01On R-454B, the 18,000 needs a 16 A circuit (20 A maximum fuse) on the Regular and 17.5 A (20 A) on the Max Performance; on R-410A, 18 A (25 A) and 20 A (25 A).
Bosch, 18K Multi Zone Regular and Max Performance sheets, Gen 4, BTC 769208364 B and 769208365 B (01.2026), and R-410A, BTC 769108336 B and 769108334 B (03.2023)
02On R-454B as on R-410A, Bosch allows up to 15 m (49 ft) of height between the outdoor unit and a head, and 10 m (33 ft) between two heads.
Bosch, Gen 4 multi-zone installation manual, BTC 769203312 D (04.2026); R-410A multi-zone manual, BTC 769103307 B (06.2022), table 4
03The 18,000 R-454B comes with its 3/8 to 1/2 in adapters: two for the Regular, three for the Max Performance.
Bosch, Climate 5000 Gen 4 multi-zone service manual, BTC 769202304 A (04.2025), table 24