AirGreenLENNOX
LENNOX · MERIT · VARIX · VARIX EXTREME · VARIX MINIThe LENNOX space at AirGreenSold and installed by AirGreen in Montréal, Laval, Longueuil, on the South Shore and the North Shore.
All of LENNOX
Updated October 28, 2026
575 VLENNOX Varix · three-phase · R-410A

Varix 575 V: the VRF that connects to Hydro-Québec’s 600 V.

Hydro-Québec says it in its voltage bulletin: some business customers have a 600 V service “suited to loads with a nominal voltage of 575 V” (our translation). That is the -4J Varix’s voltage. Here, the protection for each module, from 20 A to 45 A, as LENNOX prints it.

17systems on this pagefrom 6 to 38 tons
600 VHydro-Québec’s service, normal range 550 to 625 VHydro-Québec voltage bulletin
45 Aprotection for the 18 and 20-ton; 20 A from 6 to 10 tonsLENNOX quick guide, March 2025
24.8 Athe 14-ton at 575 V, a figure its submittal confirmsSubmittal VRC168S4M-4J, Dec. 2024
The shop

The 575 V Varix, right below

17 systems from 6 to 38 tons, price on quote. Every model number ends in J: 575 V three-phase.

AirGreenLENNOX
01 · Protection, module by module

At 575 V, each Varix module fits on 20 A to 45 A of protection

Maximum overcurrent protection (MOP) and minimum circuit ampacity (MCA) at 575 V, from the LENNOX Varix quick reference guide (March 2025). The 14-ton 575 V submittal gives the same 24.8 A and 30 A.

Module or system
Your service: Hydro-Québec’s 600 V
530550600625635

Gradient: the 600 V normal range, 550 to 625 V; pale band: the marginal range, 530 to 635 V. Hydro-Québec writes that this service suits 575 V loads. Your electrician confirms yours.

Varix 10 tons at 575 V · VPC120S4M-4J

20A

Maximum protection for this module at 575 V. Minimum circuit ampacity: 17.4 A.

The eight single modules at 575 V

Nominal cooling120,000 BTU/h
Nominal heating135,000 BTU/h
Outdoor modules1

Open the VPC120S4M-4J page

02 · The closest sibling

575 V or 460 V at equal capacity: a little less current, and no transformer

Same module, same capacity. What changes: the letter (J or G), the current, and the path from Hydro-Québec’s 600 V.

Module compared
Varix 575 V · 10 tonsLetter J · this page
Varix 460 V · 10 tonsLetter G
Model numberVPC120S4M-4J
Model numberVPC120S4M-4G
Unit voltage575 V three-phase, 60 Hz
Unit voltage460 V three-phase, 60 Hz
On Hydro-Québec’s 600 VDirect connection: this service suits 575 V loads
On Hydro-Québec’s 600 V600 to 480 V transformer, which the electrician confirms
Minimum ampacity (MCA)17.4 A
Minimum ampacity (MCA)19.4 A
Maximum protection (MOP)20 A
Maximum protection (MOP)25 A
Cooling · heating120,000 · 135,000 BTU/h
Cooling · heating120,000 · 135,000 BTU/h
Varix Extreme at this voltageNo
Varix Extreme at this voltageYes: 6, 8 and 10-ton modules
LENNOX warrantyW900015-01, same conditions
LENNOX warrantyW900015-01, same conditions

Pink rows are the differences. Current: LENNOX Varix quick reference guide (March 2025). Voltages: Hydro-Québec voltage bulletin. Varix Extreme: LENNOX flyer 38Y93 (April 2025).

03 · Did you know

Three things the LENNOX documents say about the 575 V Varix

J

The J at the end of the number means 575 V three-phase

In the LENNOX Varix nomenclature: J = 575 V three-phase 60 Hz. The VRC168S4M-4J submittal confirms it in practice: its 24.8 A and 30 A are the 575 V column of the quick guide.

LENNOX, nomenclature 38Z31 (Apr. 2025); submittal VRC168S4M-4J (Dec. 2024).
20 A

From 6 to 10 tons, the same 20 A protection

At 575 V, the 6, 8 and 10-ton modules share a 20 A maximum protection, for 13.4 to 17.4 A of minimum ampacity. At 460 V, the 10-ton already moves to 25 A.

LENNOX, Varix quick reference guide, March 2025.
Extreme

No Varix Extreme at 575 V

LENNOX offers the Varix Extreme, its cold-climate version, at 208-230 V or 460 V three-phase only. On a 600 V service, the standard Varix is the one that comes in 575 V.

LENNOX, Varix Extreme flyer 38Y93, April 2025.
04 · The project

Who does what in a 575 V Varix project, and what LENNOX requires for 10 years

Who does what

  • The engineer designs the system and prepares the drawings.
  • LENNOX approves the design (VRF Technical Support) before purchase: the first condition for 10 years.
  • The electrician confirms the 600 V service and the 575 V circuits: 20 A to 45 A of protection per single module, according to LENNOX.
  • AirGreen does the refrigeration (RBQ subclass 15.10), ventilation (15.8) and electrical work (16): only what its licence covers.
  • The code: Québec’s pressure installations regulation points to the CSA B52 Mechanical refrigeration code (2023 edition).

