THERMO 2000 VoltMax SCR VOLTSCR24045P3 Commercial Electric Boiler | 45 kW - 240V 3 Phase

In stock

The 240 V three-phase VoltMax 45 delivers 45 kW of hot water to the ventilation coils, radiators or floors of a commercial building, at a current of 108.3 A.

Model numberVOLTSCR24045P3

45 kW153,540 BTU/h
108.3 Aat 240 V three phase
Hydro-airhot water for coils
240 V · three phaseCoils, radiators, floorsOutdoor sensor included
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR24045P3
ManufacturerThermo 2000
Output45 kW (153,540 BTU/h)
Power supply240 V, three phase, 60 Hz
Current108.3 A
Water volume11 US gal (41.6 L)
Thermo 2000 warrantyTank 10 years · components 2 years

45 kW of hot water to heat a commercial space through its ventilation ductwork

The VoltMax 45 on 240 V three phase

Thermo 2000’s VoltMax is a hot water electric boiler designed for commercial and institutional buildings. The 45 kW model, supplied at 240 V three phase, produces 153,540 BTU/h and draws 108.3 A. It is part of configuration A, which groups the 22.5 to 90 kW sizes.

It heats the water of a closed loop. That water can feed radiators or radiant floors, but also the coil of a ventilation unit: this is known as hydro-air.

Hydro-air: heating through the ductwork with hot water

Many stores, showrooms and restaurants are heated by air distributed through their ductwork. In a hydro-air system, that air passes through a coil supplied with hot water by the boiler, warms up, then circulates through the space. The boiler stays in the mechanical room; the coil goes in the air handler or in a unit heater.

The VoltMax 45 adapts to the chosen coil. Its setpoint ranges from 50 °F to 200 °F (10 °C to 93 °C), and the included outdoor sensor lets the water be adjusted to the weather. Its output follows the demand: SCR solid-state relays vary it from 0 to 100%, in addition to relay stages, and Thermo 2000 points out that this modulation limits peak power demand.

The Schneider Electric controller can also take its commands from the system that runs the ventilation. It communicates over BACnet IP or MS-TP and accepts a 0-10 Vdc signal for setpoint and output. Its Ethernet port provides a web page and email alarms.

What installation by AirGreen covers

AirGreen works in ventilation, refrigeration and electrical under RBQ licence 5645-9605-01, so we look at the whole hydro-air system, not just the boiler. The on-site estimate is free in Montreal, Laval, Longueuil, on the North Shore and on the South Shore. We survey the ductwork, the ventilation unit, the 240 V three-phase service and the space in the mechanical room, then give you a written quote. It specifies the circulator and expansion tank, which are not among the parts supplied by Thermo 2000, and the coil if it needs replacing.

We install the boiler with the required clearances, including 24 in in front and 32 in above, connect it through its 1 1/2 in NPT connections, mount the outdoor sensor and make the electrical connection. After filling and purging, we set the setpoint for the coil and check the supply air temperature with you.

AirGreen is a family business established in Montreal for more than fifteen years. Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Your space, heated through its ductwork

To heat your commercial space with a 45 kW VoltMax in a hydro-air setup, ask for a free estimate. You receive a written quote, and financing is available.

01 · What it is for

Hot water for the ventilation coils of a commercial space

In a hydro-air system, the boiler heats the water and a ventilation unit runs it through a coil; the warmed air then travels through the ductwork. The VoltMax 45 is the boiler in this setup, on 240 V three phase.

  • Stores, showrooms and restaurants heated by air through the ductwork
  • Air handlers or unit heaters fitted with a hot water coil
  • Commercial buildings on 240 V three phase
  • Mixed systems: coils, radiators and radiant floors
A boiler for hydro-airThe VoltMax’s hot water feeds the ventilation unit’s coil, which distributes the heat through the ductwork.
Setpoint from 50 °F to 200 °FA range wide enough to match the water temperature to the chosen coil.
0-10 Vdc controlThe system that runs the ventilation can set the boiler’s setpoint or output by external signal.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
Manufacturer designationVoltMax 45, SCR series (VOLTMAX SCR 45-240-3 PH)
TypeCommercial hot water electric boiler
Output45 kW
Output in BTU/h153,540 BTU/h
Power supply240 VAC, 60 Hz, three phase
Current108.3 A
ModulationSCR from 0 to 100% (solid-state relay) plus relay stages
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French/English
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
External controlSetpoint and output by 0-10 Vdc signal
Outdoor sensorIncluded (outdoor reset)
Domestic hot water2nd setpoint for an indirect water heater; pump contact with or without DHW priority
Low water cut-offOptional up to 60 kW (standard above)
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight310 lb (141 kg)
ConfigurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR24045P3
03 · Before installing

What to know before installing

  • 240 V three-phase, 60 Hz supply, for a current of 108.3 A; the electrician sizes the protection and conductors.
  • The coil, ventilation unit, circulator and expansion tank are not supplied with the boiler: we choose and size them together.
  • The water setpoint is set from the coil or ventilation unit data sheet.
  • Clearances: 24 in in front, 32 in above, 3 in on the sides and at the back, none at the floor.
  • Low water cut-off optional on this size; it is standard above 60 kW.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • Control ON/OFF switch
  • Control and power fuses and breakers
  • SCR relays
  • 2 limit controls, one automatic, one manual
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

What is a hydro-air system?

Heating where hot water from a boiler runs through the coil of a ventilation unit. The air passing through the coil warms up and travels through the ductwork. The VoltMax 45 supplies that hot water.

Can the boiler follow the ventilation?

Yes. Its Schneider Electric controller communicates over BACnet IP or MS-TP and accepts an external 0-10 Vdc signal for setpoint and output.

Can coils and radiant floors be combined?

Yes, the same boiler can serve several circuits. A radiant floor needs cooler water than a coil: the system design takes this into account, and we do it during the estimate.

What current should be planned for?

Thermo 2000 lists 108.3 A for this 240 V three-phase model. The electrician sizes the protection and conductors from that value.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 45 kW VoltMax for your hydro-air system, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom