GREENTEK PROFILE 1.2E and LIFEBREATH METRO XTR, ERV air exchangers

Home / Comparisons / Air exchangers

Comparison · ERV air exchanger · 127 CFM at 0.4 in. w.c.

GREENTEK PROFILE 1.2E and LIFEBREATH METRO XTR: two 10-inch ERVs for the ceiling

Two slim energy recovery ventilators (ERVs), made to slip above a dropped ceiling or into a condo bulkhead. Same thickness on both sheets, 10 in., and the same airflow in the HVI directory at 0.4 in. w.c., 127 CFM. What separates them shows elsewhere: the size of the ports, the length of the cabinet, the room to leave for servicing, the watts and the way they defrost.

At 0.4 in. w.c.: 127 and 127 CFM (HVI) Ports: 5 in. and 6 in. Servicing: 8.5 in. and 22 in. in front METRO XTR at 64 CFM: 54 W (HVI), 77 W (sheet 0724)
GREENTEK PROFILE 1.2E (AirGreen image)
GREENTEK

PROFILE 1.2E

ERV, side ports · product 464401 · HVI 2005261

Sheet 464046 (rev. 2024-04-10) · same HVI values as the FANTECH FIT 120E (2005016), same listed owner, Systemair Inc.

See the product page
LIFEBREATH METRO XTR (AirGreen image)
LIFEBREATH

METRO XTR

ERV, ports at both ends · HVI 2005571

Sheet METRO XTR - 0724 · manual 69-METRO IOM 0826

See the product page
Estimated running cost

PROFILE 1.2E or METRO XTR: what the fans cost per year

An air exchanger does not heat or cool: what it uses is fan power. The HVI directory publishes the watts at each 0 °C test point. The METRO XTR is listed there at 54 W at both 49 and 64 CFM; its 0724 sheet states 77 W at 64 CFM. The calculation follows the directory.

HVI test point, at 0 °C
Price per kWh (Rate D, April 1, 2026)
How this amount is calculated
  1. Power: the watts in the HVI directory at 0 °C. First point: 55 W at 51 CFM (PROFILE 1.2E) and 54 W at 49 CFM (METRO XTR). Second point: 63 W at 68 CFM and 54 W at 64 CFM. The PROFILE 1.2E also has a third point, 104 W at 131 CFM; the METRO XTR has only two at 0 °C.
  2. Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
  3. Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.

The two units are not tested at exactly the same airflows: the dollar gap mixes fan consumption with the amount of air moved. AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the home, the settings and the use; this amount is not a promise.

In the ceiling

A section through the dropped ceiling, to scale, with the access panel and the ducts

Both cabinets are 10 in. thick. Move the slider to change the height of the gap between the slab and the dropped ceiling: the diagram shows whether the cabinet fits, the size of the ducts coming out of it, and the zone to keep clear under the access panel to open the unit. Each manufacturer publishes its own distance.

Photo of the GREENTEK PROFILE 1.2E
Photo, in perspective: not to scale
Photo of the LIFEBREATH METRO XTR
Photo, in perspective: not to scale
PROFILE 1.2E ports (sheet 464046): four 5 in. (125 mm) round metal connections, rubber seal, two on each side. Standard version: house-side supply and return on the right; the -M versions put them on the left.
METRO XTR ports (sheet 0724, manual 0826, fig. 9): four 6 in. (152 mm) round collars, two at each end, with balancing ports built into the collars. Mirrored version offered.

Diagram to scale (same scale for both). Lengths drawn: PROFILE 1.2E, 20 27/32 in. cabinet and 24 5/8 in. with the connections (sheet 464046); METRO XTR, 26 in. (660 mm) cabinet, collars drawn short because the sheet does not give their length. The photos, taken in perspective, are not to scale.

The HVI numbers

What the PROFILE 1.2E and the METRO XTR recover, from −25 °C to 35 °C

The HVI directory publishes each unit's effectiveness at test airflows chosen by the manufacturer. For these two ERVs, the test airflows are close at 0 °C (51 and 49 CFM) but move apart at −25 °C (51 and 70 CFM) and in summer (51 and 64 CFM). The numbers read side by side; none is marked as higher.

SRE: sensible recovery efficiency; adjusted SRE: the same, corrected for fan heat per the HVI method. TRE: total recovery efficiency, heat and moisture, in cooling. Net moisture transfer: share of moisture moved from one airstream to the other. Source: HVI directory, section III, data as of November 4, 2026.

Airflow and pressure

From 0.4 to 0.6 in. w.c., exactly the same airflow

Net fresh airflow drops as the static pressure in the ducts rises. The HVI directory gives the METRO XTR a few more CFM at low pressures (0.1 to 0.3 in.), the same values for both units from 0.4 to 0.6 in. (127, 117 and 106 CFM), then a few more CFM for the PROFILE 1.2E from 0.7 to 1.0 in. The actual pressure depends on each installation's ducts, grilles and hoods.

