AirGreenTRANE
RunTru 23 SeriesTRANE RunTru 23 wall heat pump, heating down to −30 °CSold and installed by AirGreen. We install across Montreal, Laval, Longueuil, the South Shore and the North Shore.
The whole TRANE space
RunTru 23 Series

TRANE RunTru 23: the heat it gives, degree by degree

4 sizes, 9,000 to 24,000 BTU/h, using R-410A. For each one, Trane publishes a heating table from −30 °C to 26 °C. We turned it into a tool: pick the size and the outdoor temperature, and it gives the heat Trane publishes for that point.

Updated October 29, 2026. Figures from Trane’s documents and the sources listed at the bottom of the page.
4sizes on this page
−30 °Cpublished heating limit, per Trane
15,311BTU/h at −30 °C, the 24,000
23SEER2, on all four sizes
Our reading of the figures

On an ordinary January night in Montreal (−14 °C, the average January low in the 1981–2010 normals), the 12,000 BTU/h RunTru 23 still gives 9,894 BTU/h, 82% of its rated output. At −30 °C, it has 6,380 BTU/h left. The on-site estimate tells you whether the room needs backup heat.

Sold and installed by AirGreenPublished heating down to −30 °CIndoors from 25 dB(A) at 1 mFree on-site estimate
The models

The 4 RunTru 23 units

Price on quote, after the free on-site estimate.

R-410A9,000 to 24,000 BTU/h
TRANE
TRANETRANE
01 · The cold night

How much heat at −20 °C, −25 °C, −30 °C?

Pick the size, then the outdoor temperature. The figures are those of Trane’s heating table for each size, with the room at 20 °C.

Size
−30 °C8 °C
9,894BTU/h

that is 2.90 kW, or 82% of its rated 12,000 BTU/h

Share of rated output82%

In Montreal, Montreal-Trudeau station

  • Average January low−14.0 °C
  • Days below −10 °C62.9 a year
  • Days below −20 °C14.3 a year
  • Days below −30 °C0.27 a year
  • Station record, January 15, 1957−37.8 °C

Environment and Climate Change Canada, 1981–2010 normals; the record covers the station’s whole period. A “day below −10 °C” is a day whose low drops below it.

Source: Trane submittals M4THS2309A to 2324A-SUB-1B-EN (August 5, 2022), heating table, 20 °C column. Trane presents these capacities as normal operation, not as certified values. Trane does not publish power input by temperature: the tool shows heat, not efficiency.

TRANETRANE
02 · The four sizes

The RunTru 23 in figures, size by size

Trane figure9,000 BTU/h12,000 BTU/h18,000 BTU/h24,000 BTU/h
Rated cooling9,100 BTU/h12,000 BTU/h18,000 BTU/h22,000 BTU/h
Rated heating11,000 BTU/h12,000 BTU/h18,200 BTU/h24,000 BTU/h
SEER2 / HSPF2 / EER223 / 9.5 / 14.723 / 9 / 12.523 / 8.3 / 1323 / 9.5 / 13
Heat at −30 °C4,100 BTU/h6,380 BTU/h7,842 BTU/h15,311 BTU/h
Outdoor sound, at 1 m52 dB(A)52 dB(A)57 dB(A)59 dB(A)
Indoor, 7 speeds25 to 40 dB(A)27 to 43 dB(A)31 to 46 dB(A)35 to 53 dB(A)
Line set, liquid – gas1/4 – 3/8 in1/4 – 1/2 in1/4 – 5/8 in1/4 – 5/8 in
Longest run / highest lift15 m / 10 m20 m / 10 m30 m / 20 m30 m / 20 m
Circuit, MCA / MOP9 A / 15 A10 A / 15 A15 A / 20 A16 A / 25 A
Compressorrotaryrotaryrotarytwin rotary
Outdoor unit, W × H × D848 × 596 × 320 mm, 33.5 kg899 × 596 × 378 mm, 38 kg965 × 700 × 396 mm, 47 kg1,003 × 790 × 427 mm, 56.5 kg
The modelSee the productSee the productSee the productSee the product

Sources: Trane sell sheet 26-1063-04 (2024) for SEER2, HSPF2 and EER2; submittals M4THS23…-SUB-1B-EN (August 5, 2022) for the rest. Sound as sound pressure at 1 m.

