AirGreenLENNOX
LENNOX · MERIT · VARIX · VARIX EXTREME · VARIX MINIThe LENNOX space at AirGreenSold and installed by AirGreen in Montréal, Laval, Longueuil, on the South Shore and the North Shore.
All of LENNOX
Updated October 28, 2026
208-230 VLENNOX Varix · three-phase · R-410A

Varix 208-230 V: for the building that already has 208 V three-phase.

Same module, same capacities as the 460 V and 575 V Varix. What changes is the current: at 208-230 V a 10-ton module needs 40.8 A minimum and 45 A of protection. The same module at 575 V: 17.4 A and 20 A. We show you the gap, module by module.

17units on this page15 of them are 208-230 V Varix
40.8 Athe 10-ton at 208-230 V, against 17.4 A at 575 VLENNOX quick guide, March 2025
80 Aprotection for the 18 and 20-ton at 208-230 VLENNOX quick guide, March 2025
822 lbthe 16-ton, 73-1/4 in. wideSubmittal VPC192S4M-4Y, Dec. 2024
The shop

The 17 units on this page, right below

208-230 V Varix from 10 to 38 tons, price on quote. 2 model numbers on the list do not end in Y: the “Real voltage” section shows which.

AirGreenLENNOX
01 · Current, module by module

At 208-230 V, the same module draws about twice the current of 575 V

Minimum circuit ampacity (MCA) and maximum overcurrent protection (MOP), as LENNOX prints them at 208-230 V and at 575 V. Capacities do not change from one voltage to the next.

Module or system

MCA: minimum circuit ampacity. MOP: maximum overcurrent protection. Values from the LENNOX Varix quick reference guide (March 2025). Hydro-Québec’s voltage bulletin names 120 V single-phase and 600 V three-phase: your electrician confirms what your service provides.

Varix 10 tons at 208-230 V · VPC120S4M-4Y

40.8A

Minimum circuit ampacity at 208-230 V, with 45 A protection. The same module at 575 V: 17.4 A and 20 A. At 208-230 V it needs 2.3 times the 575 V current.

Minimum ampacity (MCA)

208-230 V40.8 A
575 V17.4 A

Maximum protection (MOP)

208-230 V45 A
575 V20 A
Nominal cooling120,000 BTU/h
Nominal heating135,000 BTU/h
Outdoor modules1

Open the VPC120S4M-4Y page

The eight single modules at a glance
Module208-230 VMCA · MOP575 VMCA · MOP
6 tons28 · 35 A13.4 · 20 A
8 tons36 · 40 A16.1 · 20 A
10 tons40.8 · 45 A17.4 · 20 A
12 tons52.6 · 60 A22.2 · 25 A
14 tons54.4 · 60 A24.8 · 30 A
16 tons60 · 70 A30.5 · 40 A
18 tons64 · 80 A34 · 45 A
20 tons68 · 80 A35.8 · 45 A

LENNOX Varix quick reference guide, March 2025: the eight single modules of the series, 6 to 20 tons.

02 · Real voltage

This list, number by number: the voltage LENNOX writes into it

In the Varix nomenclature, the last letter of the number gives the voltage. We read it for every unit on this page, live.

  • VPC072L4M-4G6 tons · Varix Extreme · three-phaseG460 Vnot a 208-230 V Varix
  • VPC096L4M-4G8 tons · Varix Extreme · three-phaseG460 Vnot a 208-230 V Varix
  • VPC120S4M-4Y10 tons · Varix · three-phaseY208-230 V
  • VPC144S4M-4Y12 tons · Varix · three-phaseY208-230 V
  • VPC168S4M-4Y14 tons · Varix · three-phaseY208-230 V
  • VPC192S4M-4Y16 tons · Varix · three-phaseY208-230 V
  • VPC216S4M-4Y18 tons · Varix · three-phaseY208-230 V
  • VPC240S4M-4Y20 tons · Varix · three-phaseY208-230 V
  • VPC264S4M-4Y22 tons · Varix · three-phaseY208-230 V
  • VPC288S4M-4Y24 tons · Varix · three-phaseY208-230 V
  • VPC312S4M-4Y26 tons · Varix · three-phaseY208-230 V
  • VPC336S4M-4Y28 tons · Varix · three-phaseY208-230 V
  • VPC360S4M-4Y30 tons · Varix · three-phaseY208-230 V
  • VPC384S4M-4Y32 tons · Varix · three-phaseY208-230 V
  • VPC408S4M-4Y34 tons · Varix · three-phaseY208-230 V
  • VPC432S4M-4Y36 tons · Varix · three-phaseY208-230 V
  • VPC456S4M-4Y38 tons · Varix · three-phaseY208-230 V