GREENTEK PROFILE 1.2E HVI 2005261LIFEBREATH METRO XTR HVI 2005571
Construction

5 or 6 in. ports, slide-out core or hinged door: inside the two cabinets

Two ways to reach the same airflow in 10 in.: a shorter cabinet with 5 in. ports whose core slides out, on one side; a longer cabinet with 6 in. ports, a hinged door and an outside electrical box, on the other. Each card says which document publishes it.

Recovery core

PROFILE 1.2E: polymer membrane, 12 × 12 in., 8.15 in. deep; freeze tolerant, water washable, mould resistant. METRO XTR: cross-flow core that transfers heat and water vapour, removable for cleaning.

sheet 464046sheet 0724
Defrost

PROFILE 1.2E: at −10 °C and below, the fresh-air fan stops and the exhaust fan goes to high speed, then the cycle repeats. METRO XTR: below −3 °C, the fresh-air fan stops while exhaust continues; 3 min of defrost for 25 min of ventilation at −3 °C, 4.5 for 17 at −20 °C, 7 for 15 at −35 °C.

sheet 464046manual 0826, p. 14
Filters

PROFILE 1.2E: two washable electrostatic filters, UL 900 certified, 11.3 × 8.15 × 0.125 in. METRO XTR: washable MERV 6 filters on the exhaust and supply airstreams; MERV 13 optional (65-195-6R).

sheet 464046sheet 0724
Fans and motors

PROFILE 1.2E: two backward-curved fans, factory balanced, sealed ball bearings; several speeds. METRO XTR: one PSC motorized impeller per airstream; five speeds, the highest (Hi3) set at the factory, adjustable by DIP switches.

sheet 464046sheet 0724
Controls

PROFILE 1.2E: optional STS 2.0 touch-screen control, EHC 2.5 and RD-1 dehumidistats, EHC 2.0 control, T4 and T5 timers. METRO XTR: 5 speeds with the DXPL03, 2 with the BC02 or BC04, 1 with the BC03.

sheet 464046manual 0826
Mounting

PROFILE 1.2E: hung from the ceiling with the supplied bracket, or fixed to the wall; optional chain kit. METRO XTR: on the ceiling or the wall, brackets supplied; on a wall, the door hinges must face the floor.

sheet 464046manual 0826, p. 25
Service access

PROFILE 1.2E: core, filters, fans and electronic panel accessible; the core slides out with 8.5 in. (216 mm) of clearance in front. METRO XTR: hinged door, no screws; externally mounted electrical box for the board and DIP switches; 22 in. (559 mm) in front for servicing.

sheet 464046sheet 0724
Drain

No drain required for either, per both manufacturers.

sheet 464046sheet 0724
Installation

Dropped ceiling, access panel and clearance: installation per Greentek and Lifebreath

ItemGREENTEK PROFILE 1.2ELIFEBREATH METRO XTR
Cabinet dimensionssheet 464046 · sheet 0724 and manual 0826, fig. 920 27/32 × 20 3/4 in., 10 in. thick; 24 5/8 in. with the connections26 × 22 in. (660 × 559 mm), 10 in. (254 mm) thick
Weight34 lb (15 kg), including core42 lb (19 kg)
Ports4 round 5 in. (125 mm) connections, rubber seal, on the sides4 round 6 in. (152 mm) collars, built-in balancing ports, at both ends
MountingCeiling (bracket supplied) or wallCeiling or wall, hinges toward the floor on a wall
Service clearance8.5 in. (216 mm) in front, to slide out the core22 in. (559 mm) in front, for servicing
Power supply120 V; 120 W rated, 1.0 A running, 1.4 A CSA rating; 3 ft cord with plug120 V, 60 Hz; 1.2 A, MCA 2.0 A, MOP 15 A; hardwired and mirrored versions offered
DrainNo drain requiredNo drain required
DefrostAt −10 °C and below: fresh air off, exhaust at high speedBelow −3 °C: fresh air off, exhaust continues
LocationAbove a dropped ceiling, where mechanical space is shortHeated space; standard 10 in. dropped ceiling with access panel; bulkhead or closet; attic not recommended

Values declared by the manufacturers. PROFILE 1.2E dimensions read from the table in sheet 464046 (dimensions D, B, E and C, same drawing as Systemair's FIT series).

Questions

Your questions about the PROFILE 1.2E and the METRO XTR

Why does the PROFILE 1.2E have the same numbers as the FANTECH FIT 120E?

In the HVI directory, the GREENTEK PROFILE 1.2E (2005261) and the FANTECH FIT 120E (2005016) have the same listed owner, Systemair Inc., and the same certified values: all ten airflows and all five energy points. Their sheets also publish the same tables. This page compares the PROFILE 1.2E with the METRO XTR; another page in the series compares the FIT 120E with the METRO 120 ERVD.

Do both fit in a 10 in. dropped ceiling?

Both sheets give 10 in. of thickness. Lifebreath writes that its slim models fit a standard 10 in. dropped ceiling with an access panel for maintenance (manual 0826, p. 24). Room must also be left for the ducts: 5 in. in diameter for the PROFILE 1.2E, 6 in. for the METRO XTR, with their insulation.

