Home / Comparisons / Air exchangers
FANTECH FIT 120E and LIFEBREATH METRO 120 ERVD: two compact ERVs, measure by measure
Two energy recovery ventilators (ERVs) built for condos and apartments, where the unit goes in a closet or above a ceiling. Both are listed in the HVI directory: at 0.4 in. w.c., 127 CFM for the FIT 120E and 123 CFM for the METRO 120 ERVD. Their energy tests are not run at the same airflows; the page shows them side by side and says each time what compares directly.
Under the ceiling, to scale
Diagram, 1 in. = the same length for both · FIT 120E METRO 120 ERVD
FIT 120E
ERV, side ports · product 463401 · HVI 2005016
Sheet 445731 (rev. 2023-07-20) · manual 445657 (rev. 2023-07-17) · same HVI values under GREENTEK PROFILE 1.2E (2005261)
See the product page
METRO 120 ERVD
ERV with recirculation defrost, ports at both ends · HVI 2005105
Sheet METRO 120 ERVD - 0924 · manual 69-METRO IOM 0826
See the product pageFIT 120E or METRO 120 ERVD: the cost of the watts over a year
An air exchanger does not heat or cool: what it uses is the power of its two fans. The HVI directory publishes the watts at each 0 °C test point. These two units are not tested at the same airflows: pick each one's low, middle or high test point. The airflow of each test is written next to the amount.
How this amount is calculated
- Power: the watts in the HVI directory at each 0 °C test point. Low point: 55 W at 51 CFM (FIT 120E) and 63 W at 49 CFM (METRO 120 ERVD). Middle point: 63 W at 68 CFM and 68 W at 64 CFM. High point: 104 W at 131 CFM and 101 W at 95 CFM.
- Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
- Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.
At none of the three points do the two units move exactly the same airflow: the dollar gap therefore mixes fan consumption with the amount of air moved. AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the home, the settings and the use; this amount is not a promise.
On the ceiling, on the wall or in a dropped ceiling: the room each one needs
In a condo, the question often comes down to a few inches: the cabinet's thickness, and the space to keep clear in front of the service door to slide out the core and filters. Pick where the unit goes, then move the slider. Both diagrams are at the same scale, based on the dimensions and clearances each manufacturer publishes.


- fresh air, from outside
- stale air, to outside
- stale air, from the house
- fresh air, to the house
- fresh air, from outside
- stale air, to outside
- stale air, from the house
- fresh air, to the house
Diagram to scale (1 in. = the same length for both). The METRO 120 ERVD collars are drawn short: the sheet gives the cabinet length (25 3/4 in.), not the collars'. The sheet photos, taken in perspective, are not to scale.
What each one recovers at 0 °C, at −25 °C and in summer
An ERV recovers heat and moisture: in winter it keeps some in the house; in summer it keeps some outside. The HVI directory publishes each unit's effectiveness at test airflows chosen by the manufacturer. Here those airflows are close, not identical: the numbers read side by side, with neither marked as higher.
SRE: sensible recovery efficiency; adjusted SRE: the same, corrected for fan heat per the HVI method. TRE: total recovery efficiency, heat and moisture, in cooling. Net moisture transfer: share of moisture moved from one airstream to the other. Source: HVI directory, section III, data as of November 4, 2026.
The more the ducts resist, the less air gets through: the two cross at 0.5 in. w.c.
Net fresh airflow drops as the static pressure in the ducts rises. Up to 0.4 in. w.c., the FIT 120E moves more; at 0.5 in., both are at 117 CFM; above that, the METRO 120 ERVD does. The directory lists the METRO 120 ERVD up to 1.4 in. and the FIT 120E up to 1.0 in. The actual pressure depends on each installation's ducts, grilles and hoods.
Core, motors, defrost: the FIT 120E and the METRO 120 ERVD, part by part
Two different builds: a cabinet that mounts upright or flat, with a defrost that shuts off the fresh air, on one side; a flat cabinet with a damper that recirculates house air, on the other. Each card says which document publishes it.
FIT 120E: polymer membrane that transfers heat and moisture, 12 × 12 in., 8.15 in. deep; freeze tolerant and water washable. METRO 120 ERVD: cross-flow core that transfers heat and water vapour, removable for cleaning.
FIT 120E: at −10 °C and below, the fresh-air fan stops and the exhaust fan goes to high speed, then the cycle repeats. METRO 120 ERVD: below −3 °C, a motorized damper closes the fresh air and stale air recirculates through the core; no ventilation during that time. 3 min of defrost for 25 min of ventilation at −3 °C, 4.5 for 17 at −20 °C, 7 for 15 at −35 °C.
FIT 120E: two washable electrostatic filters, 11.3 × 8.15 × 0.125 in. METRO 120 ERVD: washable MERV 6 filters on the exhaust and supply airstreams; MERV 13 optional (65-195-6R).
