THERMO 2000 VoltMax SCR VOLTSCR20827P1 Commercial Electric Boiler | 27 kW - 208V 1 Phase

In stock

Thermo 2000’s VoltMax SCR at 27 kW, 208 V single phase: a commercial electric boiler that heats the building and can feed an indirect water heater.

Model numberVOLTSCR20827P1

27 kWat 208 V single phase
6 x 6 kWreplaceable Incoloy elements
130.1 Acurrent at full output
208 V · single phase2nd hot-water setpointCommercial boiler
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR20827P1
ManufacturerThermo 2000
DesignationVOLTMAX SCR 27-208-1 PH
Output27 kW
Power supply208 V, single phase, 60 Hz
Current130.1 A
Water volume11 US gal (41.6 L)

27 kW to heat a building supplied at 208 V single phase, and its hot water if needed

One boiler, two uses

In many small buildings in Montreal and Laval, a single mechanical room serves both the heating of the units and the hot water at the taps. Thermo 2000’s VoltMax SCR 27-208-1 PH is designed for this kind of building. It delivers 27 kW to a loop of radiators, baseboards or radiant floor, and its controller provides a 2nd setpoint for an indirect water heater, with a pump contact that can give priority to domestic hot water.

Thermo 2000 intends it for commercial, institutional and multi-unit buildings. All the heat is electric, with no GHG emissions on site, and the manufacturer highlights a quiet, clean, low-maintenance unit.

What the VoltMax SCR 27-208-1 PH brings

Its six 6 kW Incoloy immersion elements are replaceable. They are driven by relay stages and by a solid-state relay (SCR) that modulates output from 0 to 100%, which, according to Thermo 2000, limits peak power demand. The setpoint ranges from 50 °F to 200 °F (10 °C to 93 °C), and the included outdoor sensor allows weather-based reset.

The Schneider Electric controller shows its alarm codes in French or English on a 3 in backlit display. For a building managed remotely, it offers BACnet IP or MS-TP, an external 0-10 Vdc control, an Ethernet port with a web page and email alarms.

Electrical and space: the points to confirm

On a 208 V single-phase supply, the boiler draws 130.1 A at full output. That is a large load for a single phase: we check the building’s electrical service and size the protection and conductors from the nameplate. The vertical design, for its part, needs little room: 3 in at the sides and rear, 24 in at the front and 32 in above. The unit weighs 310 lb (141 kg) and holds 11 US gal of water.

Our work on site

It all starts with a free on-site estimate and a written quote. The quote includes the circulator, the expansion tank and, if you want domestic hot water, the indirect water heater, since none of them are among the supplied parts. It also covers the low-water cut-off, optional at this size.

Our technicians install the boiler, connect it through its 1 1/2 in male NPT connections, pipe the discharge of the factory-installed relief valve and mount the outdoor sensor. The electrical connection is made under AirGreen’s RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). We then set both setpoints and the hot-water priority.

AirGreen is a family business established in Montreal for more than fifteen years, also installing in Longueuil, on the South Shore and on the North Shore. Thermo 2000 warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Let’s talk

Ask for a free estimate for your building: the quote is in writing, and financing is available to spread out your payments.

01 · What it is for

Space heating and hot water for a building, from a single boiler

The VoltMax SCR heats a loop of radiators, baseboards or radiant floor, and its controller provides a 2nd setpoint for an indirect water heater. Thermo 2000 designs it for commercial, institutional and multi-unit buildings.

  • Apartment building with a central loop and an indirect water heater
  • Retail or offices heated by hot-water radiators
  • Small institutional building supplied at 208 V single phase
  • Replacing a commercial electric boiler on an existing loop
Heating and hot waterA 2nd setpoint for an indirect water heater and a pump contact with or without domestic hot water priority.
Six 6 kW elementsReplaceable Incoloy immersion elements, driven by the 0 to 100% SCR relay and relay stages.
Setpoint up to 200 °FAdjustable setpoint from 50 °F to 200 °F (10 °C to 93 °C), with outdoor reset from the included sensor.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 27-208-1 PH
TypeCommercial electric hot-water boiler, SCR modulation
Output27 kW
Power supply208 VAC, 60 Hz, single phase
Current130.1 A
Heating elements6 x 6 kW, Incoloy immersion, replaceable
ModulationSCR 0 to 100% (solid-state relay) and relay stages
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT (4 side connections)
Relief valve and drain connections3/4 in female NPT
Temperature setpoint50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD: SCR modulation, stage rotation, outdoor reset, pump contact with or without domestic hot water priority, 2nd setpoint for an indirect water heater, alarm codes, °C/°F, French and English
CommunicationBACnet IP / MS-TP · Ethernet port (web page, email alarms) · external 0-10 Vdc signal (setpoint and output)
Outdoor sensorIncluded
Low-water cut-offOptional at this size (standard above 60 kW)
ClearancesSides 3 in · rear 3 in · front 24 in · top 32 in · floor 0 in
Weight310 lb (141 kg)
Manufacturer configurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR20827P1
03 · Before installing

What to know before installing

  • Commercial boiler: 208 V single-phase, 60 Hz supply, drawing 130.1 A. Protection and conductors are sized from the nameplate.
  • The indirect water heater, circulator and expansion tank are not among the supplied parts.
  • Low-water cut-off: optional at this size, standard above 60 kW.
  • Required clearances: sides 3 in, rear 3 in, front 24 in, top 32 in, floor 0 in.
  • The unit weighs 310 lb (141 kg) and holds 11 US gal of water.
In the box
  • Schneider Electric controller with backlit LCD
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relay
  • Two high-limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

How does the boiler handle domestic hot water?

With an indirect water heater connected to the loop. The controller provides a 2nd setpoint for that water heater and a pump contact with or without domestic hot water priority. The indirect water heater is added to the quote.

What electrical supply is needed?

208 V single phase, 60 Hz, able to deliver 130.1 A. We size the protection and conductors from the nameplate and check the building’s electrical service.

Can the elements be replaced?

Yes. Thermo 2000 uses replaceable Incoloy immersion elements. This model has six 6 kW elements.

How much room is needed in the mechanical room?

Thermo 2000 requires 3 in at the sides and rear, 24 in at the front and 32 in above, and no clearance to the floor. Also plan room for the circulator, the expansion tank and, if applicable, the indirect water heater.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 27 kW VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.