THERMO 2000 VoltMax SCR VOLTSCR48030P3 Commercial Electric Boiler | 30 kW - 480V 3 Phase

In stock

Thermo 2000’s VoltMax SCR at 30 kW, 480 V three phase: a CSA and UL certified commercial electric boiler that draws 36.1 A at full output.

Model numberVOLTSCR48030P3

36.1 Aat 480 V three phase, full output
102,360 BTU/h30 kW
ASME IVH-stamped tank, CRN
480 V · three phaseCSA · UL 834Commercial boiler
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR48030P3
ManufacturerThermo 2000
DesignationVOLTMAX SCR 30-480-3 PH
Output30 kW (102,360 BTU/h)
Power supply480 V, three phase, 60 Hz
Current36.1 A
Water volume11 US gal (41.6 L)

30 kW on 480 V three phase, with the certifications an engineer or inspector asks for

For buildings supplied at 480 V

Thermo 2000’s VoltMax SCR 30-480-3 PH is a commercial electric hot-water boiler that connects directly to a 480 V three-phase supply. It delivers 30 kW, or 102,360 BTU/h according to the manufacturer, and draws only 36.1 A at full output. It heats a loop of radiators, baseboards or radiant floor in a commercial, institutional or multi-unit building, with no GHG emissions on site.

The VoltMax SCR series also comes in 208 V, 240 V and 600 V. Before recommending the 480 V version, we therefore confirm your building’s actual voltage, whether it is in Montreal, Laval or on the South Shore.

Certifications and documents

In an engineered project, certifications and documentation matter as much as output. The VoltMax carries the CSA mark for Canada and the United States, to CSA C22.2 No. 165-92 and UL 834. Its tank complies with CSA B-51-14, is CRN registered and carries the ASME Section IV H stamp. Thermo 2000 publishes an engineering specification, a manual and a brochure, which you will find in the Documents section of this page.

Operation and controls

Output is measured out by a solid-state relay (SCR) that modulates from 0 to 100%, alongside the relay stages that the controller alternates. According to Thermo 2000, this modulation limits peak power demand. The Incoloy immersion elements are replaceable.

The Schneider Electric controller, with a 3 in backlit display, sets the setpoint from 50 °F to 200 °F and applies outdoor reset with the included sensor. It communicates over BACnet IP or MS-TP, accepts an external 0-10 Vdc control for setpoint and output, and sends its alarms by email through its Ethernet port. A 2nd setpoint and a pump contact with or without priority allow an indirect water heater to be added.

AirGreen’s installation

We start with a free on-site estimate, followed by a written quote. It includes the circulator and expansion tank, which are not among the supplied parts, and the low-water cut-off if the project requires it: at this size, it is optional. The boiler weighs 310 lb (141 kg), holds 11 US gal of water and needs clearances of 3 in at the sides and rear, 24 in at the front and 32 in above.

Our technicians connect it to the loop through its four 1 1/2 in male NPT side connections, pipe the discharge of the factory-installed relief valve and mount the outdoor sensor. The electrical connection, with protection and conductors sized from the nameplate, is made under AirGreen’s RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical).

AirGreen is a family business established in Montreal for more than fifteen years, also installing in Longueuil and on the North Shore. Thermo 2000 warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Next step

Send us your project’s drawings or specification, or ask for a free estimate: the quote is in writing, and financing is available to spread out your payments.

01 · What it is for

A commercial boiler for buildings supplied at 480 V

The VoltMax SCR heats the water of a loop of radiators, baseboards or radiant floor in a commercial, institutional or multi-unit building. This version connects directly to a 480 V three-phase supply.

  • Commercial or industrial building supplied at 480 V three phase
  • Engineered project that requires CSA, UL, CRN and ASME
  • Institutional building connected to a BACnet system
  • Space heating and an indirect water heater on the same boiler
36.1 A at full outputOn 480 V three phase, the boiler’s 30 kW calls for a modest current.
CSA and UL certifiedCSA C22.2 No. 165-92 and UL 834; CSA B-51-14 tank, CRN registration, ASME Section IV H stamp.
SCR modulation from 0 to 100%The solid-state relay adjusts output continuously, with rotation of the relay stages.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 30-480-3 PH
TypeCommercial electric hot-water boiler, SCR modulation
Output30 kW
Output in BTU/h102,360 BTU/h
Power supply480 VAC, 60 Hz, three phase
Current36.1 A
Heating elementsIncoloy immersion, replaceable
ModulationSCR 0 to 100% (solid-state relay) and relay stages
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT (4 side connections)
Relief valve and drain connections3/4 in female NPT
Temperature setpoint50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD: SCR modulation, stage rotation, outdoor reset, pump contact with or without domestic hot water priority, 2nd setpoint for an indirect water heater, alarm codes, °C/°F, French and English
CommunicationBACnet IP / MS-TP · Ethernet port (web page, email alarms) · external 0-10 Vdc signal (setpoint and output)
Outdoor sensorIncluded
Low-water cut-offOptional at this size (standard above 60 kW)
ClearancesSides 3 in · rear 3 in · front 24 in · top 32 in · floor 0 in
Weight310 lb (141 kg)
Manufacturer configurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR48030P3
03 · Before installing

What to know before installing

  • Commercial boiler for a 480 V three-phase, 60 Hz supply: the building’s voltage must be confirmed before ordering.
  • Protection and conductors are sized from the unit’s nameplate.
  • Low-water cut-off: optional at this size, standard above 60 kW.
  • The circulator and the expansion tank are not on the list of supplied parts.
  • Clearances: sides 3 in, rear 3 in, front 24 in, top 32 in, floor 0 in. Weight: 310 lb (141 kg).
In the box
  • Schneider Electric controller with backlit LCD
  • Outdoor temperature sensor
  • ON/OFF control switch
  • Control and power fuses and breakers
  • SCR relay
  • Two high-limit controls (automatic and manual)
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

How do I know whether my building is supplied at 480 V?

We check on site, at the electrical service, before anything is ordered. The VoltMax SCR also comes in 208 V, 240 V and 600 V versions: we choose the one that matches your building.

What certifications does the boiler carry?

The CSA mark for Canada and the United States, to CSA C22.2 No. 165-92 and UL 834. The tank complies with CSA B-51-14, is CRN registered and carries the ASME Section IV H stamp.

Where can I find the technical documentation?

Thermo 2000’s engineering specification, manual and brochure are in the Documents section of this page.

What electrical protection is needed?

The boiler draws 36.1 A at 480 V three phase. We size the protection and conductors from the nameplate.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 480 V 30 kW VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.