THERMO 2000 VoltMax SCR VOLTSCR20823P1 Commercial Electric Boiler | 22.5 kW - 208V 1 Phase

In stock

Thermo 2000’s VoltMax SCR at 22.5 kW, 208 V single phase: a commercial electric boiler that modulates its output from 0 to 100%.

Model numberVOLTSCR20823P1

22.5 kWat 208 V single phase
0-100%SCR output modulation
11 US galof water (41.6 L)
208 V · single phaseSCR modulationCommercial boiler
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR20823P1
ManufacturerThermo 2000
DesignationVOLTMAX SCR 23-208-1 PH
Output22.5 kW
Power supply208 V, single phase, 60 Hz
Current108.4 A
Elements6 x 5 kW

22.5 kW modulated from 0 to 100% for a commercial building on 208 V single phase

What the VoltMax SCR 23-208-1 PH is

Thermo 2000’s VoltMax is an electric hot-water boiler designed for commercial, institutional and multi-unit buildings. This model, designated VOLTMAX SCR 23-208-1 PH by the manufacturer, delivers 22.5 kW on a 208 V single-phase supply. It heats the water of a loop of radiators, baseboards or radiant floor, with no GHG emissions on site.

What sets it apart is the way it measures out its output. On top of its relay stages, the VoltMax modulates its output from 0 to 100% through a solid-state relay (SCR). Rather than switching its elements on in blocks, it follows demand continuously. According to Thermo 2000, this modulation limits the peak power the boiler draws. Its six Incoloy immersion elements are replaceable, and the unit is designed to be quiet, clean and low-maintenance.

Its place in a Quebec building

It typically suits a ground-floor commercial space of a mixed-use building in Montreal, a small apartment building in Laval heated by a central loop, or South Shore offices that have kept their hot-water radiators. In these buildings supplied at 208 V single phase, the VoltMax draws 108.4 A at full output: we size the protection and conductors from the unit’s nameplate.

Its vertical design needs little room. Thermo 2000 specifies clearances of 3 in at the sides and rear, 24 in at the front and 32 in above. The unit weighs 310 lb (141 kg) and holds 11 US gal of water. Its Schneider Electric controller, with a 3 in backlit display, shows alarm codes in French or English, applies outdoor reset with the included sensor and connects to a building management system over BACnet IP or MS-TP.

What AirGreen’s installation covers

We start with a free on-site estimate: existing loop, mechanical room, electrical service and the building’s needs. The written quote that follows lists the circulator and expansion tank, which are not among the supplied parts, as well as the low-water cut-off, optional at this size.

Our technicians set the boiler in place while respecting the clearances, connect it to the loop through its 1 1/2 in male NPT connections and pipe the discharge of the factory-installed relief valve. They mount the outdoor sensor, make the electrical connection under AirGreen’s RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical), then set the setpoint, between 50 °F and 200 °F, and the outdoor reset.

AirGreen is a family business established in Montreal for more than fifteen years. We also work in Longueuil and on the North Shore. Thermo 2000 warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Let’s plan your project

Building manager or owner, ask for a free estimate: you will receive a written quote, and financing is available to spread out your payments.

01 · What it is for

Hot-water heating for a commercial or multi-unit building

The VoltMax SCR heats the water of a hydronic loop: radiators, hot-water baseboards or radiant floor. Thermo 2000 designs it for commercial, institutional and multi-unit buildings, with solid-state output modulation.

  • Commercial space or offices heated by a hot-water loop
  • Small apartment building with a central boiler
  • Building connected to a building automation system (BACnet)
  • Replacing a commercial electric boiler at the end of its life
SCR modulation from 0 to 100%The solid-state relay adjusts output continuously, on top of the relay stages; Thermo 2000 says this limits peak power demand.
Compact vertical designClearances of 3 in at the sides and rear, 24 in at the front and 32 in above, according to the manufacturer.
Replaceable Incoloy elementsSix Incoloy immersion elements (6 x 5 kW) that can be replaced during maintenance.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 23-208-1 PH
TypeCommercial electric hot-water boiler, SCR modulation
Output22.5 kW
Power supply208 VAC, 60 Hz, single phase
Current108.4 A
Heating elements6 x 5 kW, Incoloy immersion, replaceable
ModulationSCR 0 to 100% (solid-state relay) and relay stages
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT (4 side connections)
Relief valve and drain connections3/4 in female NPT
Temperature setpoint50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD: SCR modulation, stage rotation, outdoor reset, pump contact with or without domestic hot water priority, 2nd setpoint for an indirect water heater, alarm codes, °C/°F, French and English
CommunicationBACnet IP / MS-TP · Ethernet port (web page, email alarms) · external 0-10 Vdc signal (setpoint and output)
Outdoor sensorIncluded
Low-water cut-offOptional at this size (standard above 60 kW)
ClearancesSides 3 in · rear 3 in · front 24 in · top 32 in · floor 0 in
Weight310 lb (141 kg)
Manufacturer configurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR20823P1
03 · Before installing

What to know before installing

  • Commercial boiler: 208 V single-phase, 60 Hz supply, drawing 108.4 A. Protection and conductors are sized from the unit’s nameplate.
  • The low-water cut-off is optional at this size; it is standard above 60 kW.
  • The circulator and the expansion tank are not on the list of supplied parts.
  • Clearances to respect: sides 3 in, rear 3 in, front 24 in, top 32 in, floor 0 in.
  • The unit weighs 310 lb (141 kg) and holds 11 US gal of water: plan for a floor that carries this load.
In the box
  • Schneider Electric controller with backlit LCD
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relay
  • Two high-limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

What does SCR modulation bring?

The solid-state relay (SCR) varies the output from 0 to 100% instead of only switching elements on in blocks. Thermo 2000 says this modulation limits the peak power the boiler draws.

Why is the model called 23 when it delivers 22.5 kW?

The number 23 is Thermo 2000’s model designation (VOLTMAX SCR 23-208-1 PH). The output the manufacturer publishes at 208 V is 22.5 kW.

What electrical supply is needed?

A 208 V single-phase, 60 Hz supply able to deliver 108.4 A. We size the protection and conductors from the unit’s nameplate.

Can it connect to our building management system?

Yes. The controller communicates over BACnet IP or MS-TP, accepts an external 0-10 Vdc signal for setpoint and output, and its Ethernet port gives access to a web page and email alarms.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 22.5 kW VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.