ELIOS e-Multi multi-zone heat pumps
One ELIOS compressor, up to six rooms: the combination table decides, not the BTU.
Four e-Multi outdoor units, 18,000 to 48,000 BTU/h, 3 to 6 heads each. Each head has a score, and the sum of the scores must appear in the ELIOS table. Below, a planner checks your combination.
The e-Multi in four numbers
SUB_E_XHSA submittals (07.26) and TAB_E_MZCBEX table (March 2026).
The essentials
What only an ELIOS multi-zone system requires, and allows.
The rules that decide how many rooms and which heads, drawn from the ELIOS documents.
Maximum heads on the 18,000, 27,000, 36,000 and 48,000 BTU/h outdoor units.
SUB_E_XHSA*, p. 2Each head counts for a fixed score (0.5 for a 6,000, 3 for a 33,000); the sum must appear in the ELIOS table.
TAB_E_MZCBEX, p. 2Maximum connection ratio advised by ELIOS; above 100%, no extra capacity.
TAB_E_MZCBEX, p. 2Combinations listed in the ELIOS table for the four outdoor units on this page.
TAB_E_MZCBEX, rev. 3Total line allowed from 27,000 to 48,000 (35 m per head); 60 m on the 18,000 (30 m per head).
SUB_E_XHSA*, p. 1Maximum height between the outdoor unit and the heads, then between the heads themselves.
SUB_E_XHSA*, p. 1Pre-charged per connection: refrigerant is added only beyond that.
ISM_E_XHSXHZ, p. 35Heating range of the EXS family we sell; ELIOS also publishes an EXZ family rated to −30 °C.
SUB_E_XHSA*, SUB_E_XHZA*What the 48,000 compressor still gives at −15 °C (20,000 at −25 °C).
SUB_E_XHSA48_2_O1 ; NEEPThe 18,000 compressor is twin-rotary; the 27,000 to 48,000 units are rotary.
e-Multi 202509 brochureWall, ducted, cassette and console heads mix on one compressor; some combinations exclude the 1-way cassette.
e-Multi 202603 brochure; TAB_E_MZCBEXIf a head leaks, an automatic valve isolates the refrigerant and the compressor stops.
Brochure e-Multi 202603, p. 4LogisVert per outdoor unit, list of Oct. 25, 2026: the amount does not depend on the number of heads.
Hydro-Québec listThe e-Multi wall heads are the EMC wall unit’s indoor units.
TRS_E_410454_1By AirGreen, who checks every combination with the ELIOS tool before the quotation.
The family
From the 2-head to the 6-head system: one page per number of rooms.
Counts and amounts read live. The more heads, the fewer compressors remain possible.
2 heads
2-head e-Multi
On all four compressors.
4listings18,000
–48,000
BTU/h−25 °Ccoldest certified23.1best SEER2$4,416
LogisVert max
See the page →
3 heads
3-head e-Multi
Allowed sizes depend on the compressor.
4listings18,000
–48,000
BTU/h−25 °Ccoldest certified23.1best SEER2$4,416
LogisVert max
See the page →
4 heads
4-head e-Multi
From the 27,000 up.
3listings27,000
–48,000
BTU/h−25 °Ccoldest certified23.1best SEER2$4,416
LogisVert max
See the page →
5 heads
5-head e-Multi
On the 36,000 or 48,000.
2listings36,000
–48,000
BTU/h−25 °Ccoldest certified23.1best SEER2$4,416
LogisVert max
See the page →
6 heads
6-head e-Multi
The maximum: 48,000 and six heads.
1listings48,000
BTU/h−25 °Ccoldest certified21.3best SEER2$4,416
LogisVert max
See the page →
The duel
Two compressors side by side: what you gain by going one size up.
Pick two outdoor units: certified heat, cold, SEER2 and LogisVert.
AirGreen × ELIOS
One ELIOS compressor for the house, a local team for the plan.
ELIOS publishes the allowed combinations. AirGreen chooses the heads room by room and runs the lines.