FIT 120E: two backward-curved fans, factory balanced, sealed ball bearings; several speeds. METRO 120 ERVD: one centrifugal fan per airstream, PSC motor, several speeds; high speed factory-set at Hi3, adjustable by DIP switches.
FIT 120E: ECO-Feel AUTO IAQ wall control recommended; ECO-Touch AUTO IAQ, EDF8, EDF3, RTS-W, RTS5, RTS2 and MDEH1 compatible. METRO 120 ERVD: wall-mounted main control; 5 speeds with the DXPL03, 2 with the BC02 or BC04, 1 with the BC03.
FIT 120E: on the ceiling or the wall, with the bracket supplied; optional chain kit. METRO 120 ERVD: on the ceiling, with the brackets supplied; Lifebreath limits wall mounting to the METRO XTR, MAX XTR and MAX XTR PLUS.
No drain required for either, per both manufacturers. Lifebreath recommends an auxiliary pan if the unit sits above a water-sensitive area.
FIT 120E: G90 galvanized steel. METRO 120 ERVD: 22-gauge prepainted galvanized steel, insulated against exterior condensation; hinged door, no screws.
Installing a FIT 120E or a METRO 120 ERVD: what Fantech and Lifebreath ask for
| Item | FANTECH FIT 120E | LIFEBREATH METRO 120 ERVD |
|---|---|---|
| Cabinet dimensionssheets 445731 and 0924 | 20 7/8 × 20 3/4 in., 10 in. thick; 24 5/8 in. with the collars | 25 3/4 × 19 3/8 in. (654 × 492 mm), 9 3/4 in. (248 mm) thick |
| Weight | 34 lb (15 kg), including core | 37 lb (16.8 kg) |
| Ports | 4 round 5 in. (125 mm) collars, rubber seal, on the sides | 4 round 5 in. (125 mm) collars, at both ends |
| Mounting | Ceiling or wall, bracket supplied | Ceiling, brackets supplied |
| Service clearance | 8.5 in. (216 mm) in front of the unit, to slide out the core | 25 in. (635 mm) in front of the unit, for servicing |
| Location | Above a dropped ceiling, for instance, where mechanical space is short | Heated space; closet, above a water heater or a stacked washer-dryer, 10 in. dropped ceiling with access panel; attic not recommended |
| Power supply | 120 V; 120 W rated, 1.0 A running, 1.4 A CSA rating; 3 ft cord with plug | 120 V; 1.4 A, MCA 2.0 A, MOP 15 A; plugged into an outlet, extension cord not recommended |
| Drain | No drain required | No drain required |
| Defrost | At −10 °C and below: fresh air off, exhaust at high speed | Below −3 °C: motorized damper, house air recirculated |
Values declared by the manufacturers unless stated otherwise. The FIT 120E dimensions are read from the drawing in sheet 445731: D (cabinet), B (cabinet), E (thickness) and C (with collars).
Your questions about the FIT 120E and the METRO 120 ERVD
Why are the test points not the same?
The HVI directory publishes the points each manufacturer has certified. Fantech had the FIT 120E tested at 51, 68 and 131 CFM at 0 °C; Lifebreath, the METRO 120 ERVD at 49, 64 and 95 CFM. The airflows are close, not identical; HVI asks that only values taken under the same conditions be compared. That is why no recovery row is marked “higher” on this page.
Which one can go on a closet wall?
The FIT 120E manual describes ceiling mounting and wall mounting, with the same bracket (manual 445657, pp. 11 and 12). Lifebreath's METRO manual states that only the METRO XTR, MAX XTR and MAX XTR PLUS can go on a wall; the METRO 120 ERVD mounts on the ceiling (69-METRO IOM 0826, p. 25).
Is a drain needed?
No, per both manufacturers. Lifebreath does recommend an auxiliary pan when the unit is installed above a water-sensitive area, and asks that the unit be kept from freezing.
What happens in extreme cold?
Both have an HVI test at −25 °C: 61% SRE at 51 CFM for the FIT 120E, 57% at 57 CFM for the METRO 120 ERVD. Their defrost differs: the FIT 120E shuts off the fresh air and pushes the exhaust at −10 °C and below; the METRO 120 ERVD closes the fresh air with a damper and recirculates house air below −3 °C, with longer cycles when it is colder.
Are there mirrored versions?
Yes. The FIT 120E-M swaps the side of the ports; AirGreen offers it on its website. Lifebreath publishes a mirrored METRO 120 ERVD under the code METRO-120ERVD-M. The choice depends on which side the ducts come from in the apartment's layout.
Why doesn't the page compare noise?
Neither the FIT 120E sheet nor the METRO 120 ERVD sheet publishes a sound level. Without a measurement published by both manufacturers, there is nothing to compare fairly.
