The coldest morning of the year: what the Varix Extreme keeps at -30 °C.

LENNOX advertises 100% heating capacity at -22 °F (-30 °C). The table in the same flyer gives the 6-ton module 78,000 BTU/h at -30 °C, against 81,000 at 8.3 °C: 96%. The full 100% holds down to -25 °C. We show you both, module by module, with what each one asks of the panel at 208-230 V.

10models in our catalogueFrom 6 to 24 tons
78,000BTU/h at -30 °C, 6-ton moduleLENNOX flyer 38Y93, April 2025
-25 °Ccoldest point of the table at 100%-13 °F, flyer 38Y93
50/60 AMCA and max. protection, 6 tons at 208-230 VFlyer 38Y93; guide LC1178
The shop

The 208-230 V Varix Extreme, right below

From 6 to 24 tons: one module up to 10 tons, two up to 16, three up to 24. Price on quote, after we visit the building.

AirGreenLENNOX
01 · The coldest morning

One module, one cold morning: the heat the Extreme keeps

One source for the heat: the table in LENNOX flyer 38Y93, the same at 208-230 V and 460 V. Cold frequencies come from the 1991-2020 Montréal-Trudeau normals. The current shown is the 208-230 V figure.

Module
Outdoor temperature

LENNOX table: Varix Extreme flyer 38Y93 (April 2025), heating at 47, -13 and -22 °F, same values at 208-230 V and 460 V. LENNOX publishes no colder value, and no registry (ENERGY STAR, NEEP) lists these modules. MCA: minimum circuit ampacity; max. protection: MOCP.

6-ton module at -30 °C

78,000BTU/h

LENNOX table (flyer 38Y93): 96% of the 81,000 BTU/h the same module gives at 8.3 °C.

What LENNOX advertises“100% heating capacity at -22°F”Flyer 38Y93; VPC072L4M-4G submittal
What its table says96% of the heat at 8.3 °C108% of the nominal 72,000 BTU/h (6 tons)

LENNOX does not say what its 100% is measured against. We stick to the numbers in the table.

LENNOX table 38Y93Nominal: 72,000 BTU/hWorst morning 1991-2020: nothing published

At 208-230 V three-phase: MCA / max. protection50 / 60 A
Module weight (heat pump, 208-230 V)553 lb

The worst morning of 1991-2020 at Montréal-Trudeau: -31.8 °C, on January 27, 1994. A night below -30 °C comes back about every five years (0.21 a year).

Below -30 °C, LENNOX publishes nothing more: the project designer plans backup heat for those hours.

Open the VPC072L4M-4Y page

The LENNOX table, as printed

Outdoor6 tons8 tons10 tons
8.3 °C47 °F81,000108,000135,000
-25 °C-13 °F81,000108,000135,000
-30 °C-22 °F78,000104,500130,600
Cooling, 35 °C95 °F72,00096,000120,000

BTU/h. Heating, then cooling. LENNOX, Varix Extreme flyer 38Y93 (April 2025), same values at 208-230 V and 460 V.

02 · The closest sibling

Same capacity as the standard Varix. Only the Extreme publishes its heat in deep cold.

At the same tonnage, both give the same nominal cooling and the same heat at 8.3 °C, and their submittals stop heating at -22 °F. For the standard Varix, LENNOX publishes no deep-cold heat. At 208-230 V, the Extreme module needs 1.7 to 1.9 times the Varix’s minimum circuit ampacity.

