THERMO 2000 VoltMax SCR VOLTSCR24060P1 Commercial Electric Boiler | 60 kW - 240V 1 Phase

In stock

The 240 V single-phase VoltMax 60 is a 60 kW Thermo 2000 commercial electric boiler, or 204,720 BTU/h, fitted with 10 identical 6 kW elements.

Model numberVOLTSCR24060P1

204,720 BTU/h60 kW on 240 V single phase
250 Acurrent published by Thermo 2000
10 x 6 kWreplaceable Incoloy elements
240 V · single phaseHydro-air, radiators, radiant floorOutdoor sensor includedLow water cut-off optional
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR24060P1
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 60-240-1 PH
Output60 kW (204,720 BTU/h)
Power supply240 V, 1 ph, 60 Hz
Current250 A
Elements10 x 6 kW

204,720 BTU/h of hot-water heating on a 240 V single-phase supply

A commercial boiler without three-phase power

A daycare set up in a former shop, a neighbourhood clinic, a good-sized apartment building: many buildings in Laval, on the South Shore or on the North Shore heat with hot water without having a three-phase supply. Thermo 2000’s VoltMax 60 answers that case. This model from the commercial VoltMax SCR series delivers 60 kW, or 204,720 BTU/h, from a 240 V single-phase supply.

It heats the water loop that feeds radiators, a radiant floor or the coil of a hydro-air system placed in a duct system. A second setpoint can also serve an indirect water heater for domestic hot water, with or without priority.

One boiler, flexible control

The Schneider Electric controller sets water temperature using the included outdoor sensor, within a setpoint of 50 °F to 200 °F (10 °C to 93 °C). It handles schedules, which lets you reduce heating in the evening and on weekends in a commercial space. The solid-state relay (SCR) varies output from 0 to 100% and, according to Thermo 2000, limits peak power demand.

Heating relies on 10 Incoloy immersion elements, all 6 kW. They are replaceable, and the controller rotates the order of the relay stages. The manufacturer describes the unit as quiet, clean and low-maintenance.

What the installation requires

The first point to check is electrical. Thermo 2000 publishes a current of 250 A for this model: that is a large load for a single-phase service, and we compare it with the available capacity before confirming the size. If the service is too tight, a smaller size in the series, such as the 55 kW or 48 kW VoltMax, may suit depending on the heating load.

As for space, the boiler is vertical and compact: 3 in of clearance on the sides and back, 24 in at the front, 32 in above, set directly on the floor. It weighs 310 lb (141 kg) and holds 11 US gal of water. At 60 kW, the low water cut-off remains an option, and the circulator and expansion tank are not among the supplied parts.

What our work includes

We start with a free on-site estimate, then give you a written quote that includes the boiler, the circulator, the expansion tank and the options chosen. Our technicians then install the VoltMax, connect it to the loop through its 1 1/2 in male NPT side connections, make the electrical connection, mount the outdoor sensor, fill and purge the system, then program the setpoint and schedules with you.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work. Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Get your quote

We install the VoltMax SCR in Montreal, Laval, Longueuil, on the North Shore and on the South Shore. Ask for your free estimate; you receive a written quote, and financing is available so you can go ahead without waiting.

01 · What it is for

A commercial boiler on a single-phase supply

Not every commercial building has three-phase power. The VoltMax 60 delivers 60 kW to a hot-water loop from a 240 V single-phase supply, for radiators, a radiant floor or a hydro-air coil.

  • Daycares, clinics and neighbourhood shops heated with hot water
  • Apartment buildings with a 240 V single-phase supply
  • A hydro-air coil installed in a duct system
  • Replacing an electric boiler of similar output
10 identical elementsTen replaceable 6 kW Incoloy immersion elements, run in stages that the controller rotates.
204,720 BTU/hThe output Thermo 2000 publishes for this size, on a simple 240 V single-phase supply.
Flexible controlIncluded outdoor sensor, schedules, 0-10 Vdc external signal and BACnet IP / MS-TP communication.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR, configuration A (22.5 to 90 kW)
Manufacturer designationVOLTMAX SCR 60-240-1 PH
TypeCommercial hot-water electric boiler with SCR modulation
Output60 kW
Output in BTU/h204,720 BTU/h
Power supply240 VAC, 60 Hz, single phase
Current250 A
Heating elements10 x 6 kW, immersion type, Incoloy, replaceable
ModulationSCR from 0 to 100% (solid-state relay) and relay stages, with stage rotation
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French or English, schedules
CommunicationBACnet IP / MS-TP, Ethernet port with web page and email alarms
External controlSetpoint and output by 0-10 Vdc signal
Outdoor sensorIncluded (outdoor temperature reset)
Domestic hot waterPump contact with or without priority, 2nd setpoint for an indirect water heater
Low water cut-offOptional on this size (standard above 60 kW)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0 in
Weight310 lb (141 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR24060P1
03 · Before installing

What to know before installing

  • 240 V single-phase, 60 Hz power supply and a current of 250 A according to Thermo 2000: a large load for a single-phase service, which we check first.
  • At 60 kW, the low water cut-off remains an option; Thermo 2000 installs it as standard only above 60 kW.
  • The circulator and expansion tank are not among the supplied parts.
  • Clearances: 3 in on the sides and back, 24 in at the front, 32 in above; sets directly on the floor.
  • Weight: 310 lb (141 kg), plus 11 US gal of water.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • On/off control switch
  • Control and power fuses and breakers
  • SCR relay
  • 2 limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can a single-phase electrical service supply 60 kW?

Thermo 2000 publishes a current of 250 A for this model on 240 V single phase. That is a large load: during the free estimate, we compare that value with the service capacity and the building’s other equipment before confirming the size.

Can it supply a hydro-air coil?

Yes. Hydro-air systems are among the applications of the VoltMax series, along with radiators, radiant floors and indirect water heaters.

Is the low water cut-off included at 60 kW?

No. Thermo 2000 offers it as an option up to and including 60 kW and installs it as standard above that. We specify in the quote whether your installation calls for one.

Are the heating elements all identical?

Yes: 10 replaceable 6 kW Incoloy immersion elements. The controller rotates the order of the stages.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 240 V single-phase VoltMax 60, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.