CONFORTO · AT electric boilers

CONFORTO AT electric boiler: the electrical specs of every model

The AT series has eight boilers from 6 to 24 kW and three two-boiler systems of 28, 32 and 40 kW. Pick a model: the page shows its BTU/h, element amps, minimum circuit ampacity, suggested fuse, minimum water flow and number of stages, as the CONFORTO brochure publishes them.

Updated October 29, 2026 · CONFORTO AT electric boiler brochure (rev. 12/14/23)

AT electric boiler brochure

The minimum water flow, by model

AT06236 kW2.0 gpm
AT08248 kW2.7 gpm
AT102510 kW3.4 gpm
AT122612 kW4.1 gpm
AT124312 kW4.1 gpm
AT164416 kW5.5 gpm
AT204520 kW6.8 gpm
AT244624 kW8.2 gpm

Brochure values, at ΔT 20 °F.

6 to 24 kWone boiler, 20,500 to 82,000 BTU/h at 240 V
38.8 to 132.5 Aminimum circuit ampacity, per the brochure
28, 32, 40 kWtwo boilers sharing the load
8 + 3boilers and systems in the shop

This page answers

CONFORTO AT electric boiler: what circuit, what minimum flow, and what are the two-boiler systems?

The CONFORTO shop · boilers

All 11 boilers and systems, right below

AT electric boilers from 6 to 24 kW and the AT2800, AT3200 and AT4000 systems. Priced by quote.

01 · The electrical spec sheet

CONFORTO AT boiler amperage, fuse and minimum flow, model by model

Pick a boiler or a two-boiler system. The figures are the CONFORTO brochure’s, at 240 V; for a system, the page shows both boilers side by side.

One boiler

Two boilers

AT2045 · MCA 111.7 A · fuse 125 A · 6.8 gpm See the details

Source: CONFORTO AT electric boiler brochure, rev. 12/14/23, 240 V. The brochure gives the fuse as a suggestion; the final fuse size is checked against the electrical code. The minimum water flow is given for a ΔT of 20 °F (about 11 °C).

AT2045 · 20 kW

111.7 Aminimum circuit ampacity (MCA)

Heat at 240 V68,200 BTU/h
Element amps83.3 A
Suggested fuse125 A
Minimum water flow at ΔT 20 °F6.8 gpm
Stages4, with element rotation
See the AT2045

02 · The eight boilers

CONFORTO AT electric boilers from 6 to 24 kW, side by side

Two stages up to 12 kW with the AT1226, four from the AT1243 up. The minimum circuit ampacity (MCA) is the minimum the brochure asks of each boiler’s circuit.

ModelOutputHeat at 240 VStagesElement ampsMin. circuit ampacity (MCA)Suggested fuseMinimum flow (ΔT 20 °F)
AT06236 kW20,500 BTU/h225.0 A38.8 A40 A2.0 gpm
AT08248 kW27,300 BTU/h233.3 A49.2 A50 A2.7 gpm
AT102510 kW34,100 BTU/h241.7 A59.6 A60 A3.4 gpm
AT12262 × 6 kW12 kW41,000 BTU/h250.0 A70.0 A70 A4.1 gpm
AT12434 × 3 kW12 kW41,000 BTU/h450.0 A70.0 A70 A4.1 gpm
AT164416 kW54,600 BTU/h466.7 A90.8 A100 A5.5 gpm
AT204520 kW68,200 BTU/h483.3 A111.7 A125 A6.8 gpm
AT244624 kW82,000 BTU/h4100.0 A132.5 A150 A8.2 gpm
SystemSystem outputMade ofElectrical data
AT280028 kWAT1243 + AT1644those of each boiler
AT320032 kWtwo AT1644those of each boiler
AT400040 kWtwo AT2045those of each boiler

CONFORTO AT electric boiler brochure, rev. 12/14/23: every value, at 240 V. Stages: brochure and AirGreen product pages.

03 · Boiler or furnace

At 20 kW: the AT2045 boiler and the CONFORTO furnace, figure for figure

Same output, nearly the same heat and nearly the same circuit. They differ in what they heat: the water of a hot-water system, or the air in the ducts.

