THERMO 2000 VoltMax SCR VOLTSCR20827P3 Commercial Electric Boiler | 27 kW - 208V 3 Phase

In stock

Thermo 2000’s VoltMax SCR at 27 kW, 208 V three phase: a commercial electric boiler that replaces an aging unit and can be driven by 0-10 Vdc.

Model numberVOLTSCR20827P3

92,124 BTU/h27 kW at 208 V three phase
75.1 Acurrent at full output
0-10 Vdcremote setpoint and output control
208 V · three phaseSCR modulation 0-100%Low-water cut-off optional
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR20827P3
ManufacturerThermo 2000
DesignationVOLTMAX SCR 27-208-3 PH
Output27 kW (92,124 BTU/h)
Power supply208 V, three phase, 60 Hz
Current75.1 A
Setpoint50 °F to 200 °F

Replace a commercial boiler with 27 kW of modulated output, on 208 V three phase

A replacement that respects what is already there

When the electric boiler of a commercial building reaches the end of its life, nobody wants to redo everything. The radiator loop works, so do the building controls; what is needed is a reliable unit at the centre. Thermo 2000’s VoltMax SCR 27-208-3 PH suits this case well. Designed for commercial, institutional and multi-unit buildings supplied at 208 V three phase, it delivers 27 kW, or 92,124 BTU/h according to the manufacturer.

It connects to the loop through four 1 1/2 in male NPT side connections, and its controller accepts an external 0-10 Vdc signal for setpoint and output. Existing controls can therefore keep running the heating. If the building has a management system, the VoltMax also communicates over BACnet IP or MS-TP.

Closely controlled output

The VoltMax combines relay stages with a solid-state relay (SCR) that modulates output from 0 to 100%. The controller alternates the stages, and according to Thermo 2000, the modulation limits peak power demand. The Incoloy immersion elements can be replaced during maintenance. The setpoint ranges from 50 °F to 200 °F, with outdoor reset from the included sensor and programmable schedules.

On 208 V three phase, the boiler draws 75.1 A at full output. We size the protection and conductors from the nameplate, taking into account what fed the old unit.

The job with AirGreen

A replacement starts with a free on-site estimate. In a Montreal building, a Longueuil store or a North Shore workshop, we look at the loop, the circulator and expansion tank in place, access to the mechanical room and the electrical supply. The unit weighs 310 lb (141 kg): delivery and handling have to be planned. The circulator and expansion tank are not among the supplied parts; if they need replacing, the written quote says so, as it does for the low-water cut-off, optional at this size.

On installation day, our technicians drain and disconnect the old boiler, set the VoltMax in place while respecting Thermo 2000’s clearances (3 in at the sides and rear, 24 in at the front, 32 in above), connect it to the loop and pipe the discharge of the factory-installed relief valve. The electrical connection is made under AirGreen’s RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). We then connect the existing control signal and set the setpoint.

AirGreen is a family business established in Montreal for more than fifteen years, also present in Laval and on the South Shore. Thermo 2000 warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Your quote

Send us the nameplate of your current boiler or ask for a free estimate: the quote is in writing, and financing is available to spread out your payments.

01 · What it is for

Replacing a commercial boiler without changing how the building is controlled

The VoltMax SCR heats a loop of radiators, baseboards or radiant floor. Its controller accepts an external 0-10 Vdc signal and communicates over BACnet: it fits into the control system already in place.

  • Replacing a commercial electric boiler at the end of its life
  • Building whose existing controls send a 0-10 Vdc signal
  • Multi-unit building heated by hot-water radiators
  • Retail space or workshop heated by a radiant floor
0-10 Vdc controlExisting controls can set the boiler’s temperature setpoint and output through an external signal.
Stage rotationThe controller alternates the relay stages, on top of the 0 to 100% SCR modulation.
Replaceable Incoloy elementsThe Incoloy immersion elements can be replaced during maintenance, according to Thermo 2000.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 27-208-3 PH
TypeCommercial electric hot-water boiler, SCR modulation
Output27 kW
Output in BTU/h92,124 BTU/h
Power supply208 VAC, 60 Hz, three phase
Current75.1 A
Heating elementsIncoloy immersion, replaceable
ModulationSCR 0 to 100% (solid-state relay) and relay stages
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT (4 side connections)
Relief valve and drain connections3/4 in female NPT
Temperature setpoint50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD: SCR modulation, stage rotation, outdoor reset, pump contact with or without domestic hot water priority, 2nd setpoint for an indirect water heater, alarm codes, °C/°F, French and English
CommunicationBACnet IP / MS-TP · Ethernet port (web page, email alarms) · external 0-10 Vdc signal (setpoint and output)
Outdoor sensorIncluded
Low-water cut-offOptional at this size (standard above 60 kW)
ClearancesSides 3 in · rear 3 in · front 24 in · top 32 in · floor 0 in
Weight310 lb (141 kg)
Manufacturer configurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR20827P3
03 · Before installing

What to know before installing

  • Commercial boiler: 208 V three-phase, 60 Hz supply, drawing 75.1 A. Protection and conductors sized from the nameplate.
  • The low-water cut-off is optional at this size; Thermo 2000 makes it standard above 60 kW.
  • Circulator and expansion tank: not on the list of supplied parts.
  • Clearances: sides 3 in, rear 3 in, front 24 in, top 32 in, floor 0 in.
  • Weight of 310 lb (141 kg) and 11 US gal of water: access to the mechanical room must allow delivery.
In the box
  • Schneider Electric controller with backlit LCD
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relay
  • Two high-limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can we keep our current control system?

Often, yes. The VoltMax accepts an external 0-10 Vdc signal for setpoint and output, and communicates over BACnet IP or MS-TP. We check your controls’ compatibility during the estimate.

Does the boiler connect to our existing loop?

It has four 1 1/2 in male NPT side connections. During the visit, we check the loop and the circulator and expansion tank in place, which are not supplied with the boiler.

What is stage rotation for?

The controller alternates the start-up order of the relay stages, which shares the work between them. SCR modulation also adjusts the output from 0 to 100%.

What electrical supply is needed?

208 V three phase, 60 Hz, for 75.1 A at full output. We size the protection and conductors from the nameplate.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A three-phase 27 kW VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.