Home / Comparisons / 12,000 BTU wall heat pumps
SENVILLE LETO and SENVILLE AURA R454B: what the cold-weather certificate shows
Two 12,000 BTU SENVILLE wall units, both on R-454B and 208/230 V. Their AHRI certificates do not stop at the same place: the last point published by NEEP is at −15 °C for the LETO and at −30 °C for the AURA. This page shows what each record contains, point by point, and what the ENERGY STAR criteria require for the “cold climate” designation.
SENVILLELETO 12,000 BTU, 220 V
SENL-12CD220-ILL / SENL-12CD220-OL · AHRI 215735289
Also offered in 115 V, under another certificate (AHRI 215735287).
View the product pageNEEP certified points, warmest to coldest.
SENVILLEAURA R454B 12,000 BTU
SENA-12HF-IGG / SENA-12HF-OG · AHRI 215735296
Same NEEP certified values as the MIDEA28, the DIRECT AIR HEAT XTREME PRO R-454B and the BOSCH MAX PERFORMANCE R-454B.
View the product pageWhat the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the point of reference.
How this amount is calculated
- Heat needed over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (the “Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air conditioning calculator, with the seasonal SEER2 efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one offered by Hydro-Québec’s calculators. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.
The winter gap comes from the certified HSPF2 Region V: 7.0 for the LETO, 8.0 for the AURA. This seasonal coefficient already accounts for cold days and the electric backup assumed by the standard.
Two NEEP records on the same temperature scale
Move the thermometer down. At every temperature where NEEP publishes a point, it appears on the chart. Below −15 °C, the LETO record has no more points: its last point stays on screen, with the range SENVILLE advertises. The AURA record adds one at −30 °C.
ENERGY STAR “cold climate” criteria, line by line
Thresholds published by ENERGY STAR for a non-ducted split heat pump; values from each unit’s AHRI certificate, read on NEEP. Yellow tick: the threshold.
This grid restates the criteria published by ENERGY STAR. The certification itself is granted by ENERGY STAR, which also requires a controls verification at −15 °C; the result is the one shown in the NEEP records and the directory above.
Below −15 °C: every published number, at its exact temperature
At −15 °C, both records have a certified point: 8,000 BTU/h maximum for the LETO, 11,500 for the AURA. Lower down, only the AURA has one, at −30 °C. In between, the page shows the range of the two published values, without calculating anything between them.
What SENVILLE writes for each, group by group
LETO: manufacturer’s page SENL-12CD/220 (senville.ca). AURA: manufacturer’s page SENA-12HF (senville.com). The two pages do not describe the same things: when a page is silent, the card says so.
LETO : “heating down to −15 °C (5 °F)”.
AURA : heating down to −30 °C (−22 °F); minimum outdoor heating temperature −30 °C in the specification table.
LETO : remote control; control through Alexa and the app, multi-room management.
AURA : wireless remote, voice control and the Alexa app through an included USB kit.
LETO : dehumidification, fan, Turbo and Sleep mode.
AURA : cooling, heating, dehumidification and fan.
LETO : not published on the manufacturer’s page.
AURA : built-in self-diagnosis and refrigerant leak detection.
LETO : “DC inverter” technology.
AURA : not described on the page; the specification table gives a heating range of 4,000 to 14,500 BTU/h.
LETO : 22.5 dB at low speed; Sleep mode.
AURA : 24 dB at the lowest setting.
LETO : 1.5 L/h.
AURA : 1.4 L/h.
LETO : not certified per NEEP; the manufacturer’s page does not mention it.
AURA : certified, with the cold climate designation (NEEP and the ENERGY STAR directory).
LETO : pre-charged for 25 ft; 16 ft installation kit.
AURA : pre-charged for 25 ft; 16, 25 or 50 ft kits, the last one requiring refrigerant added on site.
Four fan speeds each, published the same way
SENVILLE publishes both indoor units at four speeds (Turbo, high, medium, low) and one value for each outdoor unit. The pages do not describe the measurement conditions.
