MIDEA EVOX G3 and GREE FLEXX ULTRA, 5 tons

Comparison · Central heat pump · 5 tons

MIDEA EVOX G3 and GREE FLEXX ULTRA R32, 5 tons

Two central heat pumps for a large house. At 5 tons, the electrical service and the ductwork often set the limits: here is what each manufacturer requires, next to the certified values.

GREE FLEXX ULTRA R32, AirGreen product card GREE

FLEXX ULTRA R32 · 5 tons

FXU60HP230V1R32AH + FXU60HP230V1R32AO · AHRI 215213332 See the product page
Certified rated heating at 8.3 °C, BTU/h55,000and54,000
SEER2 (AHRI certificate)17.5and18.2
HSPF2 Region V7.7and7.8
Certified max. heating at −30 °C, BTU/h37,300and27,000
Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 60,000 BTU/h house in Montréal, on Hydro-Québec Rate D, taxes included. The certificates give 54,000 BTU/h (MIDEA) and 53,000 BTU/h (GREE) of cooling at 35 °C; the calculation uses the common nominal size, 5 tons. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the benchmark.

How this amount is calculated
  1. Heat needed over the winter. A house whose heat loss reaches 60,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: a simplification that ignores the recovery after a setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup planned for when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
  3. Electricity for cooling. 60,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
  4. Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. The network access fee, the same with or without a heat pump, is not counted.

AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, insulation, settings and use; this amount is not a promise.

What the installation needs

Circuits, backup heat and airflow, system by system

Pick a system: the house cross-section shows what its submittal sheet requires, from the outdoor unit to the ducts. Values are the manufacturers'; sizing the electrical service and the ducts is a job for a master electrician and an estimator.

MIDEA submittal sheet MAUSE-H60B-2A / MO1HE-H60B-2A.

Extreme cold

What each one publishes below −15 °C, at 5 tons

At −30 °C, the NEEP certificates give a maximum of 37,300 BTU/h for the EVOX G3 and 27,000 BTU/h for the FLEXX ULTRA, against 55,000 and 54,000 BTU/h rated at 8.3 °C. Between −15 and −30 °C, GREE also publishes a capacity table for its 60,000 BTU/h model. Each value is placed at its own temperature, with its source; nothing is calculated between two points.

The GREE table (Extended Ratings, August 27, 2024) gives total capacity with 21.1 °C indoors; it does not say whether this is maximum output. At −15 °C it gives 45,000 BTU/h, and the certificate 54,000 BTU/h maximum: the page shows both.

Features

Controls, backup heat, compressor: the 5-ton sheets

Only what the submittal sheets of the two 60,000 BTU/h systems say. A feature missing from a document is not necessarily missing from the unit.

Thermostat and control

MIDEA: 120N (X6W) wired controller with built-in Wi-Fi, wireless remote, or a third-party 24 V thermostat.

GREE: compatible with a 24 V AC thermostat.

Submittals MAUSE-H60B-2A / MO1HE-H60B-2A and GREE_FXU60_230V_R32_SUB_05162025
Electric backup heat

MIDEA: optional heat kit, up to 25 kW.

GREE: optional 6, 9 or 12 kW kits (FLEXA2LHTR06, 09 and 12).

Same sheets
Heated base pan

MIDEA: base pan heater standard; NEEP lists 150 W.

GREE: base pan with heating element; NEEP lists 160 W.

Submittal sheets · NEEP records 387394 and 392093
Compressor

MIDEA: twin rotary ETPQ480D66UMU1, standard crankcase heater.

GREE: GREE G20 twin-cylinder, two-stage inverter, with heating element.

Same sheets
Indoor fan airflow

MIDEA: 5 speeds, from 1,236 to 1,801 cfm; static pressure 0 to 0.8 in. w.c.

GREE: 5 speeds; 1,500 cfm up to 1.0 in. w.c.

Same sheets
Installation positions

MIDEA: multi-position air handler (horizontal left or right, vertical up or down).

GREE: not stated in the 5-ton submittal sheet.

Same sheets
Sound

The sound of a 5-ton system, from low speed to turbo

The 5-ton MIDEA air handler is published from 37 dB(A) at low speed up to 60 dB(A) on turbo; GREE gives a single value for its own, 53 dB(A). Outdoors, the two units are published at 64.5 and 63 dB(A). Neither sheet gives the measuring distance.

dB(A)

How to read these numbers. dB(A) measures a noise level as the ear perceives it: the lower the number, the quieter the unit. Each dot is a published value.

