THERMO 2000 BTH Ultra 600 13 Electric Boiler | 13 kW - 600V

In stock

The Thermo 2000 BTH ULTRA 13 is a 13 kW commercial wall-mounted electric boiler at 600 V three phase, designed for new installations as well as replacements.

Model numberBTH ULTCA 600 13

13 kWat 600 V (44,356 BTU/h)
12.5 Aat 600 V, 20 A breaker
3 US galof water in the boiler
600 V · three phaseCommercial versionReplacement or new
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberBTH ULTCA 600 13
ManufacturerThermo 2000
Output13 kW at 600 V (44,356 BTU/h)
Power supply600 V, 3 phase, 60 Hz
Current12.5 A
Breaker20 A
Water connections1 1/4 in female NPT

Replace your commercial boiler with a 13 kW, 600 V BTH ULTRA

A replacement boiler for commercial and institutional buildings

In many office buildings, community halls and institutional spaces, hot water heating relies on an electric boiler installed long ago. When it reaches the end of its life, Thermo 2000’s BTH ULTRA 13 offers a simple replacement: a 13 kW wall-mounted boiler, or 44,356 BTU/h, that connects to the building’s 600 V three-phase supply.

It belongs to the commercial BTH ULTRA line, offered at 480 V and 600 V three phase. Thermo 2000 designs it for commercial and institutional applications, in new construction as well as replacement, to supply radiant floors, radiators or hot water baseboards. It can also back up a heat pump or a geothermal system.

What to know before replacing

The first check is the voltage. This version is designed for 600 V three phase, with 347 V elements. It draws 12.5 A, and Thermo 2000 lists a 20 A breaker and copper wire gauge 12 or aluminum gauge 10. If your building is supplied at 480 V, the line includes a version for that voltage.

The second check is the piping. The boiler connects with 1 1/4 in female NPT fittings, and the two supplied reducers help adapt it to the existing loop. Wall-mounted, it weighs 75 lb and holds 3 US gallons of water. Its three elements run on a single stage.

Modern controls for an older system

Replacement is a chance to modernize the controls. The T2 UltraSmart controller sets the water temperature from the supplied outdoor sensor, on one of three curves (MIN, STD, MAX), and rests the boiler in warm weather. Presets by distribution system, the backlit display, Boost mode, pump purge and the 24 V supply for the thermostat make day-to-day management simpler. Two high limits, automatic at 208 °F and manual at 227 °F, protect the unit.

What AirGreen’s installation covers

After a free on-site estimate, you receive a written quote that describes removing the old boiler, installing the new one and the 600 V electrical connection. Our technicians then carry out the work, fill and purge the loop, and set the controller for the building. Thermo 2000 covers the tank for 15 years and electrical and mechanical components for 2 years, according to its commercial manual.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work.

Let’s plan the replacement

We work in Montreal, Laval, Longueuil, on the South Shore and on the North Shore.

Ask for your free estimate and a written quote for your building; financing is available.

01 · What it is for

Replacing or adding a boiler in a 600 V building

The BTH ULTRA 13 belongs to the commercial BTH ULTRA line, offered at 480 V and 600 V three phase. Thermo 2000 designs it for commercial and institutional applications, in new construction or replacement, with radiant floors, radiators or hot water baseboards.

  • Replacing a commercial electric boiler at the end of its life
  • Community hall or institutional space heated by radiators
  • Offices heated by hot water baseboards
  • Backup for a heat pump or a geothermal system
600 V connection347 V elements on a three-phase supply: 12.5 A, 20 A breaker, suggested wire copper 12 or aluminum 10.
Dual high limitsAutomatic limit at 208 °F (98 °C) and manual limit at 227 °F (108 °C).
T2 UltraSmart controllerSupplied outdoor sensor, three curves (MIN, STD, MAX), warm weather shutdown and presets by distribution system.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
Thermo 2000 designationBTH ULTRA 13 (commercial, 600 V three phase)
TypeWall-mounted electric hot water boiler
Output13 kW (44,356 BTU/h)
Power supply600 VAC, 60 Hz, three phase (347 V elements)
Current12.5 A
Breaker20 A
Suggested wire gaugeCu 12 / Al 10
Heating elements3
Stages1
Water volume3 US gal
Water connections1 1/4 in female NPT (return and supply)
Temperature range50 °F to 190 °F (10 °C to 90 °C)
High limitsAutomatic 208 °F (98 °C); manual 227 °F (108 °C)
Maximum working pressure30 psi (207 kPa)
Weight75 lb
ControlsT2 UltraSmart controller: backlit display, presets by distribution system, water temperature based on the outdoor sensor (MIN, STD, MAX curves), warm weather shutdown, Boost mode, pump purge, 24 V for thermostat and accessories
Manufacturer warrantyTank: 15 years; electrical and mechanical components: 2 years
Model numberBTH ULTCA 600 13
03 · Before installing

What to know before installing

  • 600 VAC three-phase, 60 Hz power supply (347 V elements): 12.5 A, 20 A breaker, suggested wire copper 12 or aluminum 10.
  • This size has three elements and runs on a single stage.
  • 75 lb wall-mounted boiler, 1 1/4 in female NPT connections; two reducers supplied to adapt to existing piping.
  • Maximum working pressure of 30 psi (207 kPa); 30 psi relief valve supplied.
In the box
  • 30 psi relief valve
  • Drain valve
  • 2 reducers
  • Outdoor sensor
  • Temperature and pressure gauge
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can it replace an old commercial boiler?

Yes. Thermo 2000 designs the BTH ULTRA for new installations as well as replacements. We first check that the building is supplied at 600 V three phase; its 1 1/4 in connections and the two supplied reducers make it easier to adapt to the existing piping.

Which breaker and wire does it need?

Thermo 2000 lists a 20 A breaker and copper wire gauge 12 or aluminum gauge 10. The unit draws 12.5 A at 600 V.

Is there a version for a 480 V building?

The commercial BTH ULTRA line is offered at 480 V and 600 V three phase. We choose the version that matches the voltage on your electrical service.

How is the boiler protected against overheating?

By an automatic limit at 208 °F (98 °C) and a manual limit at 227 °F (108 °C). The 30 psi relief valve protects the loop against overpressure.

What warranty does Thermo 2000 offer?

The commercial manual provides 15 years on the tank and 2 years on electrical and mechanical components.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 13 kW, 600 V BTH ULTRA, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.