What ELIOS brings
- Up to 6 headsOn the 48,000 BTU/h outdoor unit.
- 312 combinationsListed in the ELIOS table for our four compressors.
- R-454BLeak sensor and shut-off valve in every head.
What AirGreen brings
- Sold and installed by AirGreenAcross Greater Montreal.
- Free on-site estimateThe quotation names the ELIOS model that fits and the LogisVert amount Hydro-Québec lists.
- RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16.
The result: a single ELIOS compressor outside, the right head in every room, installed by AirGreen.
The planner
Pick the compressor, add your rooms: the ELIOS table answers.
Each head size has a score. If the combination is in the ELIOS table, it is allowed; otherwise change a head or the compressor.
All our e-Multi systems, right below.
One listing per compressor and number of heads.
Everything to know
The e-Multi up close: compressors, heads, lines, noise.
What to know before running lines through the whole house.
Every model, side by side
The 14 e-Multi systems, side by side.
The same compressor appears several times: one listing per number of heads. Certified figures are those of the complete system.
| Model | Heat at −8 °C | Max at −15 °C | Coldest certified point | SEER2 | HSPF2 (V) | Sound | LogisVert | Certification |
|---|---|---|---|---|---|---|---|---|
| e-Multi · 18,000 BTU/h · 3 headsEXHSA1832AN1 | 16,000 BTU/h | 13,500 BTU/h | −25 °C · 7,000 BTU/h | 23 | 7.7 | 60 dB(A) outdoor | $1,920 | AHRI 216505500 · ENERGY STAR 3891349, cold climate |
| e-Multi · 18,000 BTU/h · 2 headsEXHSA1832AN1 | 16,000 BTU/h | 13,500 BTU/h | −25 °C · 7,000 BTU/h | 23 | 7.7 | 60 dB(A) outdoor | $1,920 | AHRI 216505500 · ENERGY STAR 3891349, cold climate |
| e-Multi · 27,000 BTU/h · 4 headsEXHSA2742AV1 | 23,600 BTU/h | 19,000 BTU/h | −25 °C · 11,800 BTU/h | 23 | 7.1 | 61 dB(A) outdoor | $2,832 | AHRI 216046639 · ENERGY STAR 3799027, cold climate |
| e-Multi · 27,000 BTU/h · 3 headsEXHSA2742AV1 | 23,600 BTU/h | 19,000 BTU/h | −25 °C · 11,800 BTU/h | 23 | 7.1 | 61 dB(A) outdoor | $2,832 | AHRI 216046639 · ENERGY STAR 3799027, cold climate |
| e-Multi · 27,000 BTU/h · 2 headsEXHSA2742AV1 | 23,600 BTU/h | 19,000 BTU/h | −25 °C · 11,800 BTU/h | 23 | 7.1 | 61 dB(A) outdoor | $2,832 | AHRI 216046639 · ENERGY STAR 3799027, cold climate |
| e-Multi · 36,000 BTU/h · 5 headsEXHSA3652AV1 | 31,000 BTU/h | 26,000 BTU/h | −25 °C · 20,000 BTU/h | 23.1 | 7.5 | 63 dB(A) outdoor | $3,720 | AHRI 216046642 · ENERGY STAR 3799030, cold climate |
| e-Multi · 36,000 BTU/h · 4 headsEXHSA3652AV1 | 31,000 BTU/h | 26,000 BTU/h | −25 °C · 20,000 BTU/h | 23.1 | 7.5 | 63 dB(A) outdoor | $3,720 | AHRI 216046642 · ENERGY STAR 3799030, cold climate |