2 units on this list are not 208-230 V

The highlighted tiles do not end in Y: LENNOX writes another voltage into them. An L before the 4M marks a Varix Extreme, the cold-climate version.

G = 460 V three-phase. The 460 V Varix Extreme has its own page: Varix Extreme 460 V.

Before you choose 208-230 V

Hydro-Québec’s voltage bulletin names two low voltages: 120 V single-phase and 600 V three-phase. 208-230 V three-phase is not one of them. A -4Y Varix connects to a 208-230 V three-phase distribution in the building: your electrician confirms it exists and is large enough. If the building only has 600 V, look at the 575 V Varix.

03 · Did you know

Three things the LENNOX documents say about the 208-230 V Varix

Y

The Y at the end of the number means 208-230 V three-phase

In the LENNOX Varix nomenclature, the last letter gives the voltage: Y for 208/230 V three-phase 60 Hz, G for 460 V, J for 575 V. VPC120S4M-4Y: a 10-ton module at 208-230 V.

LENNOX, Varix nomenclature 38Z31, April 2025.
33

A single 16-ton module takes up to 33 indoor units

That is what the VPC192S4M-4Y submittal prints for the 16-ton at 208-230 V. The 6-ton submittal, in its heat recovery version, gives 12.

LENNOX, submittals VPC192S4M-4Y and VRC072S4M-4Y, Dec. 2024.
184%

You can connect up to 184% of the module’s capacity

Connected indoor units can add up to between 50% and 184% of the outdoor unit’s capacity, according to the 208-230 V LENNOX submittals. The engineer sets the right point with the LENNOX selection.

LENNOX, submittals VPC192S4M-4Y and VRC072S4M-4Y, Dec. 2024.
04 · The project

Who does what in a 208-230 V Varix project, and what LENNOX requires for 10 years

Who does what

  • The engineer designs the system and prepares the drawings.
  • LENNOX approves the design (VRF Technical Support) before purchase: the first condition for 10 years.
  • The electrician confirms the building’s 208-230 V three-phase distribution and its circuits: 35 A to 80 A of protection per single module, according to LENNOX.
  • AirGreen does the refrigeration (RBQ subclass 15.10), ventilation (15.8) and electrical work (16): only what its licence covers.
  • The code: Québec’s pressure installations regulation points to the CSA B52 Mechanical refrigeration code (2023 edition).

The LENNOX W900015-01 warranty

  • 10 years on covered components, only for a “Qualifying Installation”: a design approved by LENNOX VRF Technical Support before purchase, installation by a contractor who completed the LENNOX VRF installation course, and a complete, approved commissioning report and maintenance plan.
  • Without those conditions: 7 years on the compressor and 1 year on other components. VRF controls and accessories: 1 year.
  • For the 10 years, the LENNOX selection tool report and the commissioning report go to LENNOX (VRFregistration@lennox.com).
  • Labour, refrigerant and refrigerant piping are not covered by LENNOX.
  • Equipment ordered online is covered only if the contractor who sells it also installs it.

Submittals print “10 years” with no condition; the warranty certificate of October 1, 2024 sets the conditions.

05 · Questions

What people ask us about the 208-230 V Varix

Can my building take a 208-230 V Varix?

It needs a 208-230 V three-phase distribution. Hydro-Québec’s voltage bulletin names two low voltages, 120 V single-phase and 600 V three-phase; 208-230 V three-phase is not one of them. Your electrician confirms what your service provides. If the building only has 600 V, look at the 575 V Varix.

How much current does a module draw at 208-230 V?

