THERMO 2000 VoltMax SCR VOLTSCR600165P3 Commercial Electric Boiler | 165 kW - 600V 3 Phase

In stock

The 600 V three-phase VoltMax SCR 165 heats a building’s loop and, through its second setpoint, can supply an indirect water heater for domestic hot water.

Model numberVOLTSCR600165P3

165 kW562,980 BTU/h
158.8 Acurrent at 600 V three-phase
0 to 100%SCR power modulation
600 V · three-phase2nd setpoint: indirect water heaterOutdoor sensor supplied
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR600165P3
ManufacturerThermo 2000
Manufacturer designationVOLTMAX SCR 165-600-3 PH
Output165 kW (562,980 BTU/h)
Power supply600 V, three-phase, 60 Hz
Current158.8 A
CommunicationBACnet IP / MS-TP, Ethernet

165 kW on 600 V to heat the building and its domestic hot water

What it does and which buildings it suits

The VoltMax SCR 165 is a Thermo 2000 commercial electric boiler, here in its 165 kW, 600 V three-phase version. The manufacturer rates it at 562,980 BTU/h. Like any hot-water boiler, it heats a closed loop that feeds baseboards, radiators, a radiant floor or hydro-air coils. Its controller goes further: it manages a second setpoint for an indirect water heater, so the same boiler can also produce domestic hot water.

This two-in-one role appeals to owners of residential buildings, residences and managers of commercial buildings who want space heating and hot water in the same mechanical room.

Two setpoints, one boiler

The Schneider Electric controller has a pump contact with or without domestic hot water priority. With priority, the indirect water heater is served first when it calls for heat; without priority, space heating and hot water share the output. The setpoint adjusts from 50 °F to 200 °F (10 °C to 93 °C), and the supplied outdoor sensor adjusts the heating water temperature to the weather.

SCR modulation from 0 to 100%, through solid-state relays, matches output to actual demand, which limits peak power demand according to Thermo 2000. The controller shows its alarm codes in French or English and can send its alarms by email through its Ethernet port.

In a Quebec building

On a 600 V three-phase service, the VoltMax SCR 165 draws 158.8 A. For a residence in Montreal or a building on the North Shore, the mechanical room has to hold the boiler, the indirect water heater and their pumps. The vertical boiler takes up little room there: 3 in of clearance on the sides and back, 24 in in front and 32 in above. It weighs 550 lb (250 kg) and holds 30 US gal of water.

The installation, step by step

We start with a free on-site estimate: electrical service, loop, emitters, hot water needs and available space. The written quote then specifies the boiler, the indirect water heater, the circulating pump and the expansion tank, the last three not being on Thermo 2000’s list of supplied items.

Our crews install the boiler, connect the loop, the indirect water heater and the 600 V circuit, fill and purge the system, then set the two setpoints, the priority and the outdoor sensor. Thermo 2000 warrants the boiler’s tank for 10 years (limited warranty, closed-loop heating) and its electrical and mechanical components for 2 years. AirGreen, a family business established in Montreal for more than fifteen years, holds RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work.

Get your quote

In Montreal, on the North Shore, in Laval, Longueuil or on the South Shore, the on-site estimate is free and the quote is in writing. Financing is available.

01 · What it is for

Space heating and domestic hot water for the same building

In a residential building or a residence, the same boiler can heat the premises and, through an indirect water heater, the domestic hot water. The VoltMax SCR 165 controller handles two setpoints and a pump contact with or without domestic hot water priority.

  • Residential buildings and residences on 600 V three-phase power
  • Projects that add an indirect water heater to the heating loop
  • Hot-water baseboards, radiators, radiant floors or hydro-air coils
  • Replacing an existing commercial electric boiler
Two setpointsOne setpoint for space heating, a second for the indirect water heater, and a pump contact with or without domestic hot water priority.
Up to 200 °FSetpoint adjustable from 50 °F to 200 °F (10 °C to 93 °C), to suit the emitters and the indirect water heater.
SCR modulation from 0 to 100%Output follows demand instead of switching on in blocks; Thermo 2000 states that this limits peak power demand.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
SeriesVoltMax SCR
Manufacturer designationVOLTMAX SCR 165-600-3 PH
ConfigurationB (99 to 180 kW)
TypeCommercial hot-water electric boiler, vertical
Output165 kW
Output in BTU/h562,980 BTU/h
Power supply600 VAC, 60 Hz, three-phase
Current158.8 A
ModulationSCR 0 to 100% (solid-state relay) plus relay stages
Water volume30 US gal (113.5 L)
Water connections2 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
Max. working pressure125 psi (862 kPa), standard
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French and English
Control functionsStage rotation, outdoor reset, schedules, pump contact with or without domestic hot water priority, second setpoint for an indirect water heater
External control0-10 Vdc signal (setpoint and output)
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
Heating elementsImmersion type, Incoloy, replaceable
Low-water cutoffStandard (models above 60 kW)
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight550 lb (250 kg)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, CRN, ASME Section IV (H)
Model numberVOLTSCR600165P3
03 · Before installing

What to know before installing

  • 600 V three-phase, 60 Hz power supply: 158.8 A. The circuit is sized by a master electrician.
  • The indirect water heater, circulating pump and expansion tank are not among the items supplied by Thermo 2000: they are added to the quote as the project requires.
  • Clearances: 3 in on the sides and back, 24 in in front, 32 in above, none underneath.
  • The boiler weighs 550 lb (250 kg): access to the mechanical room is checked before delivery.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • On/off control switch
  • Control and power fuses and breakers
  • SCR relays
  • Two limit controls, automatic and manual reset
  • Factory-installed relief valve
  • Drain valve
  • Low-water cutoff
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can the VoltMax produce domestic hot water?

Not directly: it heats the loop, and an indirect water heater connected to that loop produces the domestic hot water. The controller provides a second setpoint for that water heater and a pump contact with or without priority.

What does "with or without priority" mean?

With priority, the domestic hot water demand comes before space heating; without priority, both are served at the same time. The choice is made when setting up the controller, based on how the building is used.

Is the indirect water heater included?

No. It is not among the items supplied by Thermo 2000; we select it with you based on the building’s needs and list it in the quote.

What warranty does Thermo 2000 offer?

According to its documents: 10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

Can you install it?

Yes. We connect the boiler to the heating loop and, where applicable, to the indirect water heater, then to the 600 V circuit. Commissioning includes setting the two setpoints, the priority and the outdoor sensor.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 165 kW, 600 V VoltMax SCR, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.