| e-Multi · 36,000 BTU/h · 3 headsEXHSA3652AV1 | 31,000 BTU/h | 26,000 BTU/h | −25 °C · 20,000 BTU/h | 23.1 | 7.5 | 63 dB(A) outdoor | $3,720 | AHRI 216046642 · ENERGY STAR 3799030, cold climate |
| e-Multi · 36,000 BTU/h · 2 headsEXHSA3652AV1 | 31,000 BTU/h | 26,000 BTU/h | −25 °C · 20,000 BTU/h | 23.1 | 7.5 | 63 dB(A) outdoor | $3,720 | AHRI 216046642 · ENERGY STAR 3799030, cold climate |
| e-Multi · 48,000 BTU/h · 6 headsEXHSA4862AV1 | 36,800 BTU/h | 36,000 BTU/h | −25 °C · 20,000 BTU/h | 21.3 | 7.7 | 65 dB(A) outdoor | $4,416 | AHRI 216046645 · ENERGY STAR 3799033, cold climate |
| e-Multi · 48,000 BTU/h · 5 headsEXHSA4862AV1 | 36,800 BTU/h | 36,000 BTU/h | −25 °C · 20,000 BTU/h | 21.3 | 7.7 | 65 dB(A) outdoor | $4,416 | AHRI 216046645 · ENERGY STAR 3799033, cold climate |
| e-Multi · 48,000 BTU/h · 4 headsEXHSA4862AV1 | 36,800 BTU/h | 36,000 BTU/h | −25 °C · 20,000 BTU/h | 21.3 | 7.7 | 65 dB(A) outdoor | $4,416 | AHRI 216046645 · ENERGY STAR 3799033, cold climate |
| e-Multi · 48,000 BTU/h · 3 headsEXHSA4862AV1 | 36,800 BTU/h | 36,000 BTU/h | −25 °C · 20,000 BTU/h | 21.3 | 7.7 | 65 dB(A) outdoor | $4,416 | AHRI 216046645 · ENERGY STAR 3799033, cold climate |
| e-Multi · 48,000 BTU/h · 2 headsEXHSA4862AV1 | 36,800 BTU/h | 36,000 BTU/h | −25 °C · 20,000 BTU/h | 21.3 | 7.7 | 65 dB(A) outdoor | $4,416 | AHRI 216046645 · ENERGY STAR 3799033, cold climate |
Heat at −8 °C, maximum at −15 °C and coldest point: NEEP registry (ashp.neep.org), read by AHRI number on Oct. 14, 2026. SEER2 and HSPF2 region V: same source. LogisVert amounts: Hydro-Québec’s list of eligible heat pumps, Oct. 25, 2026. Sound: ELIOS technical documents. A dash means “not published”.
The thermometer
Every e-Multi compressor, from 8 °C to −25 °C.
Total NEEP-certified capacity, shared between all the heads.
The sound meter
The outdoor compressor, on the Québec.ca scale.
Maximum outdoor unit level per ELIOS. The heads have their own levels, in the heads table.
Tech corner
The four e-Multi compressors, one line each.
SUB_E_XHSA submittals (07.26). All 208-230 V, R-454B, flared connections, 7.5 m pre-charged per connection.
| Outdoor unit | Max heads | Total / per-head lines | Height | Outdoor sound | MCA / protection | Heats down to (ELIOS) |
|---|---|---|---|---|---|---|
| 18,000 · EXHSA1832AN1 | 3 | 60 / 30 m | 15 m (10 m between heads) | 60 dB(A) | 16 / 20 A | −25 °C |
| 27,000 · EXHSA2742AV1 | 4 | 80 / 35 m | 15 m (10 m between heads) | 61 dB(A) | 23 / 25 A | −25 °C |
| 36,000 · EXHSA3652AV1 | 5 | 80 / 35 m | 15 m (10 m between heads) | 63 dB(A) | 30.5 / 35 A | −25 °C |
| 48,000 · EXHSA4862AV1 | 6 | 80 / 35 m | 15 m (10 m between heads) | 65 dB(A) | 40 / 45 A | −25 °C |
The heads
The wall heads and their score.