How to read these numbers. The decibel measures a noise level: the lower the number, the quieter the unit. Each dot is a published fan speed, from slowest to fastest.
Why this is not a ranking. The airflows are not the same: 359 CFM in Turbo for the LETO, 530 for the AURA. A fan that moves more air is usually louder at its top speed, and the measurement distance is not published.
Indoor unit, in the room
The four published speeds
Outdoor unit, outside
One published value per unit
Measurements taken by each manufacturer using its own method: read them separately, not as a ranking.
On the wall and outside: widths, weights, wiring
Indoor units, photos at the same width scale




Widths published by SENVILLE. The comparison only accounts for the cabinet width: the side clearance to allow is in the installation manual and is confirmed during the visit.
Outdoor units seen from the front, scale drawing
Drawing: cabinets drawn at the same scale from the published dimensions (width × height). The AirGreen product-page photos of both models show the same outdoor-unit illustration; the drawing gives each one’s own dimensions and weight.
| Installation | LETO | AURA R454B |
|---|---|---|
| Indoor unit W × H × D, weight | 31.57 × 11.69 × 7.44 in, 19.4 lb | 33.4 × 11.76 × 9.18 in, 24.25 lb |
| Outdoor unit W × H × D, weight | 30.12 × 21.85 × 11.93 in, 59.08 lb | 30.31 × 21.65 × 12.20 in, 82.67 lb |
| Precharged length | 25 ft | 25 ft |
| Maximum piping length | Not published by the manufacturerNot on the product page consulted. | Not published by the manufacturerNot on the product page consulted. |
| Maximum height difference | Not published by the manufacturer | Not published by the manufacturer |
| Refrigerant charge | Not published by the manufacturer | R-454B, 40.92 oz |
| Electrical protectionAccording to the manufacturer | MCA 13 A; maximum fuse 15 A | MCA 12 A; maximum fuse 15 A |
| Heating capacity min. / max., per the manufacturerPublished range, no test temperature stated | 2,400 / 12,200 BTU/h | 4,000 / 14,500 BTU/h |
| Cooling capacity min. / max., per the manufacturer | 1,700 / 13,300 BTU/h | 3,500 / 13,500 BTU/h |
| Indoor airflow, Turbo / high / medium / low | 359 · 306 · 206 · 144 CFM | 530 · 410 · 320 · 240 CFM |
| Dehumidification | 1.5 L/h | 1.4 L/h |
| Advertised heating range | Down to −15 °C (5 °F) | Down to −30 °C (−22 °F) |
SENVILLE, SENL-12CD/220 page (senville.ca) and SENA-12HF page (senville.com), accessed November 10, 2026. Airflows are rounded to the CFM (LETO: 359.0 / 306.1 / 206.0 / 144.2). Clearances around the outdoor unit are not on these pages: they are in the installation manual and are checked during the visit.
What people ask about these two SENVILLE units
Why doesn't the LETO carry the “cold climate” designation?
Its NEEP record shows “no” for ENERGY STAR and for cold climate. On the published criteria, two certificate values are below the threshold: at −15 °C, its maximum capacity of 8,000 BTU/h is 67% of its rated capacity at 8.3 °C, against a 70% threshold; its EER2 is 10.8, against a basic threshold of 11.0. Its COP at −15 °C (1.91), its HSPF2 and its SEER2 are above the thresholds.
And below −15 °C, with the LETO?
SENVILLE lists the LETO’s heating “down to −15 °C” and publishes nothing lower down; neither does NEEP. The page therefore shows its last point, 8,000 BTU/h at −15 °C, without extending the curve. For the AURA, NEEP certifies a point at −30 °C: 5,900 BTU/h maximum.
At −8.3 °C, which one heats more?
At that temperature, NEEP certifies 9,300 BTU/h maximum for the LETO and 12,800 for the AURA. The COPs at maximum capacity are 2.39 and 1.75: they are two different points on each unit’s curve, to be read together with their capacity.
