ENERGY STAR Cold Climate: what the designation says, and what it doesn't
Many people read "cold climate" as "heats down to −30 °C (−22 °F)". The ENERGY STAR specification in force checks something else: efficiency and capacity at a single temperature, 5 °F (−15 °C). Here are the criteria, where they are measured, and two real heat pumps taken through them one by one.
Cold Climate criteria of the ENERGY STAR v6.2 specification (rev. February 2026), pp. 4–5: COP and capacity measured at 5 °F, H4₂ test of Appendix M1.
FUJITSU AIRSTAGE ORION XLTH
ORION XLTH, 12,000 BTU
ASUH12KZAS / AOUH12KZAH1 · AHRI 214888802 Cold Climate designation: yes (ENERGY STAR directory) See the product page
SAMSUNG WindFree Standard
WindFree Standard, 12,000 BTU
AR12DXFAMWKN / AR12DXFAMWKX · AHRI 215399297 Cold Climate designation: no (ENERGY STAR directory) See the product pageTwo examples taken from the models AirGreen offers, to illustrate the criteria. Both are ENERGY STAR certified; the page makes no judgment on either.
Two levels: the label, then the Cold Climate designation
The ENERGY STAR v6.2 heat pump specification (revision of February 2, 2026) first sets thresholds for the label. A model can then receive the Cold Climate designation if it clears other thresholds, plus a test at 5 °F. For a ductless wall unit, here are both lists.
ENERGY STAR label, split system
Table 1, p. 4
Cold Climate designation, ductless split
Table 2 and low-ambient performance, pp. 4–5
Source: ENERGY STAR Program Requirements for Heat Pumps, Version 6.2 (rev. February 2026), Tables 1 and 2, p. 4; low-ambient performance and CVP, pp. 4–5; HSPF2 definition (Region IV), p. 2. Criteria can change: check the version in force.
Two real heat pumps, one criterion at a time
Each bar starts at zero and stops at the value published in the ENERGY STAR directory; the dark tick marks the threshold. Choose the list to check.
What each document says, degree by degree
The Cold Climate criteria stop at 5 °F. The NEEP records of the two examples go lower, each at its own temperature. Pick a point: you see what the criteria say, then the published value for each heat pump.
NEEP values: maximum capacity and matching COP, records 392122 and 389381, read November 10, 2026. Between two published points nothing is measured: the page shows the two values on either side, each with its own temperature.
Six things the designation does not promise
COP and capacity are checked at 5 °F. The specification has no criterion at −4, −13 or −22 °F.
No minimum temperature is set. Each manufacturer publishes its own: −15 °F with no lockout for the ORION XLTH, −5 °F for the WindFree Standard.
The HSPF2 threshold is defined in Region IV. HSPF2 Region V, closer to our winters, is not part of the criteria; our cost estimates use it.
It is a yes or a no. Two designated models can have very different capacities at 5 °F, and a model without it remains ENERGY STAR certified.
The criteria do not cover sound levels, defrost, snow or where the outdoor unit goes.
Version 6.2 was revised in February 2026. In the U.S., management of the program is moving from the EPA to the DOE in 2026; in Canada, NRCan administers it. Criteria can change.
The two examples, as the directory publishes them
| Value | FUJITSU AIRSTAGE ORION XLTH | SAMSUNG WindFree Standard |
|---|---|---|
| ENERGY STAR directory | ||
| ENERGY STAR Cold Climate designation | Yes | No |
| SEER2 | 30.5 | 24 |
| EER2 | 16 | 13.25 |
| HSPF2 (Region IV) | 12.7 | 9 |
| Heating capacity at 47 °F (8.3 °C) | 16,000 BTU/h | 12,000 BTU/h |
| Heating capacity at 5 °F (−15 °C) | 16,600 BTU/h | 8,000 BTU/h |
| Capacity at 5 °F, as a % of that at 47 °FAirGreen calculation from the two rows above | 104% | 67% |
| COP at 5 °F (−15 °C) | 2.16 | 1.76 |
| Controls verification (CVP) | ENERGY STAR CVP Test | ENERGY STAR CVP Test |
| Refrigerant | R-32 | R-32 |
| AHRI certificate · NEEP record | 214888802 · 392122 | 215399297 · 389381 |
| ENERGY STAR certification date | April 17, 2026 | January 7, 2026 |
| NEEP: coldest published point | ||
| Coldest published point | −15 °F (−26.1 °C): 12,200 BTU/h max., COP 1.81 | −5 °F (−20.6 °C): 10,000 BTU/h max., COP 1.81 |
higher marks the higher value of the same measure under the same conditions. It is not a recommendation. No row is marked here: the page illustrates criteria, it does not compare the two models.
What we get asked about the designation
Does "cold climate" mean the heat pump heats at −22 °F?
No. The criteria check COP and capacity at 5 °F, nothing colder. The temperature down to which a heat pump runs comes from the manufacturer, and colder certified points, when there are any, come from the model's NEEP record.
Why doesn't the WindFree Standard have the designation, with a COP of 1.76 at 5 °F?
COP is only one of the criteria. Using the values published in the directory, its capacity at 5 °F is 67% of the capacity at 47 °F, and the threshold is 70%. ENERGY STAR does not state a reason for a given model; this calculation is ours.
Is a heat pump without the designation less efficient?
The designation does not measure overall efficiency. Both examples carry the ENERGY STAR label, and the WindFree Standard clears the SEER2 and HSPF2 thresholds of the Cold Climate list. To compare efficiency, compare the same measures under the same conditions, on the certificates.
Where can I check a model's designation?
In the public ENERGY STAR directory, using the AHRI certificate number or the model numbers. The NEEP record of the same certificate also shows an "ENERGY STAR Cold Climate" field; for both examples it matched the directory on November 10, 2026.
Is the 8.5 HSPF2 threshold measured for Québec?
The specification defines HSPF2 in Region IV. NEEP records also publish HSPF2 Region V, a colder region; it is not part of the ENERGY STAR criteria. Our guide to Regions IV and V explains the difference.
Can the criteria change?
Yes. Version 6.2 was revised on February 2, 2026, and management of the program in the U.S. is moving from the EPA to the DOE in 2026. This page cites the version read on November 10, 2026.
A question about a specific model?
AirGreen offers both heat pumps used as examples on this page.
Sources
Data verified November 10, 2026. The criteria and values come from the documents above; the capacity percentage is an AirGreen calculation made with the ENERGY STAR directory values. Programs and their criteria can change.