FANTECH FIT 120E and LIFEBREATH METRO 120 ERVD, ERV air exchangers

Home / Comparisons / Air exchangers

Comparison · ERV air exchanger · 123 to 127 CFM at 0.4 in. w.c.

FANTECH FIT 120E and LIFEBREATH METRO 120 ERVD: two compact ERVs, measure by measure

Two energy recovery ventilators (ERVs) built for condos and apartments, where the unit goes in a closet or above a ceiling. Both are listed in the HVI directory: at 0.4 in. w.c., 127 CFM for the FIT 120E and 123 CFM for the METRO 120 ERVD. Their energy tests are not run at the same airflows; the page shows them side by side and says each time what compares directly.

At 0.4 in. w.c.: 127 and 123 CFM (HVI) Thickness: 10 in. and 9 3/4 in. (sheets) Mounting: ceiling or wall · ceiling Drain: none for either
FANTECH FIT 120E (AirGreen image)
FANTECH

FIT 120E

ERV, side ports · product 463401 · HVI 2005016

Sheet 445731 (rev. 2023-07-20) · manual 445657 (rev. 2023-07-17) · same HVI values under GREENTEK PROFILE 1.2E (2005261)

See the product page
LIFEBREATH METRO 120 ERVD (AirGreen image)
LIFEBREATH

METRO 120 ERVD

ERV with recirculation defrost, ports at both ends · HVI 2005105

Sheet METRO 120 ERVD - 0924 · manual 69-METRO IOM 0826

See the product page
Estimated running cost

FIT 120E or METRO 120 ERVD: the cost of the watts over a year

An air exchanger does not heat or cool: what it uses is the power of its two fans. The HVI directory publishes the watts at each 0 °C test point. These two units are not tested at the same airflows: pick each one's low, middle or high test point. The airflow of each test is written next to the amount.

HVI test point, at 0 °C
Price per kWh (Rate D, April 1, 2026)
How this amount is calculated
  1. Power: the watts in the HVI directory at each 0 °C test point. Low point: 55 W at 51 CFM (FIT 120E) and 63 W at 49 CFM (METRO 120 ERVD). Middle point: 63 W at 68 CFM and 68 W at 64 CFM. High point: 104 W at 131 CFM and 101 W at 95 CFM.
  2. Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
  3. Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.

At none of the three points do the two units move exactly the same airflow: the dollar gap therefore mixes fan consumption with the amount of air moved. AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the home, the settings and the use; this amount is not a promise.

In the closet

On the ceiling, on the wall or in a dropped ceiling: the room each one needs

In a condo, the question often comes down to a few inches: the cabinet's thickness, and the space to keep clear in front of the service door to slide out the core and filters. Pick where the unit goes, then move the slider. Both diagrams are at the same scale, based on the dimensions and clearances each manufacturer publishes.

Photo of the FANTECH FIT 120E
Photo, in perspective: not to scale
Photo of the LIFEBREATH METRO 120 ERVD
Photo, in perspective: not to scale
FIT 120E ports (sheet 445731): four 5 in. round collars, two on each side. Standard version: left side to the outdoors, right side to the house; the mirrored FIT 120E-M swaps them.
  • fresh air, from outside
  • stale air, to outside
  • stale air, from the house
  • fresh air, to the house
METRO 120 ERVD ports (sheet 0924): four 5 in. (125 mm) round collars, two at each end. Standard version: one end to the outdoors, the other to the house; Lifebreath offers a mirrored version, METRO-120ERVD-M.
  • fresh air, from outside
  • stale air, to outside
  • stale air, from the house
  • fresh air, to the house

Diagram to scale (1 in. = the same length for both). The METRO 120 ERVD collars are drawn short: the sheet gives the cabinet length (25 3/4 in.), not the collars'. The sheet photos, taken in perspective, are not to scale.

The HVI numbers

What each one recovers at 0 °C, at −25 °C and in summer

An ERV recovers heat and moisture: in winter it keeps some in the house; in summer it keeps some outside. The HVI directory publishes each unit's effectiveness at test airflows chosen by the manufacturer. Here those airflows are close, not identical: the numbers read side by side, with neither marked as higher.