Module compared
Varix ExtremeCold climate · 6 tons
VarixStandard · 6 tons
Outdoor unitVPC072L4M-4Y
Outdoor unitVPC072S4M-4Y
Nominal cooling, 35 °C72,000 BTU/h
Nominal cooling, 35 °C72,000 BTU/h
Heating at 8.3 °C (47 °F)81,000 BTU/h
Heating at 8.3 °C (47 °F)81,000 BTU/h
Published heat at -25 °C (-13 °F)81,000 BTU/h
Published heat at -25 °C (-13 °F)Not published
Published heat at -30 °C (-22 °F)78,000 BTU/h
Published heat at -30 °C (-22 °F)Not published
Heating range on the submittals-30 to 24 °C
Heating range on the submittals-30 to 24 °C
MCA / max. protection at 208-230 V50 / 60 A
MCA / max. protection at 208-230 V28 / 35 A
Modules and range6, 8 or 10 tons; 24 tons at most
Modules and range6 to 20 tons; 38 tons at most
LENNOX warrantyW900015-01
LENNOX warrantyW900015-01

Pink rows are the differences. Extreme: flyer 38Y93 and VPC072L4M-4G submittal; Varix: “Varix VRF” and LC1178 guides (March 2025), VRC072S4M-4Y submittal. The standard 208-230 V Varix units have their own page.

03 · The models, one by one

Every model on this page, with its nameplate voltage

The voltage is read from each product’s number: Y = 208/230 V three-phase, G = 460 V three-phase (LENNOX nomenclature 38Z31). From 12 to 24 tons, LENNOX combines two or three modules; its guides give no reliable values for these combinations, so we take them from the project’s LENNOX selection report.

ModelCapacityNameplate voltageMCA / max. protectionHeat at -30 °C
VPC096L4M-4Y8 tons · 1 module208-230 V, three-phase62 / 70 A104,500 BTU/h
VPC072L4M-4Y6 tons · 1 module208-230 V, three-phase50 / 60 A78,000 BTU/h
VPC288L4M-4Y24 tons · 3 modules208-230 V, three-phaseDepends on the modules chosen (project’s LENNOX selection)
VPC264L4M-4Y22 tons · 3 modules208-230 V, three-phaseDepends on the modules chosen (project’s LENNOX selection)
VPC240L4M-4Y20 tons · 3 modules208-230 V, three-phaseDepends on the modules chosen (project’s LENNOX selection)
VPC216L4M-4Y18 tons · 3 modules208-230 V, three-phaseDepends on the modules chosen (project’s LENNOX selection)
VPC192L4M-4Y16 tons · 2 modules208-230 V, three-phaseDepends on the modules chosen (project’s LENNOX selection)
VPC168L4M-4Y14 tons · 2 modules208-230 V, three-phaseDepends on the modules chosen (project’s LENNOX selection)
VPC144L4M-4Y12 tons · 2 modules208-230 V, three-phaseDepends on the modules chosen (project’s LENNOX selection)
VPC120L4M-4Y10 tons · 1 module208-230 V, three-phase76 / 90 A130,600 BTU/h
04 · Did you know

Three things the LENNOX documents say about the Extreme

L

The L in the number means cold climate

In VPC072L4M-4Y, LENNOX prints “L = COLD CLIMATE (LOW AMBIENT)”. The standard Varix carries an S in that spot, and the final Y means 208/230 V three-phase.

LENNOX, VRF nomenclature 38Z31 (April 2025).
55 dBA

“As quiet as 55 dBA”

That is what LENNOX advertises for the Extreme outdoor units, without stating the size or the measuring distance. For scale: 50 dB(A) is moderate rain; 60, a normal conversation.

LENNOX, flyer 38Y93; Québec.ca, “Noise measurement” (2022).
24 tons

Three modules at most, 24 tons in all

One module covers 6 to 10 tons, two modules 12 to 16 tons, three modules 18 to 24 tons. One system takes up to 64 indoor units.

LENNOX, flyer 38Y93; guide 38V34, p. 10.
05 · Questions

What people ask us about the 208-230 V Extreme

“100% at -22 °F”: is it true?

It depends on the base, and LENNOX does not give it. Flyer 38Y93 advertises 100% heating capacity at -22 °F (-30 °C). Its table gives the 6-ton module 78,000 BTU/h at -22 °F, and 81,000 at -13 °F as at 47 °F. Against the nominal 72,000 BTU/h, that is 108%; against the heat at 8.3 °C, 96%. We stick to the numbers in the table.

And below -30 °C?

