at full output, both deliver 40,000 BTU/h; the HVHM-42T2D draws 5.8 kW, the HVHM-36T2D 6.2 kW.
The bars show the electrical power, from 0 to 7 kW.
HVHM-36T2D and HVHM-42T2D: maximum output, COP at maximum and electrical power, by NEEP test condition
| Condition | HVHM-36T2D | HVHM-42T2D |
|---|---|---|
| Heating, 8.3 °C | 48,000 BTU/h · COP 2.34 · 6.0 kW | 52,000 BTU/h · COP 2.36 · 6.5 kW |
| Heating, −8.3 °C | 40,000 BTU/h · COP 1.89 · 6.2 kW | 40,000 BTU/h · COP 2.02 · 5.8 kW |
| Heating, −15 °C | 36,000 BTU/h · COP 1.84 · 5.7 kW | 36,000 BTU/h · COP 1.84 · 5.7 kW |
| Heating, −25 °C | 25,200 BTU/h · COP 1.34 · 5.5 kW | 25,700 BTU/h · COP 1.38 · 5.5 kW |
| Cooling, 35 °C | 42,000 BTU/h · COP 2.46 · 5.0 kW | 50,000 BTU/h · COP 2.66 · 5.5 kW |
NEEP list, entries 425474 (HVHM-36T2D) and 425406 (HVHM-42T2D), checked November 5, 2026; test temperatures 47, 17, 5 and −13 °F in heating, 95 °F in cooling. Electrical power: our calculation, maximum output ÷ COP at maximum, 1 kW = 3,412 BTU/h. At 8.3 °C, the HAXXAIR catalogue gives other values for the HVHM-36T2D: see the multi-zone page.
At −8.3 °C, the ENERGY STAR record does not give them the same rated output: 27,000 BTU/h for the HVHM-42T2D, 22,400 for the HVHM-36T2D. That is the value we use for the LogisVert indicative amount, $3,240 vs $2,688, i.e. $552 more for the HVHM-42T2D by our calculation. Only Hydro-Québec confirms the amount granted.
| Feature | HVHM-36T2D | HVHM-42T2D |
|---|---|---|
| Heads | 2 to 4 (HAXXAIR table) | offered in 2 to 5 zones, no HAXXAIR table |
| AHRI | 204100526 | 212510994 |
| ENERGY STAR Canada | 3542752 · cold climate | 4652577 · cold climate |
| Heating at −8.3 °C, rated (ENERGY STAR record) | 22,400 BTU/h | 27,000 BTU/h |
| SEER2 | 21 | 20 |
| EER2 | 12.5 | 10.5 |
| HSPF2 (region IV / V) | 9 / 7.84 | 8.95 / 7.97 |
| Minimum circuit ampacity (MCA) | 32.2 A (HAXXAIR catalogue; 33 A on our product listings) | 35 A (our product listing) |
| Maximum protection | 50 A, fuse (HAXXAIR) | 50 A, MOP (our listing) |
| LogisVert, indicative amount | $2,688 | $3,240 |
Efficiencies and outputs: NEEP list and ENERGY STAR Canada list, for the HVHM-36T2D and HVHM-42T2D. EER2: cooling efficiency at 35 °C, at rated output; SEER2 and HSPF2: seasonal cooling and heating efficiency, region V standing for a colder climate than region IV; the higher the better.
LogisVert. Hydro-Québec’s LogisVert guide v1.10 (September 15, 2026) gives $120 (ENERGY STAR cold climate) or $50 (ENERGY STAR) per 1,000 BTU/h at −8 °C, for an outdoor unit of at least 12,000 BTU/h nominal cooling capacity. We use the heating capacity at 17 °F (−8.3 °C) from the ENERGY STAR record. This is an indicative amount. Only Hydro-Québec confirms the amount granted. Here: the rated −8.3 °C row of the table above. The program’s conditions are on our HAXXAIR page.
In HAXXAIR’s HVHM-36T2D table, a four-head combination never has more than two 18,000 BTU/h heads, and only with two 9,000 heads: 9,000 + 9,000 + 18,000 + 18,000.
HAXXAIR catalogue, combination table
In HAXXAIR’s HVHM-36T2D table, the four connections A to D are all the same size, 1/4 × 3/8 in: the table lists no larger one for the combinations with 18,000 BTU/h heads.
HAXXAIR catalogue, HVHM-36T2D table
At four heads, the total length counts too: for the HVHM-36T2D, HAXXAIR publishes 65 ft at most to each head but 246 ft in total, less than four lines at their maximum (260 ft, our calculation).
HAXXAIR catalogue, HVHM-36T2D table
Residential. “Five-year warranty on parts and compressor for a residential installation.” (our translation)
Commercial. “One-year warranty on parts and five-year warranty on the compressor for a commercial installation.” (our translation)
HAXXAIR product catalogue. The catalogue says it applies to “all current models in Canada” (our translation) but does not name the HVHM-42T2D. Our quote states what applies to your installation.
Both are possible. HAXXAIR publishes 12,000 + 12,000 + 12,000 + 12,000 for the HVHM-36T2D, i.e. 48,000 BTU/h of heads, and our 4-zone HVHM-42T2D listing also offers 12,000 heads. At −15 °C, the NEEP list gives both at most 36,000 BTU/h, shared among the four heads.
At full output, by our calculation from the NEEP values: at −8.3 °C, the HVHM-42T2D draws 5.8 kW against 6.2 kW for the same heat; at −15 °C and at −25 °C, both draw the same; in mild weather and in cooling, it draws more, but also delivers more. These kW are full-load draws, not the annual consumption of the HVHM-36T2D or HVHM-42T2D. In seasonal efficiency (NEEP list), the HVHM-36T2D does better in cooling (SEER2 21 vs 20) and in region IV heating (HSPF2 9 vs 8.95); the HVHM-42T2D does better in region V, the one Natural Resources Canada uses for a climate like Ottawa’s (7.97 vs 7.84).
HAXXAIR’s HVHM-36T2D table stops at four heads. If a fifth room is planned, tell us when you request the quote: we offer only the HVHM-42T2D in 5 zones, with 9,000 or 12,000 heads on our listing.
The price depends on the choice between the HVHM-36T2D and the HVHM-42T2D, the four heads and the electrical circuit. Request a quote and we’ll come and take a look.