SRE: sensible recovery efficiency; adjusted SRE: the same, corrected for fan heat per the HVI method. TRE: total recovery efficiency, heat and moisture, in cooling. Net moisture transfer: share of moisture moved from one airstream to the other. Source: HVI directory, section III, data as of November 4, 2026.

Airflow and pressure

The more the ducts resist, the less air gets through: the two cross at 0.5 in. w.c.

Net fresh airflow drops as the static pressure in the ducts rises. Up to 0.4 in. w.c., the FIT 120E moves more; at 0.5 in., both are at 117 CFM; above that, the METRO 120 ERVD does. The directory lists the METRO 120 ERVD up to 1.4 in. and the FIT 120E up to 1.0 in. The actual pressure depends on each installation's ducts, grilles and hoods.

FANTECH FIT 120E HVI 2005016LIFEBREATH METRO 120 ERVD HVI 2005105
Construction

Core, motors, defrost: the FIT 120E and the METRO 120 ERVD, part by part

Two different builds: a cabinet that mounts upright or flat, with a defrost that shuts off the fresh air, on one side; a flat cabinet with a damper that recirculates house air, on the other. Each card says which document publishes it.

Recovery core

FIT 120E: polymer membrane that transfers heat and moisture, 12 × 12 in., 8.15 in. deep; freeze tolerant and water washable. METRO 120 ERVD: cross-flow core that transfers heat and water vapour, removable for cleaning.

sheet 445731sheet 0924
Defrost

FIT 120E: at −10 °C and below, the fresh-air fan stops and the exhaust fan goes to high speed, then the cycle repeats. METRO 120 ERVD: below −3 °C, a motorized damper closes the fresh air and stale air recirculates through the core; no ventilation during that time. 3 min of defrost for 25 min of ventilation at −3 °C, 4.5 for 17 at −20 °C, 7 for 15 at −35 °C.

sheet 445731manual 0826, p. 14
Filters

FIT 120E: two washable electrostatic filters, 11.3 × 8.15 × 0.125 in. METRO 120 ERVD: washable MERV 6 filters on the exhaust and supply airstreams; MERV 13 optional (65-195-6R).

sheet 445731sheet 0924
Fans and motors

FIT 120E: two backward-curved fans, factory balanced, sealed ball bearings; several speeds. METRO 120 ERVD: one centrifugal fan per airstream, PSC motor, several speeds; high speed factory-set at Hi3, adjustable by DIP switches.

sheet 445731sheet 0924, manual 0826
Controls

FIT 120E: ECO-Feel AUTO IAQ wall control recommended; ECO-Touch AUTO IAQ, EDF8, EDF3, RTS-W, RTS5, RTS2 and MDEH1 compatible. METRO 120 ERVD: wall-mounted main control; 5 speeds with the DXPL03, 2 with the BC02 or BC04, 1 with the BC03.

sheet 445731manual 0826
Mounting

FIT 120E: on the ceiling or the wall, with the bracket supplied; optional chain kit. METRO 120 ERVD: on the ceiling, with the brackets supplied; Lifebreath limits wall mounting to the METRO XTR, MAX XTR and MAX XTR PLUS.

manual 445657, pp. 11-12manual 0826, p. 25
Drain

No drain required for either, per both manufacturers. Lifebreath recommends an auxiliary pan if the unit sits above a water-sensitive area.

sheet 445731sheet 0924, manual 0826
Cabinet

FIT 120E: G90 galvanized steel. METRO 120 ERVD: 22-gauge prepainted galvanized steel, insulated against exterior condensation; hinged door, no screws.

