THERMO 2000 VoltMax SCR VOLTSCR24075P3 Commercial Electric Boiler | 75 kW - 240V 3 Phase

In stock

Thermo 2000’s VoltMax SCR 75 is a 75 kW commercial electric boiler on 240 V three-phase that heats a building’s loop and can also serve an indirect water heater.

Model numberVOLTSCR24075P3

75 kW255,900 BTU/h
180.4 Aon 240 V three-phase
2 setpointsheating and indirect water heater
240 V · three-phaseDomestic hot water priorityOutdoor sensor included
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR24075P3
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 75-240-3 PH
Output75 kW (255,900 BTU/h)
Power supply240 V, three-phase, 60 Hz
Current180.4 A

75 kW on 240 V three-phase to heat the building and its hot water

The largest 240 V three-phase VoltMax SCR in our range

The VoltMax SCR 75 (manufacturer designation: VOLTMAX SCR 75-240-3 PH) is a 75 kW commercial electric boiler, or 255,900 BTU/h. Among the 240 V three-phase VoltMax SCR models we offer, it is the largest size. It is aimed at owners and managers of apartment buildings, small commercial buildings and institutional buildings that already have a 240 V three-phase service.

Like every VoltMax SCR, it heats the water in a closed loop. That water can run through radiators, a radiant floor or the coils of an air handling unit. What makes it useful in a rental building is that it can also take care of an indirect water heater.

One appliance for heating and the indirect water heater

The Schneider Electric controller offers a second setpoint, reserved for the indirect water heater, and a pump contact with or without domestic hot water priority. In practice, a building in Laval or Longueuil that heats its apartments with hot water can also produce domestic water from the same boiler, through an indirect tank ordered separately.

For heating, the included outdoor sensor adjusts water temperature to the weather, over a setpoint range of 50 °F to 200 °F. Output follows demand from 0 to 100% through solid-state relays (SCR), on top of the relay stages; according to Thermo 2000, this modulation limits peak power.

It does, however, need an electrical service to match: the manufacturer lists 180.4 A on 240 V three-phase. We compare that value with the building’s actual capacity before proposing this model.

Installation by AirGreen

The estimate is free and done on site. We note the electrical service, the panel, the loop, the radiators or floor, and the occupants’ hot water needs. You then receive a written quote naming the boiler, the indirect water heater if there is one, the circulator and the expansion tank, the latter two not being on Thermo 2000’s list of supplied components.

On the day, we set the 310 lb boiler in place within its clearances (3 in on the sides and back, 24 in in front, 32 in above), connect the loop to the 1 1/2 in NPT side connections, wire the three-phase supply and the outdoor sensor, then set both setpoints and the priority. The loop is filled and purged before the system goes back into service.

The manufacturer’s warranty covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years. A family business established in Montreal for more than fifteen years, AirGreen holds RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work.

Ask for your estimate

Buildings in Montreal, Laval, Longueuil, on the North Shore and on the South Shore: the estimate is free, the quote is in writing and financing is available.

01 · What it is for

Heating and hot water for a building on 240 V three-phase

In an apartment building or a small commercial building on 240 V three-phase, the VoltMax SCR 75 heats the radiator or radiant floor loop and can also heat an indirect water heater, with or without domestic hot water priority.

  • Hydronically heated apartment buildings with a 240 V three-phase service
  • Heating loops paired with an indirect water heater for domestic water
  • Small commercial buildings with radiant floors or radiators
  • Replacing a commercial electric boiler in an existing building
A second setpoint for domestic waterThe controller manages a separate setpoint for an indirect water heater and a pump contact with or without domestic hot water priority.
75 kW modulated by SCROutput adjusts from 0 to 100% through solid-state relays; Thermo 2000 states that this limits peak power.
Remote monitoringEthernet port with web page and email alarms, BACnet IP / MS-TP for a management system.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 75-240-3 PH
TypeCommercial electric hot-water boiler, vertical design
Output75 kW
Output in BTU/h255,900 BTU/h
Power supply240 VAC, 60 Hz, three-phase
Current180.4 A
ModulationSCR 0 to 100% (solid-state relays) plus relay stages
ConfigurationA (22.5 to 90 kW models)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, French or English, °C or °F
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
External control0-10 Vdc signal (setpoint and output)
FunctionsOutdoor reset, stage rotation, pump contact with or without domestic hot water priority, second setpoint for an indirect water heater
Outdoor sensorIncluded
Heating elementsImmersion type, Incoloy, replaceable
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight310 lb (141 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR24075P3
03 · Before installing

What to know before installing

  • Current of 180.4 A on 240 V three-phase, 60 Hz: the building’s electrical service must be able to supply it, and we check it before quoting.
  • The indirect water heater, circulator and expansion tank are not among the components Thermo 2000 supplies.
  • Space to plan: 3 in on the sides and back, 24 in in front and 32 in above the boiler.
  • 75 kW is the largest 240 V three-phase size we offer in the VoltMax SCR series.
  • Thermo 2000 warranty: 10 years on the tank (closed-loop heating), 2 years on electrical and mechanical components.
In the box
  • Schneider Electric controller
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relays
  • Two limit controls, automatic and manual reset
  • Factory-installed relief valve
  • Drain valve
  • Low-water cut-off (standard above 60 kW)
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can it produce hot water for the apartments?

Through an indirect water heater, yes. The controller manages a second setpoint for that tank and a pump contact, with or without domestic hot water priority. The indirect water heater is ordered separately; we choose it with you.

What does "domestic hot water priority" mean?

With priority on, the indirect water heater’s demand comes before heating demand. The controller lets you turn it on or off, depending on how the building is used.

What current should we plan for?

Thermo 2000 lists 180.4 A on 240 V three-phase, 60 Hz. We compare that value with the capacity of the service and panel during the free estimate.

How much does it weigh and how much room does it take?

It weighs 310 lb (141 kg). Thermo 2000 requires 3 in of clearance on the sides and back, 24 in in front and 32 in above; none at the floor.

Can you install it?

Yes. We set the boiler in place, connect it to the loop, to the indirect water heater if there is one and to the 240 V three-phase service, then commission it.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 240 V VoltMax SCR 75, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.