THERMO 2000 VoltMax SCR VOLTSCR20836P1 Commercial Electric Boiler | 36 kW - 208V 1 Phase

In stock

The 208 V single-phase VoltMax 36 brings 36 kW of hot water heating to buildings without a three-phase service, with SCR modulation from 0 to 100%.

Model numberVOLTSCR20836P1

36 kWat 208 V single phase
173.4 Acurrent published by Thermo 2000
8 elementsIncoloy immersion, replaceable
208 V · single phaseEmail alarmsElectrical service to check
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR20836P1
ManufacturerThermo 2000
Output36 kW
Power supply208 V, single phase, 60 Hz
Current173.4 A
Elements8 x 6 kW (element rating)
ModulationSCR, 0 to 100%

A 36 kW commercial boiler for buildings supplied at 208 V single phase

When the building has no three phase

In several Montreal neighbourhoods, mixed-use buildings, with a store on the ground floor and apartments above, are supplied at 208 V without three phase. Thermo 2000’s VoltMax 36 comes in a single-phase version for these buildings. It delivers 36 kW and draws 173.4 A, with the same SCR modulation as the series’ three-phase models.

It is a commercial and institutional hot water electric boiler from configuration A (22.5 to 90 kW). It heats the water of a closed loop that feeds radiators, radiant floors or ventilation coils, and can also serve an indirect water heater.

Electricity first

At 173.4 A, the electrical service decides the project. Before proposing this boiler, we check the capacity of the service and panel, the room for conductors and the dedicated circuit. If the building has three phase, a three-phase VoltMax version can also be considered; we compare the options with you.

Once connected, the boiler does not draw all its power at once. SCR solid-state relays vary it from 0 to 100%, and Thermo 2000 points out that this modulation limits peak power demand. The controller rotates the stages, sharing the work among the 8 Incoloy immersion elements. These elements, each rated at 6 kW, are replaceable.

A controller that warns you

The Schneider Electric controller shows its alarm codes on a 3 in backlit LCD, in French or English. Its Ethernet port gives access to a web page and sends alarms by email: a property manager who does not live on site is alerted without waiting for a tenant’s call. The included outdoor sensor adjusts the water temperature to the weather, within a 50 °F to 200 °F setpoint range. For a building run by a central system, the controller communicates over BACnet IP or MS-TP and accepts a 0-10 Vdc signal.

Installation by AirGreen

We work in Montreal, Laval, Longueuil, on the North Shore and on the South Shore. The on-site estimate is free and the quote is in writing. It includes the circulator and expansion tank chosen for your loop, since they are not among the parts supplied by Thermo 2000.

We position the boiler with 24 in in front for service and 32 in above, connect it through its 1 1/2 in NPT connections, mount the outdoor sensor and make the electrical connection. We then fill the loop, purge it and program the controller with you. AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work. Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Your 208 V single-phase project

To find out whether your electrical service can take a 36 kW VoltMax, ask for a free estimate. You receive a written quote, and financing is available so the work can go ahead without waiting.

01 · What it is for

36 kW of hot water heat when the building only has single phase

Many Montreal buildings are supplied at 208 V without three phase. This VoltMax version lets them install a commercial boiler with SCR modulation, provided the electrical service can handle its 173.4 A.

  • Mixed-use buildings: a store on the ground floor, apartments above
  • Offices and commercial units on 208 V single phase
  • Radiator or radiant floor loops to replace or extend
  • Buildings monitored remotely by a property manager
8 replaceable Incoloy elementsIncoloy immersion elements that Thermo 2000 designs to be replaced, with stage rotation by the controller.
SCR modulation from 0 to 100%Output follows the building’s demand; according to the manufacturer, this limits peak power demand.
Email alarmsThe controller’s Ethernet port offers a web page and sends alarms by email, in addition to the codes shown on screen.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
Manufacturer designationVoltMax 36, SCR series (VOLTMAX SCR 36-208-1 PH)
TypeCommercial hot water electric boiler
Output36 kW
Power supply208 VAC, 60 Hz, single phase
Current173.4 A
Heating elements8 x 6 kW (element rating), Incoloy immersion, replaceable
ModulationSCR from 0 to 100% (solid-state relay) plus relay stages
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French/English
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
External controlSetpoint and output by 0-10 Vdc signal
Outdoor sensorIncluded (outdoor reset)
Domestic hot water2nd setpoint for an indirect water heater; pump contact with or without DHW priority
Low water cut-offOptional up to 60 kW (standard above)
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight310 lb (141 kg)
ConfigurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR20836P1
03 · Before installing

What to know before installing

  • 208 V single-phase, 60 Hz power supply. At 173.4 A, the boiler needs an electrical service with the capacity for it: we check it before any quote.
  • The 8 elements carry a 6 kW rating each; the output Thermo 2000 publishes for this model at 208 V is 36 kW.
  • The circulator and expansion tank are not on the manufacturer’s list of supplied parts: they are chosen for your loop.
  • Leave 24 in in front of the unit for service and 32 in above; 3 in is enough on the sides and at the back, no clearance underneath.
  • Low water cut-off optional on this size (standard above 60 kW).
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • Control ON/OFF switch
  • Control and power fuses and breakers
  • SCR relays
  • 2 limit controls, one automatic, one manual
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Our building has no three phase: does the VoltMax work?

Yes, this version is designed for 208 V single phase. It draws 173.4 A: we first check that the electrical service and panel can take it.

How is the boiler monitored remotely?

The Schneider Electric controller has an Ethernet port: a web page shows its status and alarms go out by email. It also communicates over BACnet IP or MS-TP with a building management system.

Can it also heat domestic water?

With an indirect water heater. The controller offers a second setpoint for that heater and a pump contact, with or without domestic hot water priority.

Can the elements be replaced?

Yes. Thermo 2000 uses replaceable Incoloy immersion elements. The manufacturer covers electrical and mechanical components for 2 years and the tank for 10 years (closed-loop heating).

What does your quote include?

The boiler, the circulator and expansion tank chosen for your loop, the hydronic and electrical connections, the outdoor sensor and commissioning with controller programming.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

36 kW on 208 V single phase, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.