"Down to −22 °F": stated range and certified point

Comparison · Guide · Extreme cold

"Down to −22 °F": stated range and certified point

For the same heat pump, two figures circulate. The manufacturer states the outdoor temperature down to which it heats. The NEEP record certifies how much heat it delivers, and at what efficiency, at its coldest point. These are not the same questions.

4 12,000 BTU modelsRange: manufacturer documentsPoints: AHRI certificates, via NEEP
Stated range
How cold?

The lowest outdoor temperature at which the manufacturer says the unit heats.

Certified point
How much?

The heating capacity and COP measured at a given temperature, published on the NEEP record of the AHRI certificate.

FUJITSU AIRSTAGE ORION XLTH 12,000 BTUFUJITSU AIRSTAGEORION XLTHASUH12KZAS / AOUH12KZAH1 · AHRI 214888802See the product page
GREE EXTRÊME R32 12,000 BTUGREEEXTRÊME R32GWH12AVDXE-D6DN***/I / GWH12AVDXE-D6DNA1B/O · AHRI 215386290See the product page
SAMSUNG WindFree MaxHeat 12,000 BTUSAMSUNGWindFree MaxHeatAR12DXDABWKN / AR12DXDACWKX · AHRI 215399291See the product page
HITACHI airHome 800 12,000 BTUHITACHIairHome 800RAK-XJ12PHAA / RAC-XJ12WHAA · AHRI 215911631See the product page

Four models already shown on our comparison pages, used as examples. AirGreen offers all four; the page ranks none of them.

Stated, certified

Four thermometers, two kinds of figures

Left of the tube, the heating range stated by the manufacturer. On the tube, the published points: solid dots for NEEP certified points, diamonds for manufacturer values. Tap a point to see its source.

stated rangeNEEP certifiedper the manufacturer

NEEP values: maximum capacity published at each temperature, read November 10, 2026. The top of the ranges (75 to 86 °F) is beyond the scale and not drawn.

Two questions

The range says how cold, the point says how much

How cold: the stated range

It comes from the manufacturer's spec sheet or website. It states an operating limit without saying how much heat comes out at that limit. Three of the four examples state −22 °F; the fourth, −15 °F.

How much: the certified point

It comes from the NEEP record of the AHRI certificate: a maximum capacity and a COP, at a precise temperature. At the four coldest published points, maximum capacity ranges from 6,000 to 12,200 BTU/h, and the temperatures are not all the same.

Read this before drawing conclusions. For three examples, the stated limit and the coldest certified point fall at the same temperature, −22 °F. For the ORION XLTH, the sheet states −15 °F with no lockout, and the coldest NEEP point is at −15 °F (−26.1 °C). A value at −15 °F is not comparable with a value at −22 °F.
At the coldest point

What each record publishes at its own limit

One row per question, one column per model. The percentage is an AirGreen calculation: maximum capacity at the coldest point, divided by the same model's certified rated capacity at 47 °F.

Read each column on its own: the coldest points are not all at the same temperature, and no row is a ranking.

Where to read each figure

Three documents, three answers

1. The manufacturer's sheet

Look for "operating range", heating column. Note the temperature, the document date and any mention of an automatic shutdown.

2. The certificate's NEEP record

Open the heating values and go down to the coldest row: temperature, maximum capacity, COP.

3. The technical tables

Some manufacturers publish their own capacities below 5 °F. HITACHI gives 13,500, 10,500 and 6,000 BTU/h at −4, −13 and −22 °F for the 12,000 BTU airHome 800.

4. Compare only at the same temperature

Two values taken at different temperatures do not tell you which one heats more. Our NEEP record guide explains each column.

Frequently asked questions

What we get asked about "down to −22 °F"

If the range goes down to −22 °F, does the heat pump heat as much as at 5 °F?

Not necessarily. For the three examples certified at −22 °F, the maximum capacity published there is lower than at 5 °F: 8,500 vs 12,200 BTU/h (EXTRÊME R32), 6,800 vs 9,000 (WindFree MaxHeat), 6,000 vs 15,200 (airHome 800).

Why isn't the coldest point at the same temperature for all of them?

The NEEP record publishes a point colder than 5 °F whose temperature varies from model to model: −15 °F for the ORION XLTH, −22 °F for the other three examples. That is why the page does not set them side by side as a ranking.

What happens below the stated limit?

FUJITSU AIRSTAGE states there is no lockout on the ORION XLTH, without giving a capacity below −15 °F. The documents consulted for the other three do not say.

Do the HITACHI sheet and the NEEP record agree at −22 °F?

For the 12,000 BTU airHome 800, yes: 6,000 BTU/h in both. At −4 and −13 °F, only the manufacturer's sheet publishes a value; it is marked as such.

Which figure should I look at for a home in Montréal?

Both, because they answer different questions. The design temperature used in our estimates for Montréal is −23.1 °C (−9.6 °F) (NRCan, HOT2000). Our sizing guide explains how these figures feed into choosing a capacity.

A product listing title says "−30 °C". Where does that figure come from?

It repeats the lower limit of the heating range stated by the manufacturer, as for the airHome 800 and the WindFree MaxHeat. The heat available at that temperature is on the NEEP record.

A question about a model's limit?

AirGreen offers the four heat pumps used as examples on this page.