THERMO 2000 VoltMax SCR VOLTSCR60045P3 Commercial Electric Boiler | 45 kW - 600V 3 Phase

In stock

The 600 V three-phase VoltMax 45 delivers 45 kW of hot water heating at 43.3 A, with the CSA, UL 834, ASME and CRN standards listed by Thermo 2000.

Model numberVOLTSCR60045P3

45 kW153,540 BTU/h
43.3 Aat 600 V three phase
CSA · UL 834CSA mark, Canada and US
600 V · three phaseASME Section IV tankBACnet IP / MS-TP
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR60045P3
ManufacturerThermo 2000
DesignationVOLTMAX SCR 45-600-3 PH
Output45 kW (153,540 BTU/h)
Power supply600 V, three phase, 60 Hz
Current43.3 A
ConfigurationA (22.5 to 90 kW)

A 45 kW electric boiler on 600 V for commercial and institutional construction projects

The VoltMax 45 on 600 V three phase

Thermo 2000’s VoltMax is a hot water electric boiler designed for commercial and institutional buildings. The series covers 22.5 to 180 kW. This model, designated VOLTMAX SCR 45-600-3 PH, delivers 45 kW, or 153,540 BTU/h, and draws 43.3 A on 600 V three phase. It belongs to configuration A (22.5 to 90 kW).

In a new building or an addition supplied at 600 V, it heats the water of a closed loop that serves radiant floors, radiators or the coils of ventilation units.

What designers want to know

Thermo 2000 lists the CSA C22.2 No. 165-92 and UL 834 standards for the VoltMax, with the CSA mark for Canada and the United States. The tank meets CSA B-51-14 and carries a CRN registration as well as the ASME Section IV “H” stamp. According to the manufacturer’s most recent engineering specification, the series is now offered in the SCR version only.

On the controls side, the Schneider Electric controller communicates over BACnet IP or MS-TP and accepts an external 0-10 Vdc signal for setpoint and output. It modulates output from 0 to 100% through solid-state relays, in addition to relay stages, and Thermo 2000 points out that this modulation limits peak power demand. Its Ethernet port provides a web page and email alarms, and the outdoor sensor is included.

On the mechanical side: four 1 1/2 in male NPT side connections, relief valve and drain at 3/4 in female NPT, 11 US gal of water (41.6 L) and a weight of 310 lb (141 kg). The required clearances are 24 in in front, 32 in above, 3 in on the sides and at the back, with no clearance at the floor. The setpoint ranges from 50 °F to 200 °F.

What installation by AirGreen covers

We work in Montreal, Laval, Longueuil, on the North Shore and on the South Shore. For a new project, we start from the drawings and specifications: we confirm the model, the voltage and the accessories to plan for, including the circulator and expansion tank, which are not among the parts supplied by Thermo 2000, and the low water cut-off, available as an option on this size. You receive a detailed written quote.

On site, our technicians install the boiler, connect it to the loop, pipe the relief valve discharge, mount the outdoor sensor and make the electrical connection under our RBQ licence 5645-9605-01, which covers ventilation, refrigeration and electrical work. We then program the controller and coordinate the BACnet integration with the project’s integrator.

AirGreen is a family business established in Montreal for more than fifteen years. Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Let’s talk about your project

To include a 45 kW VoltMax on 600 V in your project, ask for a free estimate. We give you a written quote, and financing is available.

01 · What it is for

A boiler that fits into the plans of a new building

For a new building or an addition on 600 V, the VoltMax 45 is specified by its designation VOLTMAX SCR 45-600-3 PH. Thermo 2000 publishes an engineering specification, a manual and a brochure for the series.

  • New commercial and institutional buildings supplied at 600 V
  • Additions connected to a 600 V three-phase distribution
  • Engineered projects with BACnet integration
  • Radiant floors, radiators and hot water coils (hydro-air)
Listed standardsCSA C22.2 No. 165-92 and UL 834 (CSA mark, Canada and US), CSA B-51-14 tank, CRN, ASME Section IV, “H” stamp.
Building integrationBACnet IP / MS-TP, 0-10 Vdc signal for setpoint and output, web page and email alarms.
43.3 A on 600 VThe current Thermo 2000 publishes for this 45 kW model.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
Manufacturer designationVoltMax 45, SCR series (VOLTMAX SCR 45-600-3 PH)
TypeCommercial hot water electric boiler
Output45 kW
Output in BTU/h153,540 BTU/h
Power supply600 VAC, 60 Hz, three phase
Current43.3 A
ModulationSCR from 0 to 100% (solid-state relay) plus relay stages
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French/English
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
External controlSetpoint and output by 0-10 Vdc signal
Outdoor sensorIncluded (outdoor reset)
Domestic hot water2nd setpoint for an indirect water heater; pump contact with or without DHW priority
Low water cut-offOptional up to 60 kW (standard above)
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight310 lb (141 kg)
ConfigurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR60045P3
03 · Before installing

What to know before installing

  • 600 V three-phase, 60 Hz supply, for a current of 43.3 A; the protection and conductors are sized according to the electrical drawings.
  • According to Thermo 2000’s engineering specification, the VoltMax series is now offered in the SCR version only.
  • The circulator and expansion tank are not on the manufacturer’s list of supplied parts.
  • The low water cut-off is an option on this size (standard above 60 kW): if the drawings require it, we add it to the quote.
  • Clearances: 24 in in front, 32 in above, 3 in on the sides and at the back, none at the floor.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • Control ON/OFF switch
  • Control and power fuses and breakers
  • SCR relays
  • 2 limit controls, one automatic, one manual
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

How is this model specified?

Thermo 2000 uses the naming “VOLTMAX SCR kW-voltage-X PH”. For this model: VOLTMAX SCR 45-600-3 PH. The manufacturer’s engineering specification is in the Documents section.

Which standards does the boiler meet?

Thermo 2000 lists CSA C22.2 No. 165-92 and UL 834 (CSA mark for Canada and the United States), CSA B-51-14 for the tank, CRN registration and the ASME Section IV “H” stamp.

Can it be controlled by the building management system?

Yes. The Schneider Electric controller communicates over BACnet IP or MS-TP and accepts an external 0-10 Vdc signal for setpoint and output.

What else needs to be planned besides the boiler?

The circulator, the expansion tank, the relief valve discharge, a dedicated 600 V circuit and, if the project requires it, the optional low water cut-off.

What warranty does Thermo 2000 offer?

10 years on the tank (limited warranty, closed-loop heating) and 2 years on electrical and mechanical components, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 45 kW VoltMax on 600 V for your project, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.