Electric boiler

AT2045 · 20 kW

What it heatsthe water in a hot-water heating system
Heat at 240 V68,200 BTU/h
Minimum circuit ampacity111.7 A
See the AT2045
or

Element furnace

KHE or KLE · 20 kW

What it heatsthe air in the ducts
Heat at 240 V68,288 BTU/h
Minimum circuit ampacity110 A
See the CONFORTO furnaces

The choice follows what the house already has. The two figures on each line come from two different CONFORTO documents, quoted as printed.

Boiler: AT electric boiler brochure, rev. 12/14/23. Furnace: CONFORTO KHE and KLE manuals, G2018 Rev. E, section 6.0.

04 · Did you know

Three details from the AT brochure

8.2 gpm

From 2.0 to 8.2 gpm: the minimum flow, model by model

The brochure calls for 2.0 gpm through the 6 kW AT0623 and 8.2 gpm through the 24 kW AT2446, for water that gains 20 °F (about 11 °C) as it passes through the boiler.

AT electric boiler brochure

12 + 16

The AT2800 pairs two different models

The AT3200 and the AT4000 double up one boiler: two AT1644s, two AT2045s. The AT2800 pairs a 12 kW AT1243 with a 16 kW AT1644.

AT electric boiler brochure

70 lb

The 6 kW weighs as much as the 24 kW

The brochure gives about 70 lb (32 kg) per boiler, at every output. In a system, that is 70 lb for each of the two.

AT electric boiler brochure

05 · Questions

Your questions about CONFORTO boilers

What amperage does a 20 kW CONFORTO electric boiler need?

Per the brochure, the AT2045 draws 83.3 A at its elements, with a minimum circuit ampacity of 111.7 A and a suggested 125 A fuse, at 240 V. The headroom left on your electrical service is checked on site, during the estimate.

AT electric boiler brochure, rev. 12/14/23
What is the difference between the CONFORTO AT1226 and AT1243 boilers?

Both are 12 kW. The AT1226 has two 6 kW elements and two stages; the AT1243 has four 3 kW elements and four stages. Their published figures are identical: 41,000 BTU/h, a 70.0 A minimum circuit ampacity, a suggested 70 A fuse and a 4.1 gpm minimum flow.

AT electric boiler brochure
Do the CONFORTO AT2800, AT3200 and AT4000 systems have their own electrical data?

No. The brochure publishes each boiler’s data, not the system’s. An AT4000 therefore reads as two AT2045s, each with a 111.7 A minimum circuit ampacity and a suggested 125 A fuse.

AT electric boiler brochure
How does a CONFORTO AT boiler control its output?

In stages, with element rotation: two stages on the AT0623, AT0824, AT1025 and AT1226, four on the AT1243, AT1644, AT2045 and AT2446. The brochure also lists a load-management controller and a cast-iron exchanger.

AT electric boiler brochure; AirGreen product pages
Which CONFORTO electric boiler output should I choose?

The output depends on your hot-water heating system. The AT series runs from 6 to 24 kW with one boiler, and from 28 to 40 kW with two. At the estimate, we check what your electrical service can accept: 38.8 A (6 kW) to 132.5 A (24 kW) of minimum circuit ampacity for a single boiler, per the brochure.

AT electric boiler brochure
What does a CONFORTO electric boiler cost?

Pricing is by quote. The in-home estimate is free, with no commitment.

AirGreen · Air conditioning & heating

The AT boiler and your electrical service, checked before the quote

At the estimate, we check the headroom on your electrical service for the model you have in mind, then give you a quote for the boiler.

RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16
Authorized CONFORTO dealerSold by AirGreen
Free estimateAt home, no commitment
Showroom1370 Joliot-Curie St., Suite 712, Boucherville

Sources checked on October 28, 2026

  • CONFORTO “AT electric boiler” brochure, French and English versions, rev. 12/14/23: outputs, BTU/h, element amps, minimum circuit ampacity, suggested fuse, minimum water flow, stages, weight and two-boiler systems.
  • CONFORTO KHE and KLE manuals, G2018 Rev. E (December 12, 2025), section 6.0: heat and minimum circuit ampacity of the 20 kW furnace, for the comparison.
  • AirGreen product pages: models in the shop, read live by this page; stages, recorded on October 28, 2026.

Priced by quote; free in-home estimate.