THERMO 2000 VoltMax SCR VOLTSCR20823P3 Commercial Electric Boiler | 22.5 kW - 208V 3 Phase

In stock

Thermo 2000’s VoltMax SCR at 22.5 kW, 208 V three phase: a commercial electric boiler with SCR modulation, ready for building management.

Model numberVOLTSCR20823P3

76,770 BTU/h22.5 kW at 208 V three phase
62.6 Acurrent at full output
BACnetIP and MS-TP, Ethernet port
208 V · three phaseBACnet IP / MS-TPOutdoor sensor included
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR20823P3
ManufacturerThermo 2000
DesignationVOLTMAX SCR 23-208-3 PH
Output22.5 kW (76,770 BTU/h)
Power supply208 V, three phase, 60 Hz
Current62.6 A
ModulationSCR 0 to 100%

A 22.5 kW boiler your building manager can monitor remotely

Which buildings it is for

Thermo 2000’s VoltMax SCR 23-208-3 PH is meant for commercial, institutional and multi-unit buildings supplied at 208 V three phase. It delivers 22.5 kW, or 76,770 BTU/h according to the manufacturer, to a loop of radiators, hot-water baseboards or radiant floor. Everything is electric: no GHG emissions on site, quiet and clean operation, and replaceable Incoloy immersion elements.

Think of an apartment building in Montreal heated by a central loop, offices in Longueuil or an institutional building in Laval already connected to a building automation system.

Connected to the building: BACnet, Ethernet and 0-10 Vdc

The Schneider Electric controller, with its 3 in backlit display, is this model’s strong point for a building manager. It communicates with the building management system over BACnet IP or MS-TP. It accepts an external 0-10 Vdc signal to set the temperature setpoint and the output. Its Ethernet port gives access to a web page and sends alarms by email: you know a boiler is in fault before the tenants call.

The same controller handles the 0 to 100% SCR modulation, rotation of the relay stages, outdoor reset with the included sensor and schedules. It also provides a 2nd setpoint for an indirect water heater and a pump contact with or without domestic hot water priority.

208 V three phase: what we check

On three phase, the boiler draws 62.6 A at full output. We size the protection and conductors from the nameplate, and we confirm the building’s electrical service has the required capacity. As for space, the vertical design needs little room: 3 in at the sides and rear, 24 in at the front and 32 in above, according to Thermo 2000. The unit weighs 310 lb (141 kg) and holds 11 US gal of water.

AirGreen’s installation

After a free on-site estimate, you receive a written quote. It includes the circulator and expansion tank, which are not on the list of supplied parts, and the low-water cut-off, optional at this size. Our technicians connect the boiler to the loop through its 1 1/2 in male NPT connections, pipe the discharge of the factory-installed relief valve and mount the outdoor sensor. The electrical connection is made under AirGreen’s RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). At start-up, we set the setpoint, between 50 °F and 200 °F, and prepare the link with your management system.

AirGreen is a family business established in Montreal for more than fifteen years, working on the South Shore and the North Shore. Thermo 2000 warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Next step

Send us your building’s details or ask for a free estimate: you will receive a written quote, and financing is available to spread out your payments.

01 · What it is for

A commercial boiler you can control and monitor remotely

The VoltMax SCR heats the water of a loop of radiators, baseboards or radiant floor in a commercial, institutional or multi-unit building. Its controller communicates with the building management system and sends its alarms by email.

  • Multi-unit building with a central heating loop
  • Offices or retail supplied at 208 V three phase
  • Institutional building monitored by a building automation system
  • Space heating and an indirect water heater on the same boiler
Remote monitoringEthernet port with a web page and email alarms; BACnet IP or MS-TP for the building management system.
0-10 Vdc controlAn external 0-10 Vdc signal can set the boiler’s temperature setpoint and output.
SCR modulation from 0 to 100%Output follows demand continuously, with rotation of the relay stages.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 23-208-3 PH
TypeCommercial electric hot-water boiler, SCR modulation
Output22.5 kW
Output in BTU/h76,770 BTU/h
Power supply208 VAC, 60 Hz, three phase
Current62.6 A
Heating elementsIncoloy immersion, replaceable
ModulationSCR 0 to 100% (solid-state relay) and relay stages
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT (4 side connections)
Relief valve and drain connections3/4 in female NPT
Temperature setpoint50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD: SCR modulation, stage rotation, outdoor reset, pump contact with or without domestic hot water priority, 2nd setpoint for an indirect water heater, alarm codes, °C/°F, French and English
CommunicationBACnet IP / MS-TP · Ethernet port (web page, email alarms) · external 0-10 Vdc signal (setpoint and output)
Outdoor sensorIncluded
Low-water cut-offOptional at this size (standard above 60 kW)
ClearancesSides 3 in · rear 3 in · front 24 in · top 32 in · floor 0 in
Weight310 lb (141 kg)
Manufacturer configurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR20823P3
03 · Before installing

What to know before installing

  • Commercial boiler: 208 V three-phase, 60 Hz supply, drawing 62.6 A. We size the protection and conductors from the nameplate.
  • The low-water cut-off is optional at this size (standard above 60 kW).
  • The circulator and the expansion tank are not among the supplied parts.
  • Clearances: 3 in at the sides and rear, 24 in at the front, 32 in above, 0 in to the floor.
  • Weight of 310 lb (141 kg), plus 11 US gal of water once filled.
In the box
  • Schneider Electric controller with backlit LCD
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relay
  • Two high-limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

How does the boiler connect to our building management system?

The Schneider Electric controller communicates over BACnet IP or MS-TP. It also accepts an external 0-10 Vdc signal that sets the temperature setpoint and the output.

Can alarms be received remotely?

Yes. The Ethernet port gives access to a web page and email alarms. On site, the backlit display shows alarm codes, in French or English.

Can it also heat an indirect water heater?

The controller provides a 2nd setpoint for an indirect water heater and a pump contact with or without domestic hot water priority. We design the connection for your building.

How does it differ from the 22.5 kW single-phase version?

The output is the same. The three-phase version spreads the load over the building’s three phases and draws 62.6 A at full output.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A three-phase 22.5 kW VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.