SENVILLE AURA R454B and DURASTAR Sirius Heat R454B, 12,000 BTU

Home / Comparisons / 12,000 BTU wall-mounted heat pumps

Comparison · Wall-mounted heat pump · 12,000 BTU

SENVILLE AURA R454B and DURASTAR Sirius Heat R454B, figure by figure

Both AHRI certificates publish exactly the same maximum heating capacities, from 8.3 °C to −30 °C. The rest of the sheet is not quite the same: cooling efficiency, a few low-speed operating points, and units of different sizes. Here is every line, side by side.

Max. capacity at −15 °C: 11,500 BTU/h for both Max. capacity at −30 °C: 5,900 BTU/h for both HSPF2 Region V: 8.0 for both SEER2: 25.4 and 24.0
SENVILLE AURA R454B 12,000 BTU, indoor unit, outdoor unit and remote control
SENVILLE

AURA R454B, 12,000 BTU

Ind. SENA-12HF-IGG · Outd. SENA-12HF-OG
AHRI 215735296

Same AHRI and NEEP certified values as: MIDEA MIDEA28 (AHRI 215471381), DIRECT AIR HEAT XTREME PRO R-454B (216571373) and BOSCH Climate 5000 MAX PERFORMANCE R-454B (215223282), in 12,000 BTU. Checked in NEEP on November 9, 2026.

See the product page

AHRI certificate values compared one by one: 27 identical, 14 different. All 12 full-power values are identical.

DURASTAR Sirius Heat R454B 12,000 BTU, indoor unit, outdoor unit and remote control
DURASTAR

Sirius Heat R454B, 12,000 BTU

Ind. DRAW12F2A · Outd. DRA1H12S2A
AHRI 215359252

Close relative of the family shown here: same certified maximum heating capacities, but different SEER2, EER2 and several low-speed points. So it is not the same certificate.

See the product page
Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec’s Rate D, taxes included. Both heat pumps are calculated in exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the reference point.

How this amount is calculated
  1. Heat to deliver over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours per day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump as for the baseboards: this simplification does not account for recovery after a temperature setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
  3. Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario you can set above, from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a ceiling, since a variable-speed unit slows down once the room is at temperature.
  4. Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. Network access charges, the same with or without a heat pump, are not counted.

AirGreen method v1.1, November 9, 2026. An estimate is used to compare units under the same conditions. The actual bill depends on the house, the insulation, the settings and the use; this amount is not a promise.

Here, both certificates give the same HSPF2 Region V (8.0), so winter costs the same amount in this calculation. The difference comes only from cooling, where the SEER2 differs (25.4 and 24.0).

Line by line

Two nearly identical sheets, laid one over the other

As in a comparison of two versions of a document, each published value is lined up with the other unit’s. Identical lines turn grey; lines that differ open up and show both values, with the difference highlighted.

Extreme cold

Below −15 °C: every published value, none invented

For both certificates, NEEP publishes a point at −15 °C and a point at −30 °C, with exactly the same maximum capacities. In between, DURASTAR publishes a value at −25 °C in its submittal sheet; SENVILLE publishes none on its product page. Where a value is missing, the table shows the range between the two published values on either side.

Two sources, two figures at −30 °C for the Sirius Heat. The AHRI certificate (via NEEP) gives 5,900 BTU/h maximum; the DURASTAR submittal sheet (form V1.2_0325) gives 5,800 BTU/h at the same temperature. We show both. In any direct comparison, the certificate prevails: 5,900 BTU/h for each.
Features

What each manufacturer writes, feature by feature

Only what appears in each manufacturer’s documents. When a document does not mention a feature, that is stated as is: it does not mean the feature is absent, only that it is not published in that document.

Heating in extreme cold

AURAHeating down to −30 °C (−22 °F).

Sirius HeatLow-ambient heating down to −22 °F (−30 °C); “up to 100% heating capacity at 0 °F”, with no figure at that temperature.

SENVILLE, SENA-12HF product page · DURASTAR, submittal sheet V1.2_0325

Heated base pan

AURAPTC heating cable and pan (“PTC Heat Belt and Pan”).

Sirius HeatBase pan heater included (“Included base pan heater”).

SENVILLE, product page · DURASTAR, submittal sheet

Refrigerant leak detection

AURARefrigerant leak detection.

Sirius HeatDetection system for A2L refrigerant.

SENVILLE, product page · DURASTAR, submittal sheet

Remote control with “Follow Me” sensor

AURARemote control with built-in thermostat (“Follow Me”).

Sirius HeatWireless remote control with “Follow Me”.

SENVILLE, product page · DURASTAR, submittal sheet

Wi-Fi and app

AURAWi-Fi (iOS and Android), Alexa compatible.

Sirius HeatNot published in the submittal sheet consulted.

SENVILLE, product page · DURASTAR, submittal sheet V1.2_0325

Wired wall thermostat

AURANot published on the product page consulted.

Sirius HeatCompatible with the DRSTAT101 wired thermostat.