sell sheet E1625sheet 0924
Installation

Installing a FIT 120E or a METRO 120 ERVD: what Fantech and Lifebreath ask for

ItemFANTECH FIT 120ELIFEBREATH METRO 120 ERVD
Cabinet dimensionssheets 445731 and 092420 7/8 × 20 3/4 in., 10 in. thick; 24 5/8 in. with the collars25 3/4 × 19 3/8 in. (654 × 492 mm), 9 3/4 in. (248 mm) thick
Weight34 lb (15 kg), including core37 lb (16.8 kg)
Ports4 round 5 in. (125 mm) collars, rubber seal, on the sides4 round 5 in. (125 mm) collars, at both ends
MountingCeiling or wall, bracket suppliedCeiling, brackets supplied
Service clearance8.5 in. (216 mm) in front of the unit, to slide out the core25 in. (635 mm) in front of the unit, for servicing
LocationAbove a dropped ceiling, for instance, where mechanical space is shortHeated space; closet, above a water heater or a stacked washer-dryer, 10 in. dropped ceiling with access panel; attic not recommended
Power supply120 V; 120 W rated, 1.0 A running, 1.4 A CSA rating; 3 ft cord with plug120 V; 1.4 A, MCA 2.0 A, MOP 15 A; plugged into an outlet, extension cord not recommended
DrainNo drain requiredNo drain required
DefrostAt −10 °C and below: fresh air off, exhaust at high speedBelow −3 °C: motorized damper, house air recirculated

Values declared by the manufacturers unless stated otherwise. The FIT 120E dimensions are read from the drawing in sheet 445731: D (cabinet), B (cabinet), E (thickness) and C (with collars).

Questions

Your questions about the FIT 120E and the METRO 120 ERVD

Why are the test points not the same?

The HVI directory publishes the points each manufacturer has certified. Fantech had the FIT 120E tested at 51, 68 and 131 CFM at 0 °C; Lifebreath, the METRO 120 ERVD at 49, 64 and 95 CFM. The airflows are close, not identical; HVI asks that only values taken under the same conditions be compared. That is why no recovery row is marked “higher” on this page.

Which one can go on a closet wall?

The FIT 120E manual describes ceiling mounting and wall mounting, with the same bracket (manual 445657, pp. 11 and 12). Lifebreath's METRO manual states that only the METRO XTR, MAX XTR and MAX XTR PLUS can go on a wall; the METRO 120 ERVD mounts on the ceiling (69-METRO IOM 0826, p. 25).

Is a drain needed?

No, per both manufacturers. Lifebreath does recommend an auxiliary pan when the unit is installed above a water-sensitive area, and asks that the unit be kept from freezing.

What happens in extreme cold?

Both have an HVI test at −25 °C: 61% SRE at 51 CFM for the FIT 120E, 57% at 57 CFM for the METRO 120 ERVD. Their defrost differs: the FIT 120E shuts off the fresh air and pushes the exhaust at −10 °C and below; the METRO 120 ERVD closes the fresh air with a damper and recirculates house air below −3 °C, with longer cycles when it is colder.

Are there mirrored versions?

Yes. The FIT 120E-M swaps the side of the ports; AirGreen offers it on its website. Lifebreath publishes a mirrored METRO 120 ERVD under the code METRO-120ERVD-M. The choice depends on which side the ducts come from in the apartment's layout.

Why doesn't the page compare noise?

Neither the FIT 120E sheet nor the METRO 120 ERVD sheet publishes a sound level. Without a measurement published by both manufacturers, there is nothing to compare fairly.

What airflow does my home need?

The required ventilation rate is calculated under the applicable code and the number of rooms, then the installation is set and balanced on site. This page does not do that calculation: it shows what each unit delivers at each static pressure, per the HVI directory.

All the values

The FIT 120E and the METRO 120 ERVD in the HVI directory, line by line

HVI directory, section III, data as of November 4, 2026. Airflows at the same static pressure compare directly; the energy test points, run at different airflows, read side by side.