Why two wattage values for the METRO XTR?

The HVI directory lists the METRO XTR at 54 W at both 49 and 64 CFM, at 0 °C. Lifebreath's METRO XTR - 0724 sheet states 77 W at 64 CFM. This page follows the HVI directory, which is the certification, and shows the sheet's value alongside.

Is a drain needed?

No, per both manufacturers.

What happens in extreme cold?

Both have a 72-hour HVI test at −25 °C: 61% SRE at 51 CFM for the PROFILE 1.2E, 63% at 70 CFM for the METRO XTR; the airflows differ. Both stop their fresh-air fan to defrost: the PROFILE 1.2E from −10 °C, the METRO XTR from −3 °C, with longer cycles when it is colder.

Why doesn't the page compare noise?

Neither the PROFILE 1.2E sheet nor the METRO XTR sheet publishes a sound level. Without a measurement published by both manufacturers, there is nothing to compare fairly.

What airflow does my home need?

The required ventilation rate is calculated under the applicable code and the number of rooms, then the installation is set and balanced on site. This page does not do that calculation: it shows what each unit delivers at each static pressure, per the HVI directory.

All the values

The PROFILE 1.2E and the METRO XTR in the HVI directory, line by line

HVI directory, section III, data as of November 4, 2026. Airflows at the same static pressure compare directly; the energy test points, run at different airflows, read side by side.

MeasurementGREENTEK PROFILE 1.2ELIFEBREATH METRO XTR
Net supply airflow, same static pressure
Airflow at 0.1 in. w.c. (25 Pa)155 CFM161 CFM
Airflow at 0.2 in. w.c. (50 Pa)146 CFM150 CFM
Airflow at 0.3 in. w.c. (75 Pa)136 CFM140 CFM
Airflow at 0.4 in. w.c. (100 Pa)127 CFM127 CFM
Airflow at 0.5 in. w.c. (125 Pa)117 CFM117 CFM
Airflow at 0.6 in. w.c. (150 Pa)106 CFM106 CFM
Airflow at 0.7 in. w.c. (175 Pa)95 CFM93 CFM
Airflow at 0.8 in. w.c. (200 Pa)83 CFM81 CFM
Airflow at 0.9 in. w.c. (225 Pa)72 CFM68 CFM
Airflow at 1.0 in. w.c. (250 Pa)59 CFM55 CFM
Heating, 0 °C: each test point
Sensible recovery (SRE), first point74% at 51 CFM (24 L/s), 55 W; adjusted 81%; moisture 0.7670% at 49 CFM (23 L/s), 54 W; adjusted 78%; moisture 0.63
Sensible recovery (SRE), second point69% at 68 CFM (32 L/s), 63 W; adjusted 75%; moisture 0.7177% at 64 CFM (30 L/s), 54 W; adjusted 83%; moisture 0.60
Sensible recovery (SRE), third point64% at 131 CFM (62 L/s), 104 W; adjusted 69%; moisture 0.60Two test points listed at 0 °C for this unit (49 and 64 CFM, above)
Extreme cold, −25 °C (72-hour test)
Sensible recovery (SRE) at −25 °C61% at 51 CFM (24 L/s), 55 W; adjusted 63%; moisture 0.5463% at 70 CFM (33 L/s), 59 W; adjusted 66%; moisture 0.50
Ventilation reduction at the end of the test (supply / exhaust)12.8% / 0.0%14.4% / 17.6%
Cooling, 35 °C
Total recovery (TRE)64% at 51 CFM, 55 W; adjusted 68%; moisture 0.6853% at 64 CFM, 66 W; adjusted 57%; moisture 0.54
Listing
HVI directory, section IIIHVID 2005261 · Systemair Inc.HVID 2005571 · Airia Brands Inc.
ENERGY STARGreentek reserves the mention for the -EC versions of the PROFILE; the PROFILE 1.2E does not carry itNo, per the AirGreen product page

“higher” marks the higher value of the same measure, under the same conditions. It is not a recommendation.

The PROFILE 1.2E and the METRO XTR are both on the AirGreen website.

The right choice depends on the required ventilation rate, the resistance of the ducts, the room for 5 or 6 in. ducts and the access under the unit. Talk it over with our team.

Sources and documents

Sheets, manual and directory: the sources of this page

HVI, Certified Products Directory, section IIIPublication 911, data as of November 4, 2026 · listings 2005261, 2005571 and 2005016 · consulted November 10, 2026
GREENTEK PROFILE 1.2E specification sheetItem 464046, rev. 2024-04-10, product 464401 · dimensions, weight, electrical, defrost, clearance, controls · consulted November 10, 2026
LIFEBREATH METRO XTR specification sheet“METRO XTR - 0724”, lifebreath.com · electrical, weight, ports, clearance, airflows · consulted November 10, 2026
LIFEBREATH METRO manual69-METRO IOM 0826 · METRO XTR drawing (fig. 9, p. 13), defrost (p. 14), location (p. 24), mounting (p. 25) · consulted November 10, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · fan running cost · consulted November 10, 2026