The LENNOX W900015-01 warranty

  • 10 years on covered components, only for a “Qualifying Installation”: a design approved by LENNOX VRF Technical Support before purchase, installation by a contractor who completed the LENNOX VRF installation course, and a complete, approved commissioning report and maintenance plan.
  • Without those conditions: 7 years on the compressor and 1 year on other components. VRF controls and accessories: 1 year.
  • For the 10 years, the LENNOX selection tool report and the commissioning report go to LENNOX (VRFregistration@lennox.com).
  • Labour, refrigerant and refrigerant piping are not covered by LENNOX.
  • Equipment ordered online is covered only if the contractor who sells it also installs it.

Submittals print “10 years” with no condition; the warranty certificate of October 1, 2024 sets the conditions.

05 · Questions

What people ask us about the 575 V Varix

Does the 575 V Varix connect straight to Hydro-Québec?

Hydro-Québec writes that some business customers have a 600 V service “suited to loads with a nominal voltage of 575 V” (our translation). The -4J Varix is 575 V three-phase equipment. Your electrician confirms your building’s service; Hydro-Québec gives the 600 V normal range as 550 to 625 V.

What protection does my module need at 575 V?

20 A for 6 to 10 tons, 25 A for 12 tons, 30 A for 14 tons, 40 A for 16 tons and 45 A for 18 and 20 tons: that is the maximum protection LENNOX prints for each single module in its Varix quick reference guide (March 2025). From 22 to 38 tons, each module in the system has its own value, read from the LENNOX selection for the project.

Does the 575 V Varix heat at -30 °C?

LENNOX gives the Varix a heating operating range of -22 to 75 °F (-30 to 24 °C), without publishing its capacity at that temperature. For a published capacity in deep cold, LENNOX has the Varix Extreme, but not at 575 V: only at 208-230 V or 460 V (Varix Extreme 460 V).

Can one zone heat while another cools?

Not with a VPC: it is a heat pump. Heating and cooling at the same time takes the heat recovery version (VRC…) and a mode selection box, which LENNOX says is required for heat recovery.

What LENNOX warranty comes with a Varix?

The LENNOX VRF limited warranty (W900015-01, October 1, 2024) gives 10 years on covered components only for a Qualifying Installation: a design approved by LENNOX before purchase, a contractor trained on the LENNOX VRF course, documented and approved commissioning. Otherwise, 7 years on the compressor and 1 year on other components. Labour is not covered by LENNOX.

Does LogisVert apply to the Varix?

No. LogisVert is a Hydro-Québec residential program that requires an ENERGY STAR certified unit, and no VPC Varix has an ENERGY STAR record (dataset checked October 28, 2026).

Is Wi-Fi included?

It is an option. LENNOX lists a Wi-Fi adapter among the Varix controls, along with wired wall controls, the central touch controller and the BACnet gateway.

Which size for my building?

The engineer sets it with the LENNOX selection tool, after seeing the building; LENNOX also asks for that selection report for the 10-year warranty. We don’t guess it over the phone.

Sold and installed by AirGreen

Your 575 V Varix, installed and connected by AirGreen on your 600 V.

Send us the engineer’s drawings and a photo of your electrical service: we answer with a clear quote, module by module, and what AirGreen’s RBQ licence covers.

RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16. Gas and oil: a licensed partner.
Free estimateOn site, no obligation.
Showroom1370 Joliot-Curie Street, Suite 712, Boucherville.
AirGreenLENNOX

Sources checked October 28, 2026

  1. LENNOX, “Varix VRF — Quick Reference Guide” (March 2025) and “VRF Outdoor Units — Quick Reference Guide”, LC1178 (March 2025): module and combination capacities; minimum circuit ampacity and maximum overcurrent protection at 208-230 V, 460 V and 575 V; operating range.
  2. LENNOX, submittal VRC168S4M-4J, 496123 (December 2024): heat recovery version of the 14-ton at 575 V; nominal and rated capacity, heating, current, compressors, charge, indoor units, heating range, piping, dimensions, weight.
  3. LENNOX, “VARIX VRF Systems Model Number Identification”, 38Z31 (April 2025): model number letters.
  4. LENNOX, “VRF Complete Product Guide”, 38V34 (April 2025): single, twin and triple modules; controls, including the Wi-Fi adapter.
  5. LENNOX, Varix Extreme flyer, 38Y93 (April 2025): voltages offered, 208-230 V or 460 V three-phase.
  6. LENNOX, VRF Equipment Limited Warranty, W900015-01 (October 1, 2024).
  7. Hydro-Québec, power quality bulletin on steady-state voltage, undated, checked October 28, 2026.
  8. Légis Québec, Regulation respecting pressure installations, CQLR c. B-1.1, r. 6.1 (up to date as of July 1, 2026), s. 10; Standards Council of Canada, CSA B52:23 Mechanical refrigeration code (published November 30, 2023).
  9. RBQ, information sheets for subclasses 15.8 (April 2024) and 15.10 (August 14, 2024).
  10. ENERGY STAR, Certified Air-Source Heat Pumps (dataset w7cv-9xjt), updated October 28, 2026: no VPC Varix. Hydro-Québec, LogisVert residential participation guide, version 1.10 (September 15, 2026).

Price on quote. Free on-site estimate.