THERMO 2000 VoltMax SCR VOLTSCR480144P3 Commercial Electric Boiler | 144 kW - 480V 3 Phase

In stock

A 144 kW commercial electric boiler on 480 V three-phase, Thermo 2000’s VoltMax SCR connects to the building management system through BACnet IP or MS-TP.

Model numberVOLTSCR480144P3

144 kW491,328 BTU/h
173.2 Acurrent at 480 V three-phase
0 to 100%SCR power modulation
480 V · three-phaseBACnet IP / MS-TPOutdoor sensor supplied
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR480144P3
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 144-480-3 PH
Output144 kW (491,328 BTU/h)
Power supply480 V, three-phase, 60 Hz
Current173.2 A
CommunicationBACnet IP / MS-TP, Ethernet

A 144 kW boiler that fits into your building’s management system

Who the 480 V VoltMax SCR 144 is for

In a commercial or industrial building heated with hot water, the boiler is no longer a stand-alone appliance: it has to answer to the building management system, report its alarms and follow a sequence. Thermo 2000’s VoltMax SCR 144 meets those expectations. This 144 kW version, or 491,328 BTU/h, runs on 480 V three-phase and modulates its output from 0 to 100% with solid-state relays.

It is aimed at owners, building managers and mechanical contractors who are replacing a commercial electric boiler or installing a new one to the engineer’s drawings. Workshops, heated warehouses, offices, schools: any building whose loop feeds radiators, hot-water baseboards, a radiant floor or hydro-air coils.

A controller designed for managed buildings

The Schneider Electric controller, with its 3 in backlit display, communicates over BACnet IP and MS-TP. Its Ethernet port opens a web page and sends email alarms, so the manager can follow the boiler without going down to the mechanical room. An external 0-10 Vdc signal can set the setpoint and the output, and the supplied outdoor sensor provides weather compensation. The controller also rotates the stages and can serve an indirect water heater through a second setpoint.

On compliance, Thermo 2000’s specification lists CSA C22.2 No. 165-92 and UL 834, a CSA B-51-14 tank, CRN registration and the ASME Section IV "H" stamp. These references appear in the spec sheet, and your engineer can carry them into the project specification.

480 V and the mechanical room

On 480 V three-phase, the VoltMax SCR 144 draws 173.2 A. The first check is therefore the service voltage: if your building in Laval or on the North Shore is on 600 V, the same boiler comes in that voltage. In the mechanical room, it stays compact: 3 in of clearance on the sides and back, 24 in in front, 32 in above. It holds 30 US gal of water, accepts a setpoint from 50 °F to 200 °F and weighs 550 lb (250 kg).

Installation by AirGreen

The on-site estimate is free. We check the electrical service, the loop and the emitters, then give you a written quote that specifies the circulating pump and the expansion tank, which are not on Thermo 2000’s list of supplied items. Our crews install the boiler, connect the piping and the 480 V circuit, commission it and set up the controller; the BACnet link is coordinated with your building’s integrator.

A family business established in Montreal for more than fifteen years, AirGreen holds RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work. For its part, Thermo 2000 warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Your 480 V building

For a building in Montreal, Laval, Longueuil, on the North Shore or the South Shore, ask for a free estimate. You will receive a written quote, with financing available.

01 · What it is for

A 144 kW boiler for a building on 480 V

The VoltMax SCR 144 heats the water in a closed heating system and is controlled like any other building system: BACnet, Ethernet, 0-10 Vdc signal. This version is meant for buildings whose three-phase service is 480 V.

  • Commercial and industrial buildings on 480 V three-phase power
  • Buildings monitored by a BACnet building management system
  • Heating with radiators, hot-water baseboards, radiant floors or hydro-air coils
  • Indirect water heater for domestic hot water, on the second setpoint
BACnet IP and MS-TPThe boiler joins the building management system; its Ethernet port also provides a web page and email alarms.
0-10 Vdc controlAn external signal can set the temperature setpoint and the output, per Thermo 2000.
CSA, UL, ASME and CRNCSA C22.2 No. 165-92 and UL 834, CSA B-51-14 tank, CRN registration and ASME Section IV "H" stamp, per the manufacturer’s specification.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 144-480-3 PH
ConfigurationB (99 to 180 kW)
TypeCommercial hot-water electric boiler, vertical
Output144 kW
Output in BTU/h491,328 BTU/h
Power supply480 VAC, 60 Hz, three-phase
Current173.2 A
ModulationSCR 0 to 100% (solid-state relay) plus relay stages
Water volume30 US gal (113.5 L)
Water connections2 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
Max. working pressure125 psi (862 kPa), standard
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French and English
Control functionsStage rotation, outdoor reset, schedules, pump contact with or without domestic hot water priority, second setpoint for an indirect water heater
External control0-10 Vdc signal (setpoint and output)
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
Heating elementsImmersion type, Incoloy, replaceable
Low-water cutoffStandard (models above 60 kW)
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight550 lb (250 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR480144P3
03 · Before installing

What to know before installing

  • 480 V three-phase, 60 Hz power supply: 173.2 A. Confirm the building’s service voltage; for a 600 V service, the VoltMax SCR comes in that voltage.
  • The BACnet link with the building management system is coordinated with the controls integrator.
  • The circulating pump and expansion tank are not on Thermo 2000’s list of supplied items: they are added to the quote.
  • Clearances: 3 in on the sides and back, 24 in in front, 32 in above, none underneath. Weight: 550 lb (250 kg).
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • On/off control switch
  • Control and power fuses and breakers
  • SCR relays
  • Two limit controls, automatic and manual reset
  • Factory-installed relief valve
  • Drain valve
  • Low-water cutoff
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can the boiler communicate with our building management system?

Yes. The Schneider Electric controller offers BACnet IP and MS-TP, plus an Ethernet port with a web page and email alarms. Thermo 2000 does not mention Modbus: if your system requires it, let’s talk before ordering.

Can it be driven by an external signal?

Yes, by a 0-10 Vdc signal that sets the temperature setpoint or the output. This is useful when a central controller manages the building’s heating sequence.

Our building is on 600 V: does this version work?

No, this one runs on 480 V three-phase. The VoltMax SCR series also comes in 600 V; we confirm the service voltage during the free estimate.

Which certifications does it carry?

According to Thermo 2000’s specification: CSA C22.2 No. 165-92 and UL 834 (CSA mark for Canada and the United States), CSA B-51-14 tank, CRN registration and ASME Section IV "H" stamp.

What does AirGreen’s installation include?

We set the boiler in place, connect the piping and the 480 V circuit, fill and purge the loop, then set up the controller and the outdoor sensor. The link with the management system is made with your building’s integrator.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 144 kW, 480 V VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.