THERMO 2000 VoltMax SCR VOLTSCR24054P3 Commercial Electric Boiler | 54 kW - 240V 3 Phase

In stock

The 240 V three-phase VoltMax 54 is a Thermo 2000 commercial electric boiler that can be run over BACnet IP or MS-TP from the building management system.

Model numberVOLTSCR24054P3

BACnetIP and MS-TP, plus Ethernet port
54 kW184,248 BTU/h on 240 V three phase
129.9 Acurrent published by Thermo 2000
240 V · three phaseCSA C22.2 No. 165 · UL 834Outdoor sensor includedCirculator and expansion tank to plan for
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR24054P3
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 54-240-3 PH
Output54 kW (184,248 BTU/h)
Power supply240 V, 3 ph, 60 Hz
Current129.9 A
CommunicationBACnet IP / MS-TP

54 kW on 240 V three phase, run directly by your building management system

A commercial boiler to integrate, not just to connect

In a commercial or institutional building, the boiler is part of a whole: ventilation, occupancy schedules, alarms, central setpoints. Thermo 2000’s VoltMax 54 was designed to fit into it. Its Schneider Electric controller communicates over BACnet IP or MS-TP with the building management system, and can also take its setpoint and output from a 0-10 Vdc signal.

This model runs on 240 V three phase and produces 54 kW, or 184,248 BTU/h according to the manufacturer. It heats the water loop that serves radiant floors, radiators or the coils of a hydro-air system, and can supply an indirect water heater through its second setpoint.

The data a designer needs

  • Current of 129.9 A on 240 V three phase, 60 Hz.
  • SCR modulation from 0 to 100% by solid-state relay, complemented by rotating relay stages.
  • Setpoint from 50 °F to 200 °F (10 °C to 93 °C), reset by the included outdoor sensor.
  • Four 1 1/2 in male NPT side connections; 3/4 in female NPT relief valve and drain.
  • 11 US gal (41.6 L) of water, 310 lb (141 kg).
  • Standards listed in the specification: CSA C22.2 No. 165-92 and UL 834, CSA B-51-14 tank, CRN, ASME Section IV “H”.

Its place in a Quebec building

Quebec winters vary a lot from one week to the next. With the outdoor sensor, water temperature rises when the cold sets in and comes back down in mild weather, instead of staying at maximum all winter. The boiler is vertical and compact: Thermo 2000 requires 3 in of clearance on the sides and back, 24 in at the front and 32 in above, which makes it easier to install in an existing mechanical room during a renovation.

The Incoloy immersion elements are replaceable. The manufacturer describes the unit as quiet, clean and low-maintenance, an advantage in an occupied building.

AirGreen’s installation

We start with a free on-site estimate: water loop, electrical service, mechanical room, connection point to the management system. The written quote that follows specifies the circulator and expansion tank, which are not among the supplied parts, and the low water cut-off, offered as an option at 54 kW.

Our technicians then install the boiler, connect it to the loop and the electrical supply, mount the outdoor sensor, fill and purge the system, then set up the controller. We leave the boiler ready to be connected to the building’s BACnet network by the integrator in charge.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work. Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Let’s move on to your project

We work in Montreal, Laval, Longueuil, on the North Shore and on the South Shore. Ask for a free estimate and a written quote; financing is available.

01 · What it is for

A boiler to integrate with the building management system

The VoltMax 54 heats the hot-water loop of a building with a 240 V three-phase supply. Its Schneider Electric controller exchanges data with the building management system over BACnet IP or MS-TP, or takes a setpoint and output through a 0-10 Vdc signal.

  • Commercial or institutional buildings with a central management system
  • Renovating an electric boiler room in a 240 V three-phase building
  • Radiant floors, radiators or hydro-air coils
  • An indirect water heater controlled by a second setpoint
BACnet IP / MS-TPThe controller communicates with the building management system and offers a web page and email alarms through its Ethernet port.
CSA and UL certifiedCSA C22.2 No. 165-92 and UL 834 (CSA mark for Canada and the U.S.), CSA B-51-14 tank, CRN registration and ASME Section IV “H”.
Solid-state relaySCR modulation from 0 to 100% limits peak power demand, according to Thermo 2000.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR, configuration A (22.5 to 90 kW)
Manufacturer designationVOLTMAX SCR 54-240-3 PH
TypeCommercial hot-water electric boiler with SCR modulation
Output54 kW
Output in BTU/h184,248 BTU/h
Power supply240 VAC, 60 Hz, three phase
Current129.9 A
Heating elementsImmersion type, Incoloy, replaceable
ModulationSCR from 0 to 100% (solid-state relay) and relay stages, with stage rotation
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French or English
CommunicationBACnet IP / MS-TP, Ethernet port with web page and email alarms
External controlSetpoint and output by 0-10 Vdc signal
Outdoor sensorIncluded (outdoor temperature reset)
Domestic hot waterPump contact with or without priority, 2nd setpoint for an indirect water heater
Low water cut-offOptional on this size (standard above 60 kW)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0 in
Weight310 lb (141 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR24054P3
03 · Before installing

What to know before installing

  • 240 V three-phase, 60 Hz power supply and a current of 129.9 A according to Thermo 2000.
  • The circulator and expansion tank are not on the list of supplied parts; they are selected for the loop.
  • At 54 kW, the low water cut-off is optional; it is standard above 60 kW.
  • Required clearances: 3 in on the sides and back, 24 in at the front, 32 in above, none below the unit.
  • Weight: 310 lb (141 kg), with 11 US gal of water in the unit once filled.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • On/off control switch
  • Control and power fuses and breakers
  • SCR relay
  • 2 limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Which protocols does the controller support?

BACnet IP and BACnet MS-TP. The Ethernet port also gives access to a web page and sends alarms by email, and the setpoint or output can follow a 0-10 Vdc external signal.

What current should be planned for?

Thermo 2000 publishes 129.9 A for this model on 240 V three phase. We size the breaker and conductors from that value and from the capacity of the electrical service.

Which standards does the boiler meet?

According to Thermo 2000’s specification: CSA C22.2 No. 165-92 and UL 834 (CSA mark for Canada and the U.S.), a tank compliant with CSA B-51-14, CRN registration and the ASME Section IV “H” stamp.

Can it give priority to domestic hot water?

Yes. The controller has a pump contact with or without domestic hot water priority, and a second setpoint for an indirect water heater.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 240 V three-phase VoltMax 54, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.