Why this is not a ranking. Neither manufacturer states its measuring conditions; different method, not comparable to the decibel.

Air handler, inside the house

Published values

Outdoor unit

Published values

On the MIDEA, 23 dB(A) separate the lowest speed from turbo: at this size, where the air handler goes matters as much as the published figure. Each manufacturer measures its own way; these values are reference points, not a ranking.

Installation

Piping, size and weight, at 5 tons

Outdoor units, to the same scale

Outdoor unit MIDEA MO1HE-H60B-2A
MO1HE-H60B-2A37 1/2 × 52 1/2 in · 243 lb
Outdoor unit GREE FXU60HP230V1R32AO
FXU60HP230V1R32AO35 7/16 × 49 5/8 in · 241.4 lb

Submittal-sheet photos, height to scale: 52 1/2 in for the MO1HE-H60B-2A, 49 5/8 in for the FXU60.

Air handlers, to the same scale

Air handler MIDEA MAUSE, series image
MAUSE-H60B-2A21 1/2 × 60 1/8 in · 188 lb
Air handler GREE FLEXX ULTRA, series image
FXU60HP230V1R32AH24 13/16 × 52 in · 199.5 lb

Series images of the air handlers, height to scale: 60 1/8 in for the MAUSE-H60B-2A, 52 in for the FXU60HP230V1R32AH.

How long the refrigerant line can run at 5 tons

40 ft
covered by the factory chargerefrigerant addedoutside the published limits
InstallationEVOX G3 · 5 tonsFLEXX ULTRA R32 · 5 tons
Maximum piping lengthNot stated on the 5-ton submittal sheet98 ftminimum 10 ft
Pre-charged length25 ft (7.5 m)0.7 oz per ft beyond31 ft0.215 oz per ft beyond
Maximum height difference98 ft (30 m)49 ft
Liquid – gas diameters3/8 – 3/4 in, flare connections3/8 – 3/4 in, flare connections
Refrigerant, factory chargeR-454B, 183 oz (5.2 kg)R-32, 162.3 oz
Outdoor unit W × H × D, weight37 1/2 × 52 1/2 × 16 3/8 in, 243 lb35 7/16 × 49 5/8 × 13 3/8 in, 241.4 lb
Indoor unit W × H × D, weight21 1/2 × 60 1/8 × 21 1/2 in, 188 lb24 13/16 × 52 × 21 1/4 in, 199.5 lb
Electrical protectionOutdoor: MCA 40 A, MOP 40 A; indoor: MCA 10 A, MOP 15 A208/230 VOutdoor: MCA 40 A, MOCP 45 A; indoor: MCA 7.7 A, MOCP 15 A208-230 V
Indoor fan airflow5 speeds: 1,801, 1,648, 1,501, 1,236 and 1,236 cfm5 speeds; 1,500 cfm up to 1.0 in. w.c.
Published heating / cooling range−30 to 24 °C / −30 to 50 °C−30 to 24 °C / −15 to 54 °C

Sources: MIDEA submittal sheet MAUSE-H60B-2A / MO1HE-H60B-2A (undated); GREE submittal sheet GREE_FXU60_230V_R32_SUB_05162025. GREE cooling range: 5 to 129 °F per the sheet.

Questions

What people ask us about these two 5-ton systems

Will my electrical service be enough?

For the outdoor unit, the sheets require a circuit with a minimum circuit ampacity (MCA) of 40 A and maximum protection of 40 A (MIDEA) or 45 A (GREE); the air handler has its own circuit of 15 A maximum. An electric backup heat kit adds its own load. Calculating the home's electrical service is a job for a master electrician.

Can my existing ducts keep up?

MIDEA publishes 1,236 to 1,801 cfm depending on speed, with an external static pressure of 0 to 0.8 in. w.c.; GREE publishes 1,500 cfm up to 1.0 in. w.c. Ducts designed for a smaller furnace can limit that airflow; an estimator measures the static pressure on site.

Why is the cost calculated on 60,000 BTU/h?

