FORESTAIR · E24 · MZ · E-TECH+FORESTAIR at AirGreenSold and installed by AirGreen. We install in Montréal, Laval, Longueuil, on the South Shore and on the North Shore.
All of FORESTAIR
Updated November 11, 2026
Multi-zone, 5 heads · FORESTAIR

Multi-zone heat pump, 5 zones: five rooms on one FORESTAIR FA-M42

Yes: the FA-M42’s submittal allows up to five indoor units. Three limits frame the lines, 90 m in total, 30 m per line and 10 m of elevation, and the 79 kg unit takes a breaker of up to 45 A. Beyond 37.5 m of lines, the submittal calls for 10 g of R-454B per metre; we work it out at the visit.

1five-head system, on the FA-M42
3,400 gof R-454B charged at the factorysubmittal
18 mper line on average for five lines, submittal total reachedour calculation
23,000BTU/h maximum at −25 °C for the FA-M42’s non-ducted combinationNEEP
FA-M42 · up to 5 headsA single outdoor unit
The shop

Multi-zone, 5 zones: the FA-M42 system in the shop

One FA-M42 outdoor unit and five wall heads. The FA-M42 systems with 2, 3 and 4 heads have their own pages.

FORESTAIR
The R-454B for five lines

Five lines on the FA-M42: total length, margin and R-454B to add

The FA-M42 leaves the factory already charged for part of the lines. Pick the planned total length of your lines: the calculation gives the margin under the submittal’s 90 m and the refrigerant to add.

FORESTAIR
Your five lines, in total

FA-M42-D5TL/O submittal (footer 112025), piping data: factory charge of 3,400 g of R-454B for 37.5 m of line, 10 g per metre beyond that, 90 m of line in total and 30 m per line. The calculation is ours; it assumes one line per head, since the submittal does not publish the number of connections. Elevation, 10 m at most, and the actual length of each line are measured at the on-site assessment.

FA-M42 · five lines, 60 m in total

225 gof R-454B to add (our calculation, at the submittal’s rate)

Margin under the published total30 m
Total system charge3,625 g
Calculation(60 − 37.5) m × 10 g
Average per line12 m (30 m at most)
The comparison that matters

Five rooms: one FA-M42 or two units, an FA-M27 (3 heads) and an FA-M18 (2 heads)?

One outdoor unit and one circuit, or two of each. Heating capacity comes from NEEP’s public list of cold-climate heat pumps: it lists 30,000 BTU/h at −15 °C for the FA-M42. Every figure is given per unit.

FORESTAIR
For five roomsOne FA-M42, five headsFA-M27 + FA-M18
Outdoor units1 · 1,074 × 853 × 468 mm · 79 kg2 · 978 × 803 × 421 mm (359 mm in the dimensions table), 54 kg · 927 × 699 × 380 mm, 42 kg
Heating capacity at −15 °C (NEEP, non-ducted)30,000 BTU/h19,800 and 16,000 BTU/h
Maximum at −25 °C (NEEP)23,000 BTU/h14,000 and 11,000 BTU/h
Breaker at most (and minimum circuit ampacity, MCA)45 A (28 A), one circuit30 A (18 A) and 25 A (16 A), two circuits
Lines: total · per line90 m · 30 m60 m · 30 m, and 40 m · 25 m
Outdoor sound (sound pressure)65 dB(A)62 and 58 dB(A)
SEER2 (cooling, over a season)22.024.0 and 24.0
LogisVert, indicative amount$3,720$2,688 and $2,400, per unit
FA-M42, FA-M27 and FA-M18 submittals (footer 112025); NEEP records 508676, 508678 and 508679. NEEP gives neither the number nor the size of the heads in the listed combination; your system’s capacity depends on the heads chosen. The two units are not added up: each keeps its own figures. Sound: the submittals’ sound pressure, with no measuring distance. Québec.ca reference points: 40 dB(A) is perceived as peaceful; 50 dB(A) is where noise starts to disturb. Indicative amount. Only Hydro-Québec confirms the assistance granted. The FA-M27 with three heads · The FA-M18 with two heads · A home with ducts? The E-TECH+ central heat pump
Did you know?

The 5-zone FA-M42: NEEP record, capacity and pre-charge

FORESTAIR
1 non-ducted NEEP record

the same for our FA-M42 systems with 2, 3, 4 and 5 heads

Without ducts, NEEP lists the FA-M42 as a single combination (508676), with no indoor unit named; our four FA-M42 systems carry its AHRI number, 217512364. The ducted combination has its own record, 508672.

NEEP record 508676, read November 5, 2026; our FA-M42 product pages.
42,000 · 42,000

the FA-M42 publishes the same heating and cooling capacity, in nominal BTU/h

Per its submittal, the FA-M42 publishes 42,000 BTU/h in nominal heating and 42,000 BTU/h in nominal cooling. Of the four FA-M units, it is the only one whose two figures are equal.