The score, not the BTU, decides whether a combination is allowed. EMC heads, ELIOS I1 submittals (11.25).
| Wall head | Score | Width | Sound (low–turbo) | Lines |
|---|---|---|---|---|
| 6,000 · EWHMA06 | 0.5 | 729 mm | 24–42 dB(A) | 1/4 – 3/8 in |
| 9,000 · EWHMA09 | 0.75 | 802 mm | 24–44 dB(A) | 1/4 – 3/8 in |
| 12,000 · EWHMA12 | 1 | 802 mm | 22.5–44.7 dB(A) | 1/4 – 3/8 in |
| 18,000 · EWHMA18 | 1.5 | 1,082 mm | 24.5–54.5 dB(A) | 1/4 – 1/2 in |
| 24,000 · EWHMA24 | 2 | 1,082 mm | 34.5–54.5 dB(A) | 3/8 – 5/8 in |
| 33,000 · EWHMA33 | 3 | 1,259 mm | 29.5–56 dB(A) | 3/8 – 3/4 in |
Did you know
Eight facts from the e-Multi table and manual.
Tap a card to flip it.
LogisVert · Hydro-Québec
LogisVert on the e-Multi: the compressor counts, not the number of heads.
14 of the 14 listings on this page appear on Hydro-Québec’s list of eligible heat pumps (Oct. 25, 2026). The amount follows the certified heating capacity at −8 °C, size by size.
| Model | Capacity at −8 °C | Rate | Amount |
|---|---|---|---|
| e-Multi · 48,000 BTU/h · 6 heads | 36,800 BTU/h | $120 per 1,000 BTU/h, cold climate | $4,416 |
| e-Multi · 48,000 BTU/h · 5 heads | 36,800 BTU/h | $120 per 1,000 BTU/h, cold climate | $4,416 |
| e-Multi · 48,000 BTU/h · 4 heads | 36,800 BTU/h | $120 per 1,000 BTU/h, cold climate | $4,416 |
| e-Multi · 48,000 BTU/h · 3 heads | 36,800 BTU/h | $120 per 1,000 BTU/h, cold climate | $4,416 |
| e-Multi · 48,000 BTU/h · 2 heads | 36,800 BTU/h | $120 per 1,000 BTU/h, cold climate | $4,416 |
| e-Multi · 36,000 BTU/h · 5 heads | 31,000 BTU/h | $120 per 1,000 BTU/h, cold climate | $3,720 |
| e-Multi · 36,000 BTU/h · 4 heads | 31,000 BTU/h | $120 per 1,000 BTU/h, cold climate | $3,720 |
| e-Multi · 36,000 BTU/h · 3 heads | 31,000 BTU/h | $120 per 1,000 BTU/h, cold climate | $3,720 |
| e-Multi · 36,000 BTU/h · 2 heads | 31,000 BTU/h | $120 per 1,000 BTU/h, cold climate | $3,720 |
| e-Multi · 27,000 BTU/h · 4 heads | 23,600 BTU/h | $120 per 1,000 BTU/h, cold climate | $2,832 |
| e-Multi · 27,000 BTU/h · 3 heads | 23,600 BTU/h | $120 per 1,000 BTU/h, cold climate | $2,832 |
| e-Multi · 27,000 BTU/h · 2 heads | 23,600 BTU/h | $120 per 1,000 BTU/h, cold climate | $2,832 |
| e-Multi · 18,000 BTU/h · 3 heads | 16,000 BTU/h | $120 per 1,000 BTU/h, cold climate | $1,920 |
| e-Multi · 18,000 BTU/h · 2 heads | 16,000 BTU/h | $120 per 1,000 BTU/h, cold climate | $1,920 |
How Hydro-Québec computes it
The amount follows the certified heating capacity at −8 °C: $120 per 1,000 BTU/h for a cold-climate ENERGY STAR heat pump, $50 for a standard ENERGY STAR heat pump.
- Outdoor unit of 12,000 BTU/h or more.
- Capped at 100% of the cost of the work.
- Apply within 9 months of the installation.
Source: Hydro-Québec, LogisVert participation guide, residential customers, version 1.10 of September 15, 2026. Have Hydro-Québec confirm your case. Our LogisVert page.