The LENNOX table stops at -22 °F (-30 °C), as does the heating range on the LENNOX submittal (-22 to 75 °F). The worst morning of 1991-2020 at Montréal-Trudeau was -31.8 °C, on January 27, 1994, and a night below -30 °C comes back about every five years. The designer plans backup heat for those hours.

Extreme or standard Varix, at 208-230 V?

At the same tonnage, same nominal cooling and same heat at 8.3 °C. The Extreme publishes what it keeps in deep cold (96 to 97% at -30 °C); the standard Varix does not. On the other hand, the 6-ton Extreme module draws 50 / 60 A at 208-230 V, against 28 / 35 A for the Varix. The comparison above shows it size by size.

Is 208-230 V three-phase available in Québec?

At low voltage, Hydro-Québec’s voltage bulletin names only 120 V single-phase and 600 V three-phase. A building that already has a 208 V three-phase distribution can feed the 208-230 V Extreme; otherwise it takes a transformer. Your electrician confirms what the building has. The Extreme also comes in 460 V, not in 575 V.

Is Wi-Fi included?

No, it is an option. LENNOX offers a Wi-Fi adapter among its VRF controls, along with the wireless remote, wired wall controls, the central touch controller and the BACnet gateway.

Which LENNOX warranty?

The W900015-01 VRF certificate gives 10 years only when the installation meets three LENNOX conditions: a design approved by LENNOX VRF Technical Support before purchase, installation by a contractor trained on the LENNOX VRF course, and an approved commissioning report and maintenance plan. Otherwise: 7 years on the compressor and 1 year on other parts. Controls get 1 year. Labour is not covered by LENNOX.

Do these modules carry a LogisVert amount?

We show none. We found no AHRI number and no ENERGY STAR listing for these modules (registry checked October 28, 2026); the LogisVert guide requires ENERGY STAR certification, and the Hydro-Québec program is for residential customers.

How many tons for my building?

We don’t guess it over the phone. We come and see the building, its rooms and its electrical service. For the 10-year warranty, the design must then be approved by LENNOX VRF Technical Support before purchase.

Sold and installed by AirGreen

A 208-230 V Varix Extreme, sold and installed by AirGreen.

We come and see the building, its roof and its electrical service. The quote lists the exact LENNOX models, their nameplate voltage and what each module asks of the panel.

RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16. Gas and oil: a licensed partner.
Free estimateOn site, no obligation.
Showroom1370 Joliot-Curie Street, Suite 712, Boucherville.
AirGreenLENNOX

Sources checked October 28, 2026

  1. LENNOX, Varix Extreme flyer 38Y93 (April 2025): modules, heating table at 47, -13 and -22 °F, cooling at 95 °F, MCA / MOCP, weights, dimensions, “100% heating capacity at -22ºF”, “as quiet as 55 dBA”, 64 indoor units.
  2. LENNOX, VPC072L4M-4G submittal, form 496105 (April 2026): heating range -22 to 75 °F, “100% capacity at -22°F”, nominal capacity; VRC072S4M-4Y submittal, form 496075 (December 2024): standard Varix heating range.
  3. LENNOX, quick reference guides “VRF Outdoor Units” LC1178 and Varix Extreme 38Z73 (March 2025), “Varix VRF” (March 2025): capacities and MCA / MOP of the L4M and S4M modules by voltage.
  4. LENNOX, “VARIX VRF Systems Model Number Identification”, 38Z31 (April 2025); “VRF Complete Product Guide”, 38V34 (April 2025), p. 10: single, twin and triple modules, controls, Wi-Fi adapter.
  5. LENNOX, VRF Equipment Limited Warranty W900015-01 (October 1, 2024).
  6. Hydro-Québec, power quality bulletin on steady-state voltage (in French, undated), checked October 28, 2026.
  7. ENERGY STAR, Certified Air-Source Heat Pumps (dataset w7cv-9xjt), updated October 28, 2026, and NEEP, Cold Climate Air Source Heat Pump List, checked October 28, 2026: no VPC…L4M module.