What airflow does my home need?
The required ventilation rate is calculated under the applicable code and the number of rooms, then the installation is set and balanced on site. This page does not do that calculation: it shows what each unit delivers at each static pressure, per the HVI directory.
The FIT 120E and the METRO 120 ERVD in the HVI directory, line by line
HVI directory, section III, data as of November 4, 2026. Airflows at the same static pressure compare directly; the energy test points, run at different airflows, read side by side.
| Measurement | FANTECH FIT 120E | LIFEBREATH METRO 120 ERVD |
|---|---|---|
| Net supply airflow, same static pressure | ||
| Airflow at 0.1 in. w.c. (25 Pa) | 155 CFM | 136 CFM |
| Airflow at 0.2 in. w.c. (50 Pa) | 146 CFM | 131 CFM |
| Airflow at 0.3 in. w.c. (75 Pa) | 136 CFM | 127 CFM |
| Airflow at 0.4 in. w.c. (100 Pa) | 127 CFM | 123 CFM |
| Airflow at 0.5 in. w.c. (125 Pa) | 117 CFM | 117 CFM |
| Airflow at 0.6 in. w.c. (150 Pa) | 106 CFM | 112 CFM |
| Airflow at 0.7 in. w.c. (175 Pa) | 95 CFM | 106 CFM |
| Airflow at 0.8 in. w.c. (200 Pa) | 83 CFM | 100 CFM |
| Airflow at 0.9 in. w.c. (225 Pa) | 72 CFM | 93 CFM |
| Airflow at 1.0 in. w.c. (250 Pa) | 59 CFM | 85 CFM |
| Airflow at 1.2 in. w.c. (300 Pa) | The directory stops at 1.0 in. w.c. for this unit (59 CFM) | 66 CFM |
| Airflow at 1.4 in. w.c. (350 Pa) | The directory stops at 1.0 in. w.c. for this unit (59 CFM) | 42 CFM |
| Heating, 0 °C: each test point | ||
| Sensible recovery (SRE), low point | 74% at 51 CFM (24 L/s), 55 W; adjusted 81%; moisture 0.76 | 72% at 49 CFM (23 L/s), 63 W; adjusted 81%; moisture 0.65 |
| Sensible recovery (SRE), middle point | 69% at 68 CFM (32 L/s), 63 W; adjusted 75%; moisture 0.71 | 71% at 64 CFM (30 L/s), 68 W; adjusted 78%; moisture 0.60 |
| Sensible recovery (SRE), high point | 64% at 131 CFM (62 L/s), 104 W; adjusted 69%; moisture 0.60 | 66% at 95 CFM (45 L/s), 101 W; adjusted 73%; moisture 0.50 |
| Extreme cold, −25 °C (72-hour test) | ||
| Sensible recovery (SRE) at −25 °C | 61% at 51 CFM (24 L/s), 55 W; adjusted 63%; moisture 0.54 | 57% at 57 CFM (27 L/s), 89 W; adjusted 62%; moisture 0.47 |
| Ventilation reduction at the end of the test (supply / exhaust) | 12.8% / 0.0% | 21.5% / 18.6% |
| Cooling, 35 °C | ||
| Total recovery (TRE), low point | 64% at 51 CFM, 55 W; adjusted 68%; moisture 0.68 | 44% at 49 CFM, 60 W; adjusted 49%; moisture 0.40 |
| Total recovery (TRE), next point | Only one cooling point listed for this unit (51 CFM, above) | 41% at 64 CFM, 66 W; adjusted 45%; moisture 0.35 |
| Listing | ||
| HVI directory, section III | HVID 2005016 · Systemair Inc. | HVID 2005105 · Airia Brands Inc. |
| ENERGY STAR | Not listed for this version, per the AirGreen product page; Fantech reserves the mention for the -EC versions | Not listed, per the AirGreen product page |
“higher” marks the higher value of the same measure, under the same conditions. It is not a recommendation.
The FIT 120E and the METRO 120 ERVD are both on the AirGreen website.
The right choice depends on the required ventilation rate, the resistance of the ducts, and the room the closet or ceiling offers. Talk it over with our team.
The documents behind every number on this page
Data verified on November 10, 2026. Airflow, heat and moisture recovery, power: HVI directory. Dimensions, weight, construction, mounting and controls: per the manufacturer. When a manufacturer document contradicts the HVI directory, the directory prevails.
Trademarks. FANTECH, FIT, ECO-Feel, ECO-Touch, LIFEBREATH, METRO and GREENTEK are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer for both brands; this page is not produced, sponsored or approved by the manufacturers. Data colours: the blue of the LIFEBREATH logo; AirGreen teal for FANTECH, whose logo blue would be confused with LIFEBREATH's.