The certificates give 54,000 BTU/h for the EVOX G3 and 53,000 BTU/h for the FLEXX ULTRA in cooling at 35 °C. To compare the two under the same conditions, the estimate uses the common nominal size, 5 tons, and changes only the HSPF2 and SEER2 of each certificate.

And at −30 °C?

Both certificates give a maximum output at −30 °C: 37,300 BTU/h for the EVOX G3 and 27,000 BTU/h for the FLEXX ULTRA. Both manufacturers publish a heating range down to −30 °C.

GREE's sheet and certificate differ. Which one to follow?

The GREE submittal sheet states a SEER2 of 18.5, an EER2 of 11.7 and an HSPF2 of 10.5; AHRI certificate 215213332 gives 18.2, 11.2 and 10.5. The page follows the certificate.

Do they use the same refrigerant?

No: R-454B for the EVOX G3 (GWP 466, IPCC AR4) and R-32 for the FLEXX ULTRA (GWP 675, IPCC AR4), both class A2L under ASHRAE 34.

Certified sheet

The certificate values, side by side

Certified valueEVOX G3 · 5 tonsFLEXX ULTRA R32 · 5 tons
Certificate
AHRI certificate · NEEP record215471345 · 387394MAUSE-H60B-2A + MO1HE-H60B-2A215213332 · 392093FXU60HP230V1R32AH + FXU60HP230V1R32AO
ENERGY STAR (NEEP record)Yes, cold-climate criterion includedYes, cold-climate criterion included
RefrigerantR-454B · GWP 466 (IPCC AR4) · class A2LR-32 · GWP 675 (IPCC AR4) · class A2L
Seasonal efficiency
SEER217.518.2
EER21211.2
HSPF2 Region IV9.510.5
HSPF2 Region V7.77.8
Certified heating, BTU/h
Min. / rated / max. capacity at 8.3 °C8,600 / 55,000 / 60,00016,000 / 54,000 / 54,400
Min. / rated / max. capacity at −8.3 °C16,500 / 45,000 / 54,00010,000 / 45,000 / 47,300
Min. / rated / max. capacity at −15 °C15,400 / 54,000 / 54,00019,400 / 54,000 / 54,000
COP at 8.3 °C (lowest, rated, highest output)3.23 / 3.36 / 3.094.34 / 3.40 / 3.33
COP at −15 °C (lowest, rated, highest output)2.15 / 1.90 / 1.902.20 / 2.10 / 2.10
Coldest certified point
Test temperature−30 °C (−22 °F)−30 °C (−22 °F)
Capacity at the coldest point (lowest / highest)11,600 / 37,300 BTU/h18,600 / 27,000 BTU/h
COP at the coldest point (lowest / highest output)1.53 / 1.691.27 / 1.27
Cooling
Rated capacity at 35 °C54,000 BTU/hmin. 11,400, max. 60,00053,000 BTU/hmin. 15,000, max. 53,000

“higher” marks the higher value of the same measure, under the same conditions. It is not a recommendation. At the coldest point, both are measured at −30 °C: the values compare directly, but this group is not highlighted.

Both are on the AirGreen website.

To choose for your home, talk it over with our team: bring the heated area, the condition of the ducts, the capacity of your electrical panel and your current heating.

Sources

Documents reviewed

NEEP, record 387394 (EVOX G3, 5 tons)AHRI 215471345 · reviewed November 10, 2026
NEEP, record 392093 (FLEXX ULTRA R32, 5 tons)AHRI 215213332 · reviewed November 10, 2026
MIDEA, submittal sheet MAUSE-H60B-2A / MO1HE-H60B-2AExtreme Heat AHU series, undated · reviewed November 10, 2026
GREE, submittal sheet FXU60 (R32)GREE_FXU60_230V_R32_SUB_05162025 · copy hosted by a distributor · reviewed November 10, 2026
GREE, FLEXX ULTRA R32 Extended RatingsCAT NO GREE_FLEXX_ULTRA_EXTENDED RATINGS_08272024 · heating, FXU60, 21.1 °C indoors · reviewed November 10, 2026
Hydro-Québec, Electricity RatesApril 1, 2026, Rate D, sec. 2.5 · these rates may change
NRCan, HOT2000 climate mapMontréal Intl: 4,167 degree-days (base 18 °C), design temperature −23.1 °C