Home / Comparisons / Evaporative humidifiers
APRILAIRE 600 and GENERALAIRE GF1042, the water that evaporates
Both mount on the furnace plenum. Part of the warm air passes through a wet pad, comes out more humid and returns through a bypass duct. Their output therefore depends on how warm that air is; each manufacturer states the temperature it measures at.
GENERALAIRE GF1042
GF-1042DMD / DMM · Vapor Pad GF-990-13 · GF-X3 / GF-MHX3
See the product pageWhat each one evaporates, depending on how warm the plenum air is
Pick a plenum air temperature. The page shows an output only where a manufacturer publishes one; at 49 °C, both current documents give the same figure, measured at the same temperature.
No “Cost per season” block on this page: a humidifier has no HSPF2 or SEER2, so the cost method of our heat pump comparisons does not apply.
What goes in, what evaporates, what goes down the drain
Both models let more water run than they evaporate: the excess rinses the pad and carries the minerals to the drain. Feed and evaporation rates come from the manufacturers; the water to drain is our subtraction.
An opening in the plenum and a 6 in. bypass duct
Both hang vertically on a supply or return plenum. Their openings are not the same shape: the AprilAire needs a taller opening, the GeneralAire a wider one.
The openings to cut, at the same scale
Both units at the same scale


Photos scaled to the height each manufacturer publishes; the line under each photo shows the published width. The original photo framing crops the bottom of the GeneralAire.
| Installation | APRILAIRE 600 | GENERALAIRE GF1042 |
|---|---|---|
| Plenum mounting | ||
| Plenum opening | 10 in. wide × 12 3/4 in. high | 13 5/8 in. wide × 9 1/2 in. high |
| Bypass duct | 6 in., round | 6 in., galvanized pipe |
| Supply or return plenum | Air passes from the supply duct to the return duct (owner's manual) | Warm or return plenum, “with equal efficiency” |
| Stated ambient range | Not published by the manufacturer in the 2023 sheet. | Not below 0 °C (32 °F); plenum up to 93 °C (200 °F) |
| Water and drain | ||
| Water feed rate | 3 gal/h (11.4 L/h) | About 3.5 gal/h (13.2 L/h) at 60 psiorifice GF-9903776; GF-9903775 at 20 to 40 psi |
| Hot or cold water | Output published with cold water; hot water (60 °C max) is advised, and required with a heat pump | Cold or hot; hot water can raise output by up to 30 %, copper tubing required |
| Drain | Continuous slope to the drain, no kinks or blockage | 5/8 in. hose, 15 ft supplied; floor drain, laundry sink or condensate pump |
| Electrical and size | ||
| Power supply | 24 V, 60 Hz, 0.5 A | 24 V; 2.5 W running; transformer supplied |
| Dimensions W × H × D | 15 3/8 × 15 3/4 × 10 1/4 in. | 15 1/8 × 14 × 9 in. |
| Humidifier, weight | 10 lb | 13 lb |
What each manufacturer writes, line by line
AprilAire: Model 60 automatic digital control, 10 to 45 %, ±3 % accuracy (Model 600). The 600M comes with the 4655 manual control.
GeneralAire: GF-X3 digital humidistat with the GF-1042DMD; GF-MHX3 manual humidistat with the GF-1042DMM.
AprilAire: blower activation may be needed on a heat pump or a furnace with short cycles.
GeneralAire: GF-GA50 current-sensing relay and GF-12500 air pressure switch among the material that may be needed.
AprilAire: Model 35 water panel, changed once a season, cleaning the housing at the same time.
GeneralAire: GF-990-13 Vapor Pad, at least once a year per the sheet; the manual also writes “1 to 2 times per season”.
AprilAire: close the bypass damper for the summer.
GeneralAire: shut off water and power, close the air damper for the summer.
Questions about these two humidifiers
Why do both show 17 gallons a day?
Because both manufacturers measure at the same point: a plenum at 49 °C (120 °F). AprilAire adds that the blower runs all the time and the water is cold. At 60 °C (140 °F), older documents give 22 gal/day for the AprilAire 600 (form 293, 2013) and 19 gal/day for GeneralAire's 1042LH (January 2012 brochure).
And with a heat pump?
The two manufacturers do not say the same thing. AprilAire's application guide puts heat pump plenums at 90 to 100 °F (32 to 38 °C) and lists the 600 series there, with hot water (60 °C max) and blower activation, without putting a number on output. GeneralAire writes that the unit “is not recommended for heat pumps” and that the published output needs a plenum at 120 °F or more. Our steam versus evaporative comparison takes up the question.
What size of house?
AprilAire gives a table of needs in gal/day by floor area and tightness, with 8 ft ceilings: 17 gal/day matches about 2,500 sq ft of average construction (16.7 gal/day) and 5,000 sq ft of tight construction. GeneralAire writes “up to 2,800 sq ft” on its 2021 sheet and “up to 3,000 sq ft” in its manual. The methods differ.
DMD or DMM at GeneralAire?
GeneralAire's sheet describes both under one model; only the control changes: GF-X3 digital humidistat with the DMD, GF-MHX3 manual humidistat with the DMM.
Is a drain needed?
Yes for both: the water that does not evaporate leaves at the bottom. GeneralAire supplies 15 ft of 5/8 in. hose and names a floor drain, laundry sink or condensate pump. AprilAire asks for a continuous slope, without kinks.
Why not compare the warranties?
Our comparisons do not compare warranties. Each manufacturer's warranty documents come with the quote.
Every published value, in one place
| Value | APRILAIRE 600 | GENERALAIRE GF1042 |
|---|---|---|
| Published output | ||
| Output at 49 °C (120 °F) plenum | 17 gal/day0.7 gal/h; blower on 100 % of the time, cold water | 17 gal/day“based on 120 °F / 49 °C plenum temperature” |
| Output at 60 °C (140 °F) plenum | 22 gal/dayform 293, 2013 | 19 gal/day1042LH brochure, January 2012 |
| With a heat pump | 600 series listed for 90 to 100 °F plenums, hot water and blower activation | “Not recommended for heat pumps” |
| Parts and control | ||
| Evaporator pad | Model 35 | Vapor Pad GF-990-13 |
| Humidistat supplied | Model 60 (600) or 4655 (600M) | GF-X3 (DMD) or GF-MHX3 (DMM) |
| Size | ||
| Dimensions W × H × D | 15 3/8 × 15 3/4 × 10 1/4 in. | 15 1/8 × 14 × 9 in. |
| Humidifier, weight | 10 lb | 13 lb |
US gallons. Values per the manufacturers' documents cited below; none is certified by a third party. The 60 °C values come from older documents than the other lines.
Both are on AirGreen's site.
To choose, talk with our team: tell us what heats the house, where the plenum and the drain are, and whether hot water is near the furnace.
Documents checked
Data checked November 10, 2026. Outputs, flow rates, openings and dimensions: per the manufacturers' documents cited. Litres and water to drain: AirGreen's arithmetic on those values, method shown. When two documents from the same manufacturer differ, the page says so.
Trademarks. AprilAire, GeneralAire and Vapor Pad are trademarks of their respective owners. The logos serve only to identify the products compared. AirGreen is a dealer of both brands; this page is not produced, sponsored or approved by the manufacturers.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong? Write to us: every figure reported is checked again.