THERMO 2000 VoltMax SCR VOLTSCR48054P3 Commercial Electric Boiler | 54 kW - 480V 3 Phase

In stock

On 480 V three phase, Thermo 2000’s VoltMax 54 delivers 54 kW to a hot-water loop with a current of only 65 A.

Model numberVOLTSCR48054P3

65 Acurrent on 480 V three phase
54 kW184,248 BTU/h
11 US galof water in the boiler (41.6 L)
480 V · three phaseEmail alarmsOutdoor sensor includedLow water cut-off optional
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR48054P3
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 54-480-3 PH
Output54 kW (184,248 BTU/h)
Power supply480 V, 3 ph, 60 Hz
Current65 A
Setpoint range50 °F to 200 °F

54 kW of hot-water heating for only 65 A, thanks to 480 V three phase

What the voltage changes

Thermo 2000’s VoltMax SCR comes in several voltages. In a building with a 480 V three-phase supply, the 54 kW size draws a current of 65 A, according to the manufacturer. Conductors and protective devices are sized from that value, much lower than on 208 V or 240 V for the same output. The 480 V sizes we offer in this series range from 30 kW to 180 kW; this one produces 184,248 BTU/h.

A boiler for institutional buildings

A school, a community centre, a place of worship: these buildings often heat with hot water, through radiators or radiant floors, and they are maintained by a small team with other duties. The VoltMax 54 is designed for them, as well as for commercial buildings of the same size.

The Schneider Electric controller shows alarm codes, in French or English, on a 3 in backlit display. Through its Ethernet port, it gives access to a web page and sends alarms by email. It also communicates over BACnet IP or MS-TP if the building has a management system, and accepts a 0-10 Vdc signal for setpoint or output.

On the heating side, the solid-state relay (SCR) varies output from 0 to 100%, complemented by relay stages that the controller rotates. The included outdoor sensor adjusts water temperature to the weather, within a setpoint of 50 °F to 200 °F (10 °C to 93 °C). A second setpoint supplies an indirect water heater, for hot water in kitchens or locker rooms.

Before installation

The boiler is vertical and compact. It weighs 310 lb (141 kg), holds 11 US gal of water and can be set directly on the floor. Thermo 2000 requires 3 in of clearance on the sides and back, 24 in at the front for service and 32 in above. The list of supplied parts includes the controller, outdoor sensor, fuses and breakers, two limit controls, the relief valve and the drain valve, but not the circulator or the expansion tank. Finally, the low water cut-off is an option at 54 kW.

AirGreen takes care of it

Our on-site estimate is free. We look at the water loop, the mechanical room and the 480 V electrical service, then give you a complete written quote, circulator and expansion tank included. Our technicians install the boiler, connect it to the loop through its 1 1/2 in NPT fittings, make the electrical connection, mount the outdoor sensor, fill and purge the system and set up email alarms for your team.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work. Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Let’s plan the work

We install the VoltMax SCR in Montreal, Laval, Longueuil, on the North Shore and on the South Shore. Ask for your free estimate and written quote; financing is available.

01 · What it is for

Hot-water heating for institutional buildings on 480 V

The 480 V VoltMax 54 heats the water loop of a school, a community centre or another institutional or commercial building. Its controller alerts maintenance staff with alarm codes on the display and alarms by email.

  • Schools, community centres and places of worship heated with hot water
  • Commercial buildings with a 480 V three-phase supply
  • Radiant floors, radiators and hydro-air coils
  • Replacing an electric boiler of comparable output
Only 65 AThe current Thermo 2000 publishes for 54 kW on 480 V three phase.
Clear alarmsAlarm codes on the backlit display, in French or English, and email alarms through the Ethernet port.
Modulation from 0 to 100%The solid-state relay (SCR) adjusts output continuously and limits peak power demand, according to the manufacturer.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR, configuration A (22.5 to 90 kW)
Manufacturer designationVOLTMAX SCR 54-480-3 PH
TypeCommercial hot-water electric boiler with SCR modulation
Output54 kW
Output in BTU/h184,248 BTU/h
Power supply480 VAC, 60 Hz, three phase
Current65 A
Heating elementsImmersion type, Incoloy, replaceable
ModulationSCR from 0 to 100% (solid-state relay) and relay stages, with stage rotation
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French or English
CommunicationBACnet IP / MS-TP, Ethernet port with web page and email alarms
External controlSetpoint and output by 0-10 Vdc signal
Outdoor sensorIncluded (outdoor temperature reset)
Domestic hot waterPump contact with or without priority, 2nd setpoint for an indirect water heater
Low water cut-offOptional on this size (standard above 60 kW)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0 in
Weight310 lb (141 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR48054P3
03 · Before installing

What to know before installing

  • 480 V three-phase, 60 Hz power supply. Thermo 2000 publishes a current of 65 A for this model.
  • The low water cut-off is offered as an option up to 60 kW; it is standard only above that.
  • The circulator and expansion tank are not among the supplied parts: we include them in the quote.
  • Clearances: 3 in at the sides and back, 24 in at the front, 32 in above; setting directly on the floor is allowed.
  • 310 lb (141 kg) to place in the mechanical room, plus 11 US gal of water.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • On/off control switch
  • Control and power fuses and breakers
  • SCR relay
  • 2 limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Why is the current so low?

Because the voltage is high. For the same output, a boiler on 480 V three phase draws much less current than on 208 V or 240 V. Thermo 2000 publishes 65 A for this 54 kW model.

What other sizes exist on 480 V?

The 480 V three-phase VoltMax SCR sizes we offer range from 30 kW to 180 kW. We choose the size from the building’s heating load, not from the old boiler alone.

How are maintenance staff alerted to a fault?

The controller shows an alarm code on its display, in French or English, and sends the alarm by email through its Ethernet port. It can also pass it to the building management system over BACnet IP or MS-TP.

Is the low water cut-off included?

Not on this size: it is offered as an option up to 60 kW and installed as standard above that. We note it in the quote if your installation needs one.

What warranty does Thermo 2000 offer?

A 10-year limited warranty on the tank for closed-loop heating, and 2 years on electrical and mechanical components.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 480 V VoltMax 54, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.