MeasurementFANTECH FIT 120ELIFEBREATH METRO 120 ERVD
Net supply airflow, same static pressure
Airflow at 0.1 in. w.c. (25 Pa)155 CFM136 CFM
Airflow at 0.2 in. w.c. (50 Pa)146 CFM131 CFM
Airflow at 0.3 in. w.c. (75 Pa)136 CFM127 CFM
Airflow at 0.4 in. w.c. (100 Pa)127 CFM123 CFM
Airflow at 0.5 in. w.c. (125 Pa)117 CFM117 CFM
Airflow at 0.6 in. w.c. (150 Pa)106 CFM112 CFM
Airflow at 0.7 in. w.c. (175 Pa)95 CFM106 CFM
Airflow at 0.8 in. w.c. (200 Pa)83 CFM100 CFM
Airflow at 0.9 in. w.c. (225 Pa)72 CFM93 CFM
Airflow at 1.0 in. w.c. (250 Pa)59 CFM85 CFM
Airflow at 1.2 in. w.c. (300 Pa)The directory stops at 1.0 in. w.c. for this unit (59 CFM)66 CFM
Airflow at 1.4 in. w.c. (350 Pa)The directory stops at 1.0 in. w.c. for this unit (59 CFM)42 CFM
Heating, 0 °C: each test point
Sensible recovery (SRE), low point74% at 51 CFM (24 L/s), 55 W; adjusted 81%; moisture 0.7672% at 49 CFM (23 L/s), 63 W; adjusted 81%; moisture 0.65
Sensible recovery (SRE), middle point69% at 68 CFM (32 L/s), 63 W; adjusted 75%; moisture 0.7171% at 64 CFM (30 L/s), 68 W; adjusted 78%; moisture 0.60
Sensible recovery (SRE), high point64% at 131 CFM (62 L/s), 104 W; adjusted 69%; moisture 0.6066% at 95 CFM (45 L/s), 101 W; adjusted 73%; moisture 0.50
Extreme cold, −25 °C (72-hour test)
Sensible recovery (SRE) at −25 °C61% at 51 CFM (24 L/s), 55 W; adjusted 63%; moisture 0.5457% at 57 CFM (27 L/s), 89 W; adjusted 62%; moisture 0.47
Ventilation reduction at the end of the test (supply / exhaust)12.8% / 0.0%21.5% / 18.6%
Cooling, 35 °C
Total recovery (TRE), low point64% at 51 CFM, 55 W; adjusted 68%; moisture 0.6844% at 49 CFM, 60 W; adjusted 49%; moisture 0.40
Total recovery (TRE), next pointOnly one cooling point listed for this unit (51 CFM, above)41% at 64 CFM, 66 W; adjusted 45%; moisture 0.35
Listing
HVI directory, section IIIHVID 2005016 · Systemair Inc.HVID 2005105 · Airia Brands Inc.
ENERGY STARNot listed for this version, per the AirGreen product page; Fantech reserves the mention for the -EC versionsNot listed, per the AirGreen product page

“higher” marks the higher value of the same measure, under the same conditions. It is not a recommendation.

The FIT 120E and the METRO 120 ERVD are both on the AirGreen website.

The right choice depends on the required ventilation rate, the resistance of the ducts, and the room the closet or ceiling offers. Talk it over with our team.

Sources and documents

The documents behind every number on this page

HVI, Certified Products Directory, section IIIPublication 911, data as of November 4, 2026 · listings 2005016, 2005105 and 2005261 · consulted November 10, 2026
FANTECH FIT 120E specification sheetItem 445731, rev. 2023-07-20, product 463401 · dimensions, weight, electrical, defrost, clearance · consulted November 10, 2026
FANTECH FIT 120E Series manualItem 445657, rev. 2023-07-17 · ceiling and wall mounting (pp. 11-12), maintenance (p. 21) · consulted November 10, 2026
FANTECH FIT Series sell sheetE1625 · G90 galvanized housing · consulted November 10, 2026
LIFEBREATH METRO 120 ERVD specification sheet“METRO 120 ERVD - 0924”, lifebreath.com · dimensions, weight, electrical, clearance, ports · consulted November 10, 2026
LIFEBREATH METRO manual69-METRO IOM 0826 · defrost (p. 14), location (p. 24), mounting (p. 25) · consulted November 10, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · fan running cost · consulted November 10, 2026