THERMO 2000 VoltMax SCR VOLTSCR24030P3 Commercial Electric Boiler | 30 kW - 240V 3 Phase

In stock

Thermo 2000’s VoltMax SCR at 30 kW, 240 V three phase: a commercial electric boiler that heats according to your schedule and the outdoor temperature.

Model numberVOLTSCR24030P3

102,360 BTU/h30 kW at 240 V three phase
72 Acurrent at full output
50-200 °Fadjustable setpoint (10-93 °C)
240 V · three phaseProgrammable schedulesOutdoor sensor included
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR24030P3
ManufacturerThermo 2000
DesignationVOLTMAX SCR 30-240-3 PH
Output30 kW (102,360 BTU/h)
Power supply240 V, three phase, 60 Hz
Current72 A
Setpoint50 °F to 200 °F

A 30 kW boiler that heats according to your building’s schedule and the weather

The VoltMax SCR 30-240-3 PH at a glance

Thermo 2000 designs the VoltMax for commercial, institutional and multi-unit buildings. This model delivers 30 kW, or 102,360 BTU/h according to the manufacturer, on a 240 V three-phase supply, and draws 72 A at full output. It heats a loop of radiators, hot-water baseboards or radiant floor, with no GHG emissions on site.

Heating when the building is occupied

Offices in Laval, a store in Longueuil, a workshop on the North Shore: these spaces do not need the same heat in the middle of the night as in the middle of the day. The VoltMax’s Schneider Electric controller handles schedules, and its included outdoor sensor lets it adjust the water setpoint to the temperature outside. The setpoint ranges from 50 °F to 200 °F (10 °C to 93 °C).

Output is measured out by a solid-state relay (SCR) that modulates from 0 to 100%, on top of the relay stages that the controller alternates. According to Thermo 2000, this modulation limits peak power demand. Two high-limit controls, one automatic and one manual, are supplied with the unit.

The building manager can monitor the boiler remotely: Ethernet port with a web page and email alarms, BACnet IP or MS-TP communication, and an external 0-10 Vdc control for setpoint and output. On site, the 3 in backlit display shows alarm codes in French or English.

What to plan for

The boiler needs a 240 V three-phase supply; we size the protection and conductors from the nameplate. It holds 11 US gal of water, weighs 310 lb (141 kg) and is placed with clearances of 3 in at the sides and rear, 24 in at the front and 32 in above. The circulator and expansion tank are not among the supplied parts, and the low-water cut-off is optional at this size.

AirGreen’s installation

After a free on-site estimate, you receive a written quote covering these items. Our technicians connect the boiler to the loop through its four 1 1/2 in male NPT side connections, pipe the discharge of the factory-installed relief valve and mount the outdoor sensor. The electrical connection is made under AirGreen’s RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). At start-up, we program the schedules with you based on occupancy hours, then the outdoor reset and alarms.

AirGreen is a family business established in Montreal for more than fifteen years, also active on the South Shore. Thermo 2000 warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Your estimate

Tell us about your premises and their occupancy hours: the estimate is free, the quote is in writing, and financing is available to spread out your payments.

01 · What it is for

Hot-water heating for a building occupied on a schedule

The VoltMax SCR feeds a loop of radiators, baseboards or radiant floor. Its controller handles schedules and adjusts the setpoint to the included outdoor sensor, which suits spaces occupied mostly during the day.

  • Offices or retail occupied on a schedule
  • Multi-unit building supplied at 240 V three phase
  • Radiant floor in a workshop or commercial space
  • Building monitored remotely by its manager
Schedules and outdoor resetThe controller runs schedules and adjusts the setpoint to the included outdoor sensor.
SCR modulation from 0 to 100%Output follows demand; according to Thermo 2000, this limits peak power demand.
Two high-limit controlsOne automatic and one manual high limit are supplied with the boiler.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 30-240-3 PH
TypeCommercial electric hot-water boiler, SCR modulation
Output30 kW
Output in BTU/h102,360 BTU/h
Power supply240 VAC, 60 Hz, three phase
Current72 A
Heating elementsIncoloy immersion, replaceable
ModulationSCR 0 to 100% (solid-state relay) and relay stages
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT (4 side connections)
Relief valve and drain connections3/4 in female NPT
Temperature setpoint50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD: SCR modulation, stage rotation, outdoor reset, schedules, pump contact with or without domestic hot water priority, 2nd setpoint for an indirect water heater, alarm codes, °C/°F, French and English
CommunicationBACnet IP / MS-TP · Ethernet port (web page, email alarms) · external 0-10 Vdc signal (setpoint and output)
Outdoor sensorIncluded
Low-water cut-offOptional at this size (standard above 60 kW)
ClearancesSides 3 in · rear 3 in · front 24 in · top 32 in · floor 0 in
Weight310 lb (141 kg)
Manufacturer configurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR24030P3
03 · Before installing

What to know before installing

  • Commercial boiler: 240 V three-phase, 60 Hz supply, drawing 72 A. Protection and conductors sized from the nameplate.
  • The low-water cut-off is optional at this size; it is standard above 60 kW.
  • The circulator and the expansion tank are not on the list of supplied parts.
  • Clearances: sides 3 in, rear 3 in, front 24 in, top 32 in, floor 0 in.
  • The unit weighs 310 lb (141 kg) and holds 11 US gal of water.
In the box
  • Schneider Electric controller with backlit LCD
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relay
  • Two high-limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can the heat be turned down when the premises are closed?

The VoltMax controller handles schedules. We program them with you based on the building’s occupancy hours during start-up.

How does the boiler take the weather into account?

With the included outdoor sensor: the controller adjusts the water setpoint to the outdoor temperature, within the 50 °F to 200 °F range.

What electrical supply is needed?

240 V three phase, 60 Hz, for 72 A at full output. We size the protection and conductors from the nameplate.

What comes with the boiler?

The controller, outdoor sensor, control switch, control and power fuses and breakers, SCR relay, two high-limit controls, factory-installed relief valve and drain valve.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 240 V three-phase 30 kW VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.