Hydro-Québec does no phone or door-to-door solicitation for LogisVert. The amount shown is indicative: only Hydro-Québec confirms the aid granted.
Questions
Questions about ELIOS e-Multi multi-zone systems.
How many rooms can an e-Multi serve?
2 to 3 on the 18,000, up to 4 on the 27,000, 5 on the 36,000 and 6 on the 48,000. The ELIOS table also sets which head sizes go together.
Why is my combination refused when the BTU fit?
Because ELIOS does not count in BTU: each head has a score, and only the sums listed in the table are allowed. For example, three heads on the 18,000 can only be 6,000 or 9,000 units.
Can a wall unit and a ducted unit be mixed?
Yes, ELIOS allows wall, ducted, cassette and console heads on one compressor. Some combinations exclude the 1-way cassette: we validate with the ELIOS tool.
Does LogisVert change with the number of heads?
No: it follows the system’s certified capacity at −8 °C. On the Oct. 25, 2026 list: $1,920 (18,000), $2,832 (27,000), $3,720 (36,000), $4,416 (48,000).
Is there an e-Multi that heats at −30 °C?
ELIOS publishes an EXZ family rated to −30 °C. The systems on this page are the EXS family, rated to −25 °C. Tell us about your house: we compare.
How far can the heads be?
35 m per head and 80 m in total from 27,000 to 48,000 (30 and 60 m on the 18,000), 15 m of height to the outdoor unit, 10 m between heads, and at least 3 m per head.
What happens if a head detects a leak?
The head’s fan runs to disperse the refrigerant, an automatic shut-off valve isolates the circuit and the compressor stops, per the 2026 e-Multi brochure.
What warranty on an e-Multi?
ELIOS publishes 1 year on parts and 5 years on the compressor, with optional 10-year coverage. ELIOS publishes no labour warranty.
AirGreen × ELIOS · your project
Several rooms, one compressor: we make the plan together.
We visit the house, propose the heads room by room, validate the combination with the ELIOS tool and price the line route.
AirGreen · Air Conditioning & Heating
RBQ licence 5645-9605-01, subclasses 15.8 (ventilation), 15.10 (refrigeration) and 16 (electrical).
Free on-site estimate across Greater Montreal: Montreal, Laval, Longueuil, the North Shore and the South Shore.
Gas, oil and hydronic work is done by a partner who holds the required licence.
Sources checked on Oct. 26, 2026
- ELIOS, e-Multi outdoor unit submittals SUB_E_XHSA18, 27, 36 and 48 (revision 2, printed 07.26), eliosprotech.com.
- ELIOS, multi-zone combination table TAB_E_MZCBEX, revision 3 (March 2026).
- ELIOS, e-Multi brochures (Elios_e-Multi_202509 V02 and 202603 V03).
- ELIOS, ISM_E_XHSXHZ installation manual (pre-charge, lengths, defrost, automatic correction).
- ELIOS, wall head submittals SUB_E_WHMA06 to 33 (I1, 11.25) and “Did you know” bulletin DYK_E_042826.
- NEEP, Cold Climate Air Source Heat Pump List, ashp.neep.org, records read by AHRI number on Oct. 14, 2026.
- ENERGY STAR, Certified Air-Source Heat Pumps dataset (data.energystar.gov, w7cv-9xjt), Canadian market, read Oct. 14, 2026.
- Hydro-Québec, LogisVert eligible heat pump list, owner, existing home, file of Oct. 25, 2026 (ELIOS rows identical to Oct. 14).
- Hydro-Québec, LogisVert participation guide, residential customers, version 1.10, Sept. 15, 2026.
- Québec.ca, “Mesure du bruit”, updated June 16, 2022 (dBA sound scale).
- ENERGY STAR, “Properly Sized Room Air Conditioners”, energystar.gov (sizing chart), read Oct. 26, 2026.
Amounts shown are estimates; only the responsible organizations confirm the aid granted. Product availability is confirmed at the time of the quotation.