vänEE · air exchangersThe vänEE space at AirGreenSold and installed by AirGreen. Montréal, Laval, Longueuil, the South Shore and the North Shore.
The full vänEE line

vänEE · Installation

Installing a vänEE air exchanger in Greater Montréal: location, drain, outdoor hoods

Before the model comes the room it will live in. The installation guide for AI Series models V110 to V160 sets precise rules: an outlet within 6 ft, outdoor hoods at least 18 in above the ground, a room between 10 and 65 °C. Check first whether a vänEE fits your mechanical room; the rules follow, in order.

18 inminimum height above the ground, or above the expected snow depth if greater (V110 to V160 guide)
6 ftminimum between the two hoods, unless you use the combined hood (V110 to V160 guide)
8 inin front of the door for service, on the V150 and V160H75 sheets
vänEE

vänEE · Your mechanical room

Will a vänEE fit at your place?

Enter the clear space in your room; the starting sizes are an example. The tool compares it with the cabinets of the 15 AI Series models the manufacturer lists as active, turned either way, using the sizes on our product pages, except three widths set at 23 1/2 in (see the legend). For the V110 to V160, the notes come from their installation guide and spec sheets; for the V180 to V230, from their spec sheets.

Clear height
in
Clear width
in
Clear depth
in
Unit ports
A drain nearby?
Ducts already in place

15 of 15 cabinets fit the space you entered

Cabinet only, in inches: height × width × depth, to the nearest 1/16 in. Add room for the ducts, the hangers and door access: we measure it during the visit. Net airflows at 0.4 in. w.g. For the three side-port cabinets V150H75NS, V150E75NS and V160H75RS, the tool uses a 23 1/2 in width, the figure on the lineup sheet (for the V150) and the manufacturer’s pages; the spec-sheet drawing carries a 23 3/8 in dimension.

  • vänEE V150H75NSHRV · 140 cfm19 1/8 × 23 1/2 × 16 1/8 in · top ports, 5 in · 35 lbFor more than 130 cfm: 6 in ducts recommended (guide). Door: 8 in clear needed in front (spec sheet); we check which side the door is on at the visit. Width counted: 23 1/2 in (the spec-sheet drawing shows 23 3/8).
  • vänEE V150E75NSERV · 129 cfm19 1/8 × 23 1/2 × 16 1/8 in · top ports, 5 in · 37 lbFor more than 130 cfm: 6 in ducts recommended (guide). Door: 8 in clear needed in front (spec sheet); we check which side the door is on at the visit. Width counted: 23 1/2 in (the spec-sheet drawing shows 23 3/8).
  • vänEE V160H75RSHRV · 150 cfm19 1/8 × 23 1/2 × 16 1/8 in · top ports, 6 in · 35 lbDoor: 8 in clear needed in front (spec sheet); we check which side the door is on at the visit. Width counted: 23 1/2 in (the spec-sheet drawing shows 23 3/8).
  • vänEE V210E75RSERV · 206 cfm19 1/2 × 27 1/8 × 21 in · top ports, 6 in · 47 lbDrain: a fitting shows on the spec-sheet drawing; we check it at the visit.
  • vänEE V230H75RSHRV · 225 cfm19 1/2 × 27 1/8 × 21 in · top ports, 6 in · 47 lb
  • vänEE V110H65RTHRV · 100 cfm21 1/2 × 21 × 16 1/8 in · top ports, 5 in · 35 lb
  • vänEE V130H65RTHRV · 119 cfm21 1/2 × 21 × 16 1/8 in · top ports, 5 in · 35 lb
  • vänEE V130E65RTERV · 119 cfm21 1/2 × 21 × 16 1/8 in · top ports, 5 in · 37 lb
  • vänEE V150H75NTHRV · 140 cfm21 1/2 × 21 × 16 1/8 in · top ports, 5 in · 35 lbFor more than 130 cfm: 6 in ducts recommended (guide). Door: 8 in clear needed in front (spec sheet); we check which side the door is on at the visit.
  • vänEE V150E75NTERV · 129 cfm21 1/2 × 21 × 16 1/8 in · top ports, 5 in · 37 lbFor more than 130 cfm: 6 in ducts recommended (guide). Door: 8 in clear needed in front (spec sheet); we check which side the door is on at the visit.
  • vänEE V160H65RTHRV · 150 cfm21 1/2 × 21 × 16 1/8 in · top ports, 6 in · 35 lb
  • vänEE V160E75RTERV · 133 cfm21 1/2 × 21 × 16 1/8 in · top ports, 6 in · 37 lb
  • vänEE V180H75RTHRV · 193 cfm21 11/16 × 24 13/16 × 21 in · top ports, 6 in · 47 lb
  • vänEE V210E75RTERV · 206 cfm21 11/16 × 24 13/16 × 21 in · top ports, 6 in · 47 lbDrain: a fitting shows on the spec-sheet drawing; we check it at the visit.
  • vänEE V230H75RTHRV · 225 cfm21 11/16 × 24 13/16 × 21 in · top ports, 6 in · 47 lb