DURASTAR, submittal sheet and Sirius Heat brochure

Operating modes

AURASelf-cleaning mode, built-in dehumidification, vertical swing, self-diagnosis.

Sirius HeatTurbo, ECO, Active Clean and Sleep modes.

SENVILLE, product page · DURASTAR, submittal sheet

Automatic restart

AURANot published on the product page consulted.

Sirius HeatAutomatic restart (“Auto restart”).

DURASTAR, submittal sheet

Frost protection at 8 °C

AURANot published on the product page consulted.

Sirius HeatFreeze protection at 46 °F (8 °C).

DURASTAR, submittal sheet

Indoor unit filter

AURASilver-ion filter.

Sirius HeatNot published in the submittal sheet consulted.

SENVILLE, product page

Fin coating

AURANot published on the product page consulted.

Sirius Heat“Golden Fin” anti-corrosion coating on the indoor and outdoor coils.

DURASTAR, submittal sheet

Quiet

Indoor unit sound, speed by speed

Each manufacturer publishes a sound level for each indoor fan speed. The points below show every one of those figures.

dB

How to read these figures. A lower dB(A) means a quieter unit. Each point is a published speed; the band connects the lowest to the highest.

Why this is not a ranking. Neither SENVILLE nor DURASTAR states, in the documents consulted, the measurement distance or method. The speeds are not named the same way either: the lowest is “Low” at SENVILLE and “Silent” at DURASTAR. Each set of figures is therefore read on its own.

Indoor unit

dB(A) per each manufacturer, from lowest to highest

Measurements taken by each manufacturer using its own method, not stated: different method — not comparable. Outdoors, SENVILLE publishes 57 dB and DURASTAR 56 dB(A), a single value each.

The installation

Two units of different sizes

The certificates look alike; the cabinets do not. According to both manufacturers, the SENVILLE indoor unit is wider and deeper, and its outdoor unit heavier.

Indoor units, at the same scale

Width published by each manufacturer; manufacturer photos drawn to scale.

SENVILLE AURA33.4 × 11.76 × 9.18 in
SENVILLE SENA-12HF-IGG indoor unit
33.4 in
DURASTAR Sirius Heat31.56 × 11.63 × 7.88 in
DURASTAR DRAW12F2A indoor unit
31.56 in

Is your wall wide enough?

Slide to set the free wall width above which the unit will be mounted.

40 in

Both manufacturers also require a clearance around the unit; see the installation guide provided with the quote.

Outdoor units, at the same scale

Width published by each manufacturer.

SENVILLE SENA-12HF-OG30.31 × 21.65 × 12.20 in · 82.67 lb
SENVILLE SENA-12HF-OG outdoor unit
30.31 in
DURASTAR DRA1H12S2A31.69 × 21.81 × 13 in · 72.8 lb
DURASTAR DRA1H12S2A outdoor unit
31.69 in
Installation, per each manufacturerSENVILLE AURA R454BDURASTAR Sirius Heat R454B
Liquid – gas diametersNot published by the manufacturer on the product page consulted1/4 – 3/8 inflare connections
Precharged length25 ft25 ft
Maximum piping lengthNot published by the manufacturer on the product page consulted82 ftminimum 10 ft; 0.16 oz of refrigerant per foot beyond 25 ft
Maximum height differenceNot published by the manufacturer on the product page consulted49 ft
Outdoor unit W × H × D, weight30.31 × 21.65 × 12.20 in, 82.67 lb31.69 × 21.81 × 13 in, 72.8 lb
Indoor unit, weight33.4 × 11.76 × 9.18 in, 24.25 lb31.56 × 11.63 × 7.88 in, 19 lb
Electrical protection and power supply208/230 V; minimum circuit ampacity 12 A, maximum fuse 15 A208/230 V; minimum circuit ampacity 15 A, recommended breaker 15 A
Dehumidification1.4 L/h1.4 L/h71 pints per day
Indoor airflow, maximum speed530 CFMTurbo speed383 CFMTurbo speed
Rated heating / cooling rangeHeating down to −30 °C; low-ambient cooling down to −30 °Cfull range not published on the product page−30 to 24 °C / −30 to 50 °C

Sources: SENVILLE, SENA-12HF product page (senville.ca), consulted November 9, 2026; DURASTAR, submittal sheet DRAW12F2A / DRA1H12S2A, form V1.2_0325. Dimensions converted to decimal inches (31-9/16 in = 31.56 in).

Questions

What we get asked about these two units

Is this one and the same model sold under two names?

Nothing supports that claim. The two pairs have separate AHRI certificates (215735296 and 215359252). Their maximum heating capacities are identical at every published temperature, but the SEER2, the EER2 and several low-speed values differ, and the manufacturers publish different dimensions and weights for the indoor and outdoor units.

Why is the winter cost the same for both?

Because our estimate uses the certificate’s HSPF2 Region V, which is 8.0 for both. The summer cost differs a little, since the SEER2 is 25.4 for the AURA and 24.0 for the Sirius Heat.

At −30 °C, how much heat do they deliver?