From 28 A (6 tons) to 68 A (20 tons) of minimum circuit ampacity, with 35 A to 80 A of protection, according to the LENNOX Varix quick reference guide (March 2025). From 22 to 38 tons the system has two or three modules and LENNOX prints the current of each.

Does the 208-230 V Varix heat at -30 °C?

LENNOX gives the Varix a heating operating range of -22 to 75 °F (-30 to 24 °C), without publishing its capacity at that temperature. For a published capacity in deep cold, LENNOX has the Varix Extreme, also offered at 208-230 V.

Can one zone heat while another cools?

Not with a VPC: it is a heat pump. Heating and cooling at the same time takes the heat recovery version (VRC…) and a mode selection box, which LENNOX says is required for heat recovery.

What LENNOX warranty comes with a Varix?

The LENNOX VRF limited warranty (W900015-01, October 1, 2024) gives 10 years on covered components only for a Qualifying Installation: a design approved by LENNOX before purchase, a contractor trained on the LENNOX VRF course, documented and approved commissioning. Otherwise, 7 years on the compressor and 1 year on other components. Labour is not covered by LENNOX.

Does LogisVert apply to the Varix?

No. LogisVert is a Hydro-Québec residential program that requires an ENERGY STAR certified unit, and no VPC Varix has an ENERGY STAR record (dataset checked October 28, 2026).

Is Wi-Fi included?

It is an option. LENNOX lists a Wi-Fi adapter among the Varix controls, along with wired wall controls, the central touch controller and the BACnet gateway.

Which size for my building?

The engineer sets it with the LENNOX selection tool, after seeing the building; LENNOX also asks for that selection report for the 10-year warranty. We don’t guess it over the phone.

Sold and installed by AirGreen

Your 208-230 V Varix, installed and connected by AirGreen.

Send us the engineer’s drawings or specifications: we answer with a clear quote, module by module, and what AirGreen’s RBQ licence covers.

RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16. Gas and oil: a licensed partner.
Free estimateOn site, no obligation.
Showroom1370 Joliot-Curie Street, Suite 712, Boucherville.
AirGreenLENNOX

Sources checked October 28, 2026

  1. LENNOX, “Varix VRF — Quick Reference Guide” (March 2025) and “VRF Outdoor Units — Quick Reference Guide”, LC1178 (March 2025): module and combination capacities; minimum circuit ampacity and maximum overcurrent protection at 208-230 V, 460 V and 575 V; operating range.
  2. LENNOX, submittal VPC192S4M-4Y, 496072 (December 2024): nominal and rated capacity, heating, current, compressors, charge, indoor units, 50% to 184% connection ratio, ranges, piping, dimensions, weight.
  3. LENNOX, submittal VRC072S4M-4Y, 496075 (December 2024): heat recovery version of the 6-ton, 12 indoor units, 50% to 184% connection ratio.
  4. LENNOX, “VARIX VRF Systems Model Number Identification”, 38Z31 (April 2025): model number letters.
  5. LENNOX, “VRF Complete Product Guide”, 38V34 (April 2025): single, twin and triple modules; controls, including the Wi-Fi adapter.
  6. LENNOX, Varix Extreme flyer, 38Y93 (April 2025): voltages offered, 208-230 V or 460 V three-phase.
  7. LENNOX, VRF Equipment Limited Warranty, W900015-01 (October 1, 2024).
  8. Hydro-Québec, power quality bulletin on steady-state voltage, undated, checked October 28, 2026.
  9. Légis Québec, Regulation respecting pressure installations, CQLR c. B-1.1, r. 6.1 (up to date as of July 1, 2026), s. 10; Standards Council of Canada, CSA B52:23 Mechanical refrigeration code (published November 30, 2023).
  10. RBQ, information sheets for subclasses 15.8 (April 2024) and 15.10 (August 14, 2024).
  11. ENERGY STAR, Certified Air-Source Heat Pumps (dataset w7cv-9xjt), updated October 28, 2026: no VPC Varix. Hydro-Québec, LogisVert residential participation guide, version 1.10 (September 15, 2026).

Price on quote. Free on-site estimate.