The vänEE shop

The vänEE air exchangers we install

The AI Series models and the older series still for sale. Pricing by quote; we confirm each model’s availability in the quote.

vänEE
Active models compared8 steps from the guideFree estimate

The installation rules

What the guide asks for, in the order we do it

From the AI Series installation guide (doc. 23831WEB, rev. X), which covers models V110 to V160. We apply it on every install of those models.

  1. The room

    Between 10 and 65 °C, near an exterior wall to keep the ducts short, away from a hot chimney, an electrical panel and other fire hazards, and away from living areas if possible. The door and the control panel stay easy to reach. Never in a cooking area, and the ducts never end inside a wall or ceiling cavity, an attic, a crawl space or a garage.

  2. Mounting

    Hung from the joists with the chains supplied, or on the wall with the brackets and 4 no. 8 × 1 1/2 in screws driven into studs. Level within 1/4 in.

  3. The drain

    For an HRV only. The supplied hose forms a trap loop at least 2 in from the unit, to keep odours out; a little water in the loop stops the hissing. With no drain nearby, the guide allows a pail. An ERV does not need one.

  4. The ducts

    Insulated flexible ducts to the outside, vapour barrier intact, the same diameter as the unit’s ports so water drains properly. Bend radius of at least 3 in, 12 in of flexible duct before any rigid duct, no screws in the ports.

  5. The outdoor hoods

    At least 6 ft apart unless you use the combined hood, and at least 18 in above the ground or the expected snow depth, whichever is greater. The intake hood sits at least 6 ft from a dryer vent, a high-efficiency central forced-air system vent, a central vacuum vent, a gas meter vent, a gas barbecue, any combustion exhaust and the garbage bins. No backdraft damper on the exhaust: it could freeze.

  6. Connecting to a furnace

    If the unit ties into a furnace’s return air, the connection sits at least 10 ft from the point where that return meets the furnace.

  7. Power

    A standard grounded outlet within 6 ft. No extension cord.

  8. Start-up

    Before plugging in: ducts sealed with tape, doors and windows closed, range hood, dryer and bathroom fans off. According to vänEE, the unit then balances itself: we wait for the maximum airflow to show, then set the minimum and maximum airflows and the installation type, from T-1 (fully ducted system) to T-5.

vänEE

Did you know?

Three details from the installation guide

Combustion

The guide forbids a stale-air exhaust grille in a room with a fuel-burning appliance, such as a furnace, a gas water heater or a fireplace.

Guide 23831WEB rev. X, p. 6

+60 s

If the unit is colder than the room when it is plugged in, start-up takes 60 seconds longer. That’s normal.

Guide 23831WEB rev. X, p. 16

Water

In cooler weather, an HRV can produce a lot of water: a badly run drain hose means water damage.