FA-M18 to FA-M42 submittals: System Ratings.
7.5 m per head

the FA-M42’s pre-charged length divided by its five heads at most; the same ratio on the three other submittals (our calculation)

Length covered by the factory charge: 15 m for the FA-M18 (2 heads at most), 22.5 m for the FA-M27 (3), 30 m for the FA-M36 (4) and 37.5 m for the FA-M42 (5), or 7.5 m per head (our calculation).

FA-M18 to FA-M42 submittals: Refrigerant Piping Data; AirGreen calculation.
What we check in your home

Five lines on one FA-M42: what we measure in your home

FORESTAIR
  • The R-454B to add, to the gram: up to 525 g when your five lines reach the submittal’s total (our calculation).
  • The power supply: the FA-M42 submittal lists an MCA of 28 A, the current the unit’s wiring must hold at a minimum.
Frequently asked questions

FORESTAIR multi-zone, 5 zones: common questions

FORESTAIR
What breaker for a 5-zone FORESTAIR system?

For the FA-M42 system, 45 A at most on 208-230 V, with a minimum circuit ampacity of 28 A, per the submittal. The submittal publishes a single value for the unit; it does not say whether it varies with the number of heads, nor how the heads are powered. We check the panel at the on-site assessment.

Five rooms: one big unit or two smaller ones?

An FA-M42 needs one outdoor unit and one circuit; an FA-M27 with three heads and an FA-M18 with two need two of each. For their non-ducted combinations, NEEP lists 30,000 BTU/h at −15 °C for the FA-M42, and 19,800 and 16,000 BTU/h for the FA-M27 and FA-M18, without naming any heads. We decide it with you at the visit.

One FA-M42 or two units: which is quieter outside?

The FA-M42 submittal publishes 65 dB(A) for its outdoor unit; those of the FA-M27 and FA-M18, 62 and 58 dB(A), but there are then two units outside. These are sound pressures with no measuring distance, and none of these submittals publishes the heads’ noise. Québec.ca reference points: 40 dB(A) is perceived as peaceful; 50 dB(A) is where noise starts to disturb.

With a ducted head, which NEEP figures apply to the FA-M42?

Those of another record, 508672 (AHRI 217512368), which contradicts itself: its nominal value is above its maximum at −8.3 °C (34,400 against 32,000 BTU/h) and at −15 °C (33,000 against 30,400 BTU/h). We repeat it as listed, without correcting it. The submittal itself does not change: same lines, same charge, same breaker.

How much LogisVert assistance for a 5-zone FORESTAIR system?

$3,720, indicative amount from our product page. It comes from 31,000 BTU/h, the heating capacity NEEP lists at −8.3 °C for the FA-M42’s non-ducted combination, × $120 per 1,000 BTU/h, the LogisVert guide v1.10 rate at −8 °C for an ENERGY STAR “cold climate” heat pump: $3,720. NEEP does not decide the assistance: the guide looks to ENERGY STAR heat pumps. Only Hydro-Québec confirms the assistance granted.

Sold and installed by AirGreen.

Before the visit: five rooms, one unit outside

  • Does one of the five rooms have ducts? Tell us: NEEP then lists the FA-M42 under another number, 508672.
  • The distance to each room: 30 m at most per line, 90 m in total.
RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16. Gas and oil: a licensed partner.
Free estimateAt home, no commitment.
LogisVert on the quoteAHRI number and indicative amount when the unit qualifies. Only Hydro-Québec confirms the assistance granted.
Showroom1370 Joliot-Curie Street, Suite 712, Boucherville.

Hydro-Québec never solicits by phone or door to door for the LogisVert Efficient Homes Program.

AirGreenFORESTAIR

Sources

  1. FORESTAIR, submittal data FA-M18-D2TL/O, “Multizone Series Condensing Unit”, footer 112025, © FORESTAIR 2025. PDF
  2. FORESTAIR, submittal data FA-M27-D3TL/O, “Multizone Series Condensing Unit”, footer 112025, © FORESTAIR 2025. PDF
  3. FORESTAIR, submittal data FA-M36-D4TL/O, “Multizone Series Condensing Unit”, footer 112025, © FORESTAIR 2025. PDF
  4. FORESTAIR, submittal data FA-M42-D5TL/O, “Multizone Series Condensing Unit”, footer 112025, © FORESTAIR 2025. PDF
  5. NEEP, Cold Climate Air Source Heat Pump List, records 508676, 508678, 508679 and 508672, read November 5, 2026. ashp.neep.org
  6. ENERGY STAR, heat pump registry, Canadian market (dataset w7cv-9xjt), record 4529626, read November 5, 2026. data.energystar.gov
  7. Hydro-Québec, LogisVert Efficient Homes Program, participant’s guide, version 1.10 (September 15, 2026). Indicative amounts: those on our product pages. hydroquebec.com
  8. Government of Québec, “Noise measurement”, updated June 16, 2022. quebec.ca

Page updated November 11, 2026.