TRANETRANE
03 · 23 versus 17

The same size in the other series

In the 12,000 BTU/h size, the RunTru 17 gives 6,800 BTU/h at −20 °C, 994 BTU/h less than the RunTru 23, and that is the lowest temperature Trane publishes for it. For cooling, its SEER2 is 16.5 against 23.

TRANETRANE
04 · Installation

What Trane requires at installation

Two rules specific to the 23 Series, then the ones Trane also gives for the 17 Series. A proper installation is checked against them.

  • 23 Series: the outdoor unit away from bedroom windows (guide, p. 12).
  • 23 Series: line set no longer than 15 m on the 9,000, 20 m on the 12,000 and 30 m on the 18,000 and 24,000, with a height difference of 10 m (9,000 and 12,000) or 20 m (18,000 and 24,000) at most.
  • The outdoor unit at least 31.8 mm (1 1/4 in) above the ground or its base, for the drain, level, and fastened firmly where winds are strong.
  • Evacuation to 350 microns or below before start-up.
  • Interconnecting wire at least 14 AWG, 600 V, stranded, no longer than 70 m.

Sources: Trane installer’s guide 88-M4MHW23-1A-EN (November 22, 2021) and submittals (2022); for the shared rules, also the 17 Series guide, 88-M4MHW17-1B-EN (March 16, 2023).

TRANETRANE
05 · Owners

You already have a RunTru 23

  • Filter: activated carbon and catechin, to be cleaned at least once a year; the 24,000 also has a washable filter and an air-purifying filter.Submittals
  • No remote? The button on the unit starts AUTO mode: 25 °C in cooling, 20 °C in heating.Installer’s guide, p. 42 (77 and 68 °F)
  • Code F0: refrigerant leak protection. That’s a job for a refrigeration technician.Installer’s guide, code list
  • Warranty: Trane’s limited parts warranty goes, in most cases, from 5 to 10 years if the unit is registered within 60 days of installation; residential and multi-family use. Labour is not covered by Trane; AirGreen guarantees it for 6 years on installations done since October 5, 2026. RunTru registration line: 1-855-956-5685.runtruhvac.com, Warranty page
TRANETRANE
06 · Did you know

Three RunTru 23 details

01

On R-410A, the RunTru 23 heats colder, per Trane, than the brand’s newer R-454B wall unit: down to −30 °C, against −25 °C for the 9,000 to 24,000 BTU/h M5THS23.

Guide 88-M4MHW23-1A-EN, p. 10; guides 88-M5MHWUN-1A-EN and DLR-SVX026A-EN
02

It also cools in deep cold: Trane gives a cooling range of −29 °C to 50 °C outdoors.

Installer’s guide 88-M4MHW23-1A-EN, p. 10
03

The 24,000 runs a twin rotary compressor; the 9,000, 12,000 and 18,000 run a single rotary.

Submittals M4THS23…-SUB-1B-EN
07 · Questions

What people ask us about the RunTru 23

Does it really heat at −30 °C?
Trane publishes a heating range of −30 °C to 30 °C and, in its tables, gives the heat at −30 °C for each size: from 4,100 BTU/h (9,000) to 15,311 BTU/h (24,000), with the room at 20 °C.
What is its efficiency (COP) in deep cold?
Trane does not publish it. Its sheets give one COP per size, at test conditions (3.61 for the 12,000), and its tables give heat, not power input.
Is it ENERGY STAR cold-climate certified?
No. No M4THS unit is in the current Canadian ENERGY STAR list, cold climate or otherwise (checked October 28, 2026), even though the 23 Series sheets still carry the logo. For a heat pump installed since November 26, 2025, LogisVert requires that certification: no LogisVert grant on this series under the current rules. Only Hydro-Québec confirms the assistance granted.
Is it noisy?
Indoors, 25 to 53 dB(A) at 1 m depending on size and fan speed: at the lowest speed, all four sizes stay under 40 dB(A) (25 to 35), a library or a refrigerator on Québec.ca’s scale. Outdoors, 52 to 59 dB(A) at 1 m, above the 50 dB(A) Québec.ca gives as the start of annoyance; Trane’s guide asks for the outdoor unit to go away from bedroom windows.
Do I still need backup heat?
It depends on the room. The colder it gets, the less heat it gives: the Cold Night tool above shows it size by size. The on-site visit settles it, once we’ve seen the room.
AirGreen
AirGreen × TRANE

A RunTru 23 in your home, installed by AirGreen

One visit to see the room and measure; the written quote says which RunTru 23 size to choose, and whether backup heat still makes sense.