AirGreenHAXXAIR

Sold and installed by AirGreen.Montreal, Laval, Longueuil, South Shore and North Shore

HAXXAIR 4-zone heat pump · HVHM-36T2D or HVHM-42T2D

HAXXAIR 4-zone heat pump: HVHM-36T2D or HVHM-42T2D, what do you gain in the cold?

Four rooms: the HVHM-36T2D or the HVHM-42T2D. At full output, the HVHM-42T2D adds hardly any heat in the cold: the same maximums at −8.3 °C and at −15 °C on the NEEP list, a 500 BTU/h gap at −25 °C. It delivers more in cooling and in mild weather, with a better COP at full output but a lower EER2 at rated output (10.5 vs 12.5), and it is the only one we also offer in 5 zones.

At full output: what the two 4-zone units deliver, and what they draw

For each NEEP test condition, we work out the electrical power the two 4-zone units draw at full output, from their maximum and the COP at that maximum. COP: kWh of heat delivered (or removed, in cooling) per kWh of electricity. Starting point: −8.3 °C.

Heating, outdoor temperature
Cooling, outdoor temperature
T2D HVHM-36T2D
Maximum output
40,000 BTU/h
COP at maximum
1.89
Electrical power
6.2 kW
T2D HVHM-42T2D
Maximum output
40,000 BTU/h
COP at maximum
2.02
Electrical power
5.8 kW

At −8.3 °C, at full output, both deliver 40,000 BTU/h; the HVHM-42T2D draws 5.8 kW, the HVHM-36T2D 6.2 kW.

The bars show the electrical power, from 0 to 7 kW.

The two 4-zone units at all five NEEP test conditions

HVHM-36T2D and HVHM-42T2D: maximum output, COP at maximum and electrical power, by NEEP test condition

ConditionHVHM-36T2DHVHM-42T2D
Heating, 8.3 °C48,000 BTU/h · COP 2.34 · 6.0 kW52,000 BTU/h · COP 2.36 · 6.5 kW
Heating, −8.3 °C40,000 BTU/h · COP 1.89 · 6.2 kW40,000 BTU/h · COP 2.02 · 5.8 kW
Heating, −15 °C36,000 BTU/h · COP 1.84 · 5.7 kW36,000 BTU/h · COP 1.84 · 5.7 kW
Heating, −25 °C25,200 BTU/h · COP 1.34 · 5.5 kW25,700 BTU/h · COP 1.38 · 5.5 kW
Cooling, 35 °C42,000 BTU/h · COP 2.46 · 5.0 kW50,000 BTU/h · COP 2.66 · 5.5 kW

NEEP list, entries 425474 (HVHM-36T2D) and 425406 (HVHM-42T2D), checked November 5, 2026; test temperatures 47, 17, 5 and −13 °F in heating, 95 °F in cooling. Electrical power: our calculation, maximum output ÷ COP at maximum, 1 kW = 3,412 BTU/h. At 8.3 °C, the HAXXAIR catalogue gives other values for the HVHM-36T2D: see the multi-zone page.

HVHM-36T2D or HVHM-42T2D: the two units side by side

At −8.3 °C, the ENERGY STAR record does not give them the same rated output: 27,000 BTU/h for the HVHM-42T2D, 22,400 for the HVHM-36T2D. That is the value we use for the LogisVert indicative amount, $3,240 vs $2,688, i.e. $552 more for the HVHM-42T2D by our calculation. Only Hydro-Québec confirms the amount granted.