According to the AHRI certificate published by NEEP: 5,900 BTU/h maximum for each, with a maximum COP of 1.25. The DURASTAR submittal sheet states 5,800 BTU/h for the Sirius Heat at this temperature; the certificate prevails in any direct comparison.

Is the SENVILLE AURA sold under other names?

Three 12,000 BTU pairs have exactly the same AHRI and NEEP certified values as the AURA R454B: MIDEA MIDEA28 (AHRI 215471381), DIRECT AIR HEAT XTREME PRO R-454B (216571373) and BOSCH Climate 5000 MAX PERFORMANCE R-454B (215223282), checked November 9, 2026. The Sirius Heat shares their maximum capacities, without the same low-speed values.

Which one is quieter indoors?

The documents do not allow us to say. SENVILLE publishes 24 to 47 dB and DURASTAR 20 to 40 dB(A), without stating the distance or the method, and with speeds that are not named the same way.

Do they have Wi-Fi?

SENVILLE advertises Wi-Fi (iOS and Android) and Alexa compatibility for the AURA. The DURASTAR submittal sheet consulted mentions a wireless remote control and compatibility with the DRSTAT101 wired thermostat, with no mention of Wi-Fi.

What about the warranty?

This page does not compare warranties. Each manufacturer’s warranty documents are provided with the quote.

Certified record

The AHRI certificate values, as published

Certified value (AHRI, via NEEP)SENVILLE AURA R454BDURASTAR Sirius Heat R454B
Seasonal efficiency
SEER225.424.0
EER213.413.2
HSPF2 Region IV10.510.5
HSPF2 Region V8.08.0
Rated capacity at 35 °C12,000 BTU/h12,000 BTU/h
Heating at 8.3 °C (47 °F)
Capacity min. / rated / max.3,800 / 12,000 / 16,000 BTU/h3,800 / 12,000 / 16,000 BTU/h
COP min. / rated / max.4.84 / 3.74 / 3.354.84 / 3.63 / 3.35
Heating at −8.3 °C (17 °F)
Capacity min. / rated / max.5,300 / 12,000 / 12,800 BTU/h5,200 / 12,000 / 12,800 BTU/h
COP min. / rated / max.2.22 / 2.51 / 1.752.34 / 2.44 / 1.75
Heating at −15 °C (5 °F)
Capacity min. / rated / max.4,100 / 11,500 / 11,500 BTU/h4,000 / 11,500 / 11,500 BTU/h
COP min. / rated / max.1.72 / 1.80 / 1.801.80 / 1.80 / 1.80
Coldest published point
Test temperature−30 °C (−22 °F)−30 °C (−22 °F)
Capacity min. and max.2,000 and 5,900 BTU/h2,000 and 5,900 BTU/h
COP min. and max.1.17 and 1.251.07 and 1.25
Certificates
RefrigerantR-454BGWP 466 (IPCC, AR4); class A2L (ASHRAE 34)R-454BGWP 466 (IPCC, AR4); class A2L (ASHRAE 34)
ENERGY STAR and cold climateYes; cold climate: yesENERGY STAR directory, Nov. 9, 2026Yes; cold climate: yesENERGY STAR directory, Nov. 9, 2026
AHRI certificate · NEEP record215735296 · record 385685215359252 · record 389518

“higher” marks the higher value of the same measure, under the same conditions. It is not a recommendation.

Both are on the AirGreen website.

A question about either one, or about the installation in your home? Talk to our team.

Sources

Documents consulted

AHRI certificate 215735296 · NEEP, record 385685SENVILLE SENA-12HF-IGG / SENA-12HF-OG, SENA series. Consulted November 9, 2026.
AHRI certificate 215359252 · NEEP, record 389518DURASTAR DRAW12F2A / DRA1H12S2A, DRA series. Consulted November 9, 2026.
ENERGY STAR directory, heat pumpsSENA-12HF-OG (certified May 6, 2026) and DRA1H12S2A (ID 3621148, certified May 6, 2026): cold climate, yes. Consulted November 9, 2026.
DURASTAR, submittal sheet DRAW12F2A / DRA1H12S2AForm V1.2_0325 (copy hosted by a distributor). Capacities, sound, dimensions, piping, features. Consulted November 9, 2026.
DURASTAR, Sirius Heat R-454B brochure (French)DRSTAT101 wired thermostat, modes, warranty. Undated. Consulted November 9, 2026.
SENVILLE, SENA-12HF (AURA) product pagesenville.ca: sound by speed, dimensions, weight, airflow, features, heating down to −30 °C. Consulted November 9, 2026.
NEEP, records 387358, 382480 and 392021MIDEA MIDEA28, DIRECT AIR HEAT XTREME PRO R-454B, BOSCH Climate 5000 MAX PERFORMANCE R-454B: same certified values as the AURA. Consulted November 9, 2026.
Hydro-Québec, Electricity RatesApril 1, 2026, Rate D, sec. 2.5. Consulted November 9, 2026.
NRCan, HOT2000 climate map, Montréal IntlHeating degree-days base 18 °C and design temperature. Consulted November 9, 2026.