115 V or 220 V?
The 12,000 BTU LETO comes in 115 V and in 208/230 V, under two different certificates: 215735287 (115 V: SEER2 21.2, HSPF2 Region V 6.7) and 215735289 (220 V: SEER2 21.3, HSPF2 Region V 7.0). This page compares the 220 V version, like the AURA, offered in 208/230 V.
Does the AURA go by other names?
On NEEP, the MIDEA28 (AHRI 215471381), the DIRECT AIR HEAT XTREME PRO R-454B (216571373) and the BOSCH MAX PERFORMANCE R-454B (215223282) have the same certified values as the 12,000 BTU AURA. Each brand’s indoor units, remotes and documents may differ.
Which one costs less to run?
With the method in the “Cost per season” section, round-the-clock heating and the average price, the estimate is $437 per winter for the LETO and $382 for the AURA, against $896 with baseboards. These amounts change with the sliders; they are for comparing, not for predicting a bill.
Are they eligible for grants?
Eligibility depends on the official list in effect on the purchase date. This page promises no amount; the current list is checked when the quote is prepared.
All AHRI and NEEP values
| Certified value | LETO | AURA R454B |
|---|---|---|
| Cooling | ||
| 35 °C: min. / rated / max.BTU/h | 1,700 / 12,000 / 13,300 | 3,800 / 12,000 / 13,500 |
| SEER2 | 21.3 | 25.4 |
| EER2 | 10.8 | 13.4 |
| Heating, same conditions | ||
| HSPF2 Region IV / V | 9.1 / 7.0 | 10.5 / 8.0 |
| 8.3 °C: min. / rated / max.BTU/h | 3,500 / 12,000 / 13,400 | 3,800 / 12,000 / 16,000 |
| 8.3 °C: COP min. / rated / max. | 3.11 / 3.17 / 2.91 | 4.84 / 3.74 / 3.35 |
| −8.3 °C: min. / rated / max.BTU/h | 1,100 / 9,300 / 9,300 | 5,300 / 12,000 / 12,800 |
| −8.3 °C: COP min. / rated / max. | 1.07 / 2.39 / 2.39 | 2.22 / 2.51 / 1.75 |
| −15 °C: min. / rated / max.BTU/h | 700 / 8,000 / 8,000 | 4,100 / 11,500 / 11,500 |
| −15 °C: COP min. / rated / max. | 0.76 / 1.91 / 1.91 | 1.72 / 1.80 / 1.80 |
| Coldest point — different temperatures, not highlighted | ||
| Test temperature | −15 °C (5 °F): no colder point on the record | −30 °C (−22 °F) |
| Capacity min. / max. | 700 / 8,000 BTU/h | 2,000 / 5,900 BTU/h |
| COP at maximum capacity | 1.91 | 1.25 |
| Certifications and refrigerant | ||
| ENERGY STAR / cold climate (NEEP) | No / No | Yes / Yes |
| AHRI certificate · NEEP record | 215735289 · 385692 | 215735296 · 385685 |
| RefrigerantGWP per the IPCC (AR4); ASHRAE 34 class | R-454B · GWP 466 · A2L | R-454B · GWP 466 · A2L |
higher marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Capacities and COPs at each point are not highlighted: the order changes depending on the point.
Both are on the AirGreen website.
To choose for your home, talk to our team: bring the width of the planned wall, the outdoor location and the coldest temperature you want to cover.
Where each number comes from
Data verified on November 10, 2026. Performance: AHRI certificates and the NEEP database. Dimensions, sound, airflows, ranges and features: according to the manufacturer. When a source contradicts the AHRI certificate, the certificate prevails; this is the case of the AURA’s Canadian page, which prints EER2 and HSPF2 values different from the certificate.
Trademarks. SENVILLE, LETO, AURA and ENERGY STAR are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer for the brand; this page is not produced, sponsored or endorsed by the manufacturer.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong? Write to us: every reported figure is checked again.