Guide 23831WEB rev. X, p. 8

vänEE

vänEE · Same airflow, two installs

V130H65RT or V130E65RT: same cabinet, not the same job

Both deliver the same net airflow at 0.4 in. w.g. What changes at install and upkeep:

FeatureV130H65RTV130E65RT
Net airflow at 0.4 in. w.g.119 cfm119 cfm
Core typeHRVERV
Drainrequirednone
Weight35 lb37 lb
Core cleaningsoaked in cold or lukewarm soapy water, every fallnever soaked: vacuum and soft brush, every fall

Airflows, types, drain and weights read from our product pages; cleaning per guide 23831WEB rev. X, p. 24.

Upkeep

What the V110 to V160 guide asks for, season after season

Every quarter

  • Filters: vacuum, then warm water and mild soap, rinse and let dry.
  • Condensate tray and outdoor hood: clean and clear.

Every fall

  • The quarterly routine, then the core cleaning shown in the table above.

In cold weather, if condensation forms on the windows, the guide advises keeping the house above 18 °C.

The guide makes part of the warranty depend on the core maintenance it describes: the terms are on our vänEE page.

No time? We handle it: air exchanger maintenance.

AirGreen × vänEE

The guide comes from the manufacturer. The install is ours.

What vänEE brings (AI Series)

  • The manufacturer’s installation guide for the V110 to V160.
  • The spec sheets for each model, with their sizes.
  • A washable MERV 8 filter included.

What AirGreen brings

  • The visit: we measure the room, look for the drain and pick the hood spots.
  • Installation by our technicians, under AirGreen’s RBQ licence 5645-9605-01 (subclasses 15.8, 15.10 and 16).
  • Start-up and airflow settings, with you.

Questions

Your questions before an install

Does a vänEE need a drain?

An HRV does: the AI Series HRV sheets all show a built-in drain fitting, hose included. For the V110 to V160, the guide asks for a nearby drain with a trap loop, or a pail, and asks for none on their ERVs. For the V180 to V230, we follow their spec sheet; the V210 ERV sheet shows a drain fitting on its drawing, which we check at the visit. For the older series, we follow the manufacturer’s documents.

Can I have a single outdoor hood?

Yes, on the V110 to V160, with the manufacturer’s combined hood (VTYIK1) and its Tandem transition. The guide limits that transition to units of 160 cfm or less at 0.4 in. w.g.; it adds static pressure and needs a joist opening of at least 9 3/4 in.

What if the ducts run through an unheated space?

The V110 to V160 guide then asks for the unit to run continuously, except during maintenance or repair, and for the house never to drop below 18 °C.

What if my existing ducts are 6 in?

The same guide asks for insulated ducts the same diameter as the ports. The V160 models have 6 in ports. The V110, V130 and V150 models have 5 in ports: the guide then calls for a 5 to 6 in transition, secured with duct tape only, and it recommends 6 in ducts on a V150 if you need more than 130 cfm.

What about renovations?

For these models, the guide says to switch the unit off: construction dust clogs the filters early.

Nearby pages

Go further

AirGreen

Your mechanical room, measured by us

We come and look at the room, the drain, the ducts and the wall where the hoods will go. You get a quote with the model that really fits.

Or call us: 514 316-2973

Sources checked on November 23, 2026

  1. AI Series installation guide (models V110 to V160), doc. 23831WEB, rev. X (pages 2, 4 to 10, 16 and 23 to 25).
  2. AI Series spec sheets: the V110H65RT sheet, 1109189G (V130H65), 1108607G (V130E65), 1109193G (V150H75), 1109192H (V150E75), 1109195G (V160H65RT), 1109196G (V160H75), 1109194J (V160E75RT), 1108462D (V180H75RT), 1108469D (V210E75RT), 1108468D (V210E75RS), 1108466D (V230H75RT), 1108464D (V230H75RS).
  3. Lineup sheet 91828 (02/2025) and the manufacturer’s product pages, read on November 23, 2026: active and discontinued models.
  4. Model sizes, airflows and types: our product pages, read live on this page (three widths: see the tool legend). Drain and clearance notes: the guide and the spec sheets.

The installation rules are the manufacturer’s; your municipality may add its own.