FeatureHVHM-36T2DHVHM-42T2D
Heads2 to 4 (HAXXAIR table)offered in 2 to 5 zones, no HAXXAIR table
AHRI204100526212510994
ENERGY STAR Canada3542752 · cold climate4652577 · cold climate
Heating at −8.3 °C, rated (ENERGY STAR record)22,400 BTU/h27,000 BTU/h
SEER22120
EER212.510.5
HSPF2 (region IV / V)9 / 7.848.95 / 7.97
Minimum circuit ampacity (MCA)32.2 A (HAXXAIR catalogue; 33 A on our product listings)35 A (our product listing)
Maximum protection50 A, fuse (HAXXAIR)50 A, MOP (our listing)
LogisVert, indicative amount$2,688$3,240

Efficiencies and outputs: NEEP list and ENERGY STAR Canada list, for the HVHM-36T2D and HVHM-42T2D. EER2: cooling efficiency at 35 °C, at rated output; SEER2 and HSPF2: seasonal cooling and heating efficiency, region V standing for a colder climate than region IV; the higher the better.

LogisVert. Hydro-Québec’s LogisVert guide v1.10 (September 15, 2026) gives $120 (ENERGY STAR cold climate) or $50 (ENERGY STAR) per 1,000 BTU/h at −8 °C, for an outdoor unit of at least 12,000 BTU/h nominal cooling capacity. We use the heating capacity at 17 °F (−8.3 °C) from the ENERGY STAR record. This is an indicative amount. Only Hydro-Québec confirms the amount granted. Here: the rated −8.3 °C row of the table above. The program’s conditions are on our HAXXAIR page.

Did you know?

In HAXXAIR’s HVHM-36T2D table, a four-head combination never has more than two 18,000 BTU/h heads, and only with two 9,000 heads: 9,000 + 9,000 + 18,000 + 18,000.

HAXXAIR catalogue, combination table

In HAXXAIR’s HVHM-36T2D table, the four connections A to D are all the same size, 1/4 × 3/8 in: the table lists no larger one for the combinations with 18,000 BTU/h heads.

HAXXAIR catalogue, HVHM-36T2D table

At four heads, the total length counts too: for the HVHM-36T2D, HAXXAIR publishes 65 ft at most to each head but 246 ft in total, less than four lines at their maximum (260 ft, our calculation).

HAXXAIR catalogue, HVHM-36T2D table

Warranty as published by HAXXAIR

Residential. “Five-year warranty on parts and compressor for a residential installation.” (our translation)

Commercial. “One-year warranty on parts and five-year warranty on the compressor for a commercial installation.” (our translation)

HAXXAIR product catalogue. The catalogue says it applies to “all current models in Canada” (our translation) but does not name the HVHM-42T2D. Our quote states what applies to your installation.

Frequently asked questions

Four 12,000 heads: which unit?

Both are possible. HAXXAIR publishes 12,000 + 12,000 + 12,000 + 12,000 for the HVHM-36T2D, i.e. 48,000 BTU/h of heads, and our 4-zone HVHM-42T2D listing also offers 12,000 heads. At −15 °C, the NEEP list gives both at most 36,000 BTU/h, shared among the four heads.

Does the HVHM-42T2D use more electricity than the HVHM-36T2D?

At full output, by our calculation from the NEEP values: at −8.3 °C, the HVHM-42T2D draws 5.8 kW against 6.2 kW for the same heat; at −15 °C and at −25 °C, both draw the same; in mild weather and in cooling, it draws more, but also delivers more. These kW are full-load draws, not the annual consumption of the HVHM-36T2D or HVHM-42T2D. In seasonal efficiency (NEEP list), the HVHM-36T2D does better in cooling (SEER2 21 vs 20) and in region IV heating (HSPF2 9 vs 8.95); the HVHM-42T2D does better in region V, the one Natural Resources Canada uses for a climate like Ottawa’s (7.97 vs 7.84).

What if a fifth room is added to the four?

HAXXAIR’s HVHM-36T2D table stops at four heads. If a fifth room is planned, tell us when you request the quote: we offer only the HVHM-42T2D in 5 zones, with 9,000 or 12,000 heads on our listing.

Sources

Price of an installed HAXXAIR 4-zone heat pump

The price depends on the choice between the HVHM-36T2D and the HVHM-42T2D, the four heads and the electrical circuit. Request a quote and we’ll come and take a look.