THERMO 2000 VoltMax SCR VOLTSCR480165P3 Commercial Electric Boiler | 165 kW - 480V 3 Phase

In stock

Thermo 2000’s VoltMax SCR 165 is a 165 kW commercial electric boiler on 480 V three-phase, backed by an engineering specification and CSA, UL and ASME certifications.

Model numberVOLTSCR480165P3

165 kW562,980 BTU/h
198.5 Acurrent at 480 V three-phase
0 to 100%SCR power modulation
480 V · three-phaseCSA · UL · ASMELow-water cutoff
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR480165P3
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 165-480-3 PH
Output165 kW (562,980 BTU/h)
Power supply480 V, three-phase, 60 Hz
Current198.5 A
CommunicationBACnet IP / MS-TP, Ethernet

165 kW on 480 V, with the documentation a commercial project calls for

The VoltMax SCR 165 at a glance

The VoltMax SCR 165 is Thermo 2000’s 165 kW commercial electric boiler, here in its 480 V three-phase version. The manufacturer rates it at 562,980 BTU/h. It heats the water in a closed loop that feeds radiators, hot-water baseboards, a radiant floor or hydro-air coils, and it can serve an indirect water heater through a second setpoint.

It is aimed mainly at engineer-designed projects: a new industrial building, a commercial expansion, the replacement of a commercial boiler in an existing building. In those files, the boiler first has to pass the drawing review.

What the engineer and the inspector will find

Thermo 2000 publishes an engineering specification, an installation manual and a brochure for the VoltMax, gathered in the Documents section. The specification lists CSA C22.2 No. 165-92 and UL 834, a CSA B-51-14 tank, CRN registration and the ASME Section IV "H" stamp. For safety, the boiler comes with two limit controls with automatic and manual reset, a factory-installed relief valve and, since it exceeds 60 kW, a standard low-water cutoff.

For the control sequence, the Schneider Electric controller combines SCR modulation from 0 to 100% with rotation of the relay stages. It accepts a 0-10 Vdc signal for setpoint and output, communicates over BACnet IP and MS-TP, and adjusts the water temperature with the supplied outdoor sensor.

On site, in Quebec

On 480 V three-phase, the VoltMax SCR 165 draws 198.5 A; sizing the circuit is up to the engineer or the master electrician. In an industrial building in Laval, for example, the vertical boiler fits with 3 in of clearance on the sides and back, 24 in in front and 32 in above. Its four 2 1/2 in male NPT side connections, its 30 US gal of water and its 50 °F to 200 °F setpoint go straight onto the drawings. For handling, count on 550 lb (250 kg).

Our role on site

AirGreen installs the boiler to the engineer’s drawings and specification. After a free on-site estimate, we provide a written quote that specifies the circulating pump and the expansion tank, which are not on Thermo 2000’s list of supplied items. On site, our crews set the boiler in place, connect the piping and the 480 V circuit, fill and purge the loop, then commission the controller and the outdoor sensor.

A family business established in Montreal for more than fifteen years, we hold RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work. Thermo 2000, for its part, warrants the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Let’s prepare your project

Engineer, contractor or owner in Laval, Montreal, Longueuil, on the North Shore or the South Shore: ask for a free estimate and a written quote. Financing is available.

01 · What it is for

A 165 kW boiler to write into a 480 V project specification

For the engineer or contractor preparing a project, the VoltMax SCR 165 comes with an engineering specification, an installation manual and published certifications. This version runs on 480 V three-phase.

  • New or replacement projects designed by a building mechanical engineer
  • Industrial and commercial buildings on 480 V three-phase power
  • Hot-water heating loops: radiators, baseboards, radiant floors, hydro-air
  • Projects that call for 0-10 Vdc signal control or a BACnet link
Published standardsCSA C22.2 No. 165-92 and UL 834, CSA B-51-14 tank, CRN registration and ASME Section IV "H" stamp.
Standard safety devicesLow-water cutoff standard above 60 kW, two limit controls and a factory-installed relief valve.
SCR and stage rotationThe controller combines SCR modulation from 0 to 100% with rotation of the relay stages.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 165-480-3 PH
ConfigurationB (99 to 180 kW)
TypeCommercial hot-water electric boiler, vertical
Output165 kW
Output in BTU/h562,980 BTU/h
Power supply480 VAC, 60 Hz, three-phase
Current198.5 A
ModulationSCR 0 to 100% (solid-state relay) plus relay stages
Water volume30 US gal (113.5 L)
Water connections2 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
Max. working pressure125 psi (862 kPa), standard
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French and English
Control functionsStage rotation, outdoor reset, schedules, pump contact with or without domestic hot water priority, second setpoint for an indirect water heater
External control0-10 Vdc signal (setpoint and output)
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
Heating elementsImmersion type, Incoloy, replaceable
Low-water cutoffStandard (models above 60 kW)
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight550 lb (250 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR480165P3
03 · Before installing

What to know before installing

  • 480 V three-phase, 60 Hz power supply: 198.5 A. Overcurrent protection and conductor sizes are determined by the engineer or the master electrician.
  • Published clearances to carry onto the mechanical room drawings: 3 in on the sides and back, 24 in in front, 32 in above, none underneath.
  • The circulating pump and expansion tank are not on Thermo 2000’s list of supplied items: they must be included in the specification.
  • Weight of 550 lb (250 kg) to account for in handling and for the mechanical room slab.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • On/off control switch
  • Control and power fuses and breakers
  • SCR relays
  • Two limit controls, automatic and manual reset
  • Factory-installed relief valve
  • Drain valve
  • Low-water cutoff
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Which technical documents are available?

Thermo 2000 publishes an engineering specification, an installation manual and a French brochure, gathered in the Documents section of this page.

Which standards does the boiler meet?

According to the manufacturer’s specification: CSA C22.2 No. 165-92 and UL 834 (CSA mark for Canada and the United States), CSA B-51-14 tank, CRN registration and ASME Section IV "H" stamp.

Is the low-water cutoff included?

Yes. Thermo 2000 supplies it as standard on models above 60 kW, so on this 165 kW boiler, along with two limit controls with automatic and manual reset and a factory-installed relief valve.

Can it be controlled from a PLC or a management system?

Yes: by a 0-10 Vdc signal that sets the setpoint and the output, or over BACnet IP / MS-TP. Thermo 2000 does not mention Modbus.

Do you work with the project engineer?

Yes. We install to the engineer’s drawings and specification, connect the piping and the 480 V circuit, then commission the controller and the outdoor sensor.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 165 kW, 480 V VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.