THERMO 2000 VoltMax SCR VOLTSCR480120P3 Commercial Electric Boiler | 120 kW - 480V 3 Phase

In stock

Thermo 2000’s VoltMax SCR 120 delivers 120 kW on 480 V three-phase to supply both a building’s hot-water coils and an indirect water heater.

Model numberVOLTSCR480120P3

120 kW409,440 BTU/h
144.3 Aon 480 V three-phase
2nd setpointfor an indirect water heater
480 V · three-phaseDomestic hot water priorityBACnet IP / MS-TP
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR480120P3
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 120-480-3 PH
Output120 kW (409,440 BTU/h)
Power supply480 V, three-phase, 60 Hz
Current144.3 A
Working pressure125 psi (862 kPa), standard

120 kW on 480 V to supply hot-water coils and an indirect water heater

A boiler for buildings with more than one need

The VoltMax SCR 120 (manufacturer designation: VOLTMAX SCR 120-480-3 PH) is a commercial electric boiler from Thermo 2000: 120 kW, or 409,440 BTU/h, on 480 V three-phase. It heats the water in a closed loop and belongs to the series’ configuration B, with 30 US gal of water in a 550 lb vertical cabinet.

It suits buildings that need more than space heating. A sports centre in Laval with its change rooms, a community building on the South Shore, a commercial building whose air is heated by the hot-water coils of air handling units: in these cases, the same boiler can also supply an indirect water heater.

Air heating and domestic water, set separately

The Schneider Electric controller manages two setpoints. The first sets the heating loop, with outdoor reset from the included sensor, over a range of 50 °F to 200 °F. The second setpoint is reserved for the indirect water heater, and a pump contact lets domestic hot water be served with or without priority over heating.

To meet both, the boiler modulates its output from 0 to 100% through solid-state relays (SCR), on top of its relay stages, which it rotates. Thermo 2000 states that this modulation limits peak power. On 480 V three-phase, it draws 144.3 A.

In a building with a management system, it communicates over BACnet IP or MS-TP, or follows a 0-10 Vdc signal for setpoint and output. Its Ethernet port also gives access to a web page and sends alarms by email. Its maximum working pressure is 125 psi (862 kPa) as standard.

Installation by AirGreen

We start with a free on-site estimate: 480 V service, mechanical room, air handling units, hot water needs. You then receive a written quote covering the boiler and what goes around it: indirect water heater, circulators and expansion tank, which Thermo 2000 does not supply.

Our crews deliver the boiler, set it in place with 24 in clear in front, 32 in above and 3 in on the sides and back, connect the loops to the 2 1/2 in NPT connections, wire the 480 V supply and the outdoor sensor, then fill and purge the circuit. At commissioning, we set both setpoints and the priority to suit how the building is used.

Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years. AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work.

Your building, our estimate

In Montreal, Laval, Longueuil, on the North Shore or on the South Shore, ask for a free estimate: the quote is in writing and financing is available.

01 · What it is for

Coil heating and hot water from one boiler

A sports centre, a community building with change rooms or a commercial building often has two needs: heating the air through hot-water coils and producing domestic water. The 480 V VoltMax SCR 120 handles both with a second setpoint and a pump contact with or without priority.

  • Sports centres and community buildings with change rooms
  • Air handling units with hot-water coils
  • Commercial and institutional buildings on 480 V three-phase
  • Heating loops paired with an indirect water heater
Two setpointsOne for the heating loop, a second for the indirect water heater, with or without domestic hot water priority.
120 kW, modulatedSCR modulation from 0 to 100% and stage rotation; according to Thermo 2000, modulation limits peak power.
Building integrationBACnet IP / MS-TP, 0-10 Vdc control, web page and email alarms.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 120-480-3 PH
TypeCommercial electric hot-water boiler, vertical design
Output120 kW
Output in BTU/h409,440 BTU/h
Power supply480 VAC, 60 Hz, three-phase
Current144.3 A
ModulationSCR 0 to 100% (solid-state relays) plus relay stages
ConfigurationB (99 to 180 kW models)
Water volume30 US gal (113.5 L)
Water connections2 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
Max. working pressure125 psi (862 kPa), standard
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, French or English, °C or °F
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
External control0-10 Vdc signal (setpoint and output)
FunctionsOutdoor reset, stage rotation, pump contact with or without domestic hot water priority, second setpoint for an indirect water heater
Outdoor sensorIncluded
Heating elementsImmersion type, Incoloy, replaceable
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight550 lb (250 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR480120P3
03 · Before installing

What to know before installing

  • 480 V three-phase, 60 Hz, 144.3 A according to Thermo 2000: we check the electrical service before quoting.
  • The indirect water heater, circulator and expansion tank are ordered separately: they are not among the components Thermo 2000 supplies.
  • Configuration B: 550 lb (250 kg), 2 1/2 in male NPT connections, 30 US gal of water.
  • Clearances: 3 in on the sides and back, 24 in in front, 32 in above.
  • Manufacturer warranty: 10 years on the tank (limited warranty, closed-loop heating), 2 years on electrical and mechanical components.
In the box
  • Schneider Electric controller
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relays
  • Two limit controls, automatic and manual reset
  • Factory-installed relief valve
  • Drain valve
  • Low-water cut-off (standard above 60 kW)
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

How does the boiler share heating and hot water?

The Schneider Electric controller manages a second setpoint for the indirect water heater and a pump contact, with or without domestic hot water priority. We choose the setting based on how the building is used.

Is the indirect water heater included?

No. It is ordered separately, like the circulator and expansion tank. We choose it with you and list it in the quote.

What current does it draw on 480 V?

144.3 A on 480 V three-phase, 60 Hz, according to Thermo 2000.

Can it be connected to the building management system?

Yes, over BACnet IP or MS-TP, or through a 0-10 Vdc signal for setpoint and output.

Can you install it?

Yes. We install the boiler and, where applicable, the indirect water heater, connect the loops and the 480 V supply, mount the outdoor sensor and commission it.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 480 V VoltMax SCR 120, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.