THERMO 2000 VoltMax SCR VOLTSCR60090P3 Commercial Electric Boiler | 90 kW - 600V 3 Phase
Thermo 2000’s VoltMax SCR 90 delivers 90 kW on 600 V three-phase and accepts a setpoint or output imposed by a 0-10 Vdc signal, so it follows the building’s control sequence.
Model numberVOLTSCR60090P3
514 316-2973 · sales@airgreen.ca
Quick facts
90 kW on 600 V, run by the building’s system or by its own controller
A commercial boiler that fits into a control sequence
In a clinic in Laval or a shopping centre on the South Shore, heating often goes through the hot-water coils of the air handling units, and a management system decides when to heat and to what temperature. Thermo 2000’s VoltMax SCR 90, on 600 V three-phase (manufacturer designation: VOLTMAX SCR 90-600-3 PH), suits that role well: it can take its orders from outside.
It delivers 90 kW, or 307,080 BTU/h, and heats a closed loop that can serve coils, radiators, a radiant floor or an indirect water heater. Thermo 2000 designs it for commercial and institutional buildings.
Two ways to control it, and a third without a central system
First way: a 0-10 Vdc signal. The building system imposes the water temperature setpoint or the boiler’s output. Second way: BACnet IP or MS-TP communication, which also lets the system read status and alarms. And if the building has no central system, the Schneider Electric controller does the job on its own, with the included outdoor sensor, schedules and a setpoint adjustable from 50 °F to 200 °F.
In every case, output is modulated from 0 to 100% through solid-state relays (SCR), on top of the relay stages, and the controller rotates its stages. Thermo 2000 states that this modulation limits peak power. On 600 V three-phase, the boiler draws 86.6 A.
Physically, it is the largest configuration A model: a 310 lb vertical cabinet holding 11 US gal of water, with 3 in of clearance on the sides and back, 24 in in front and 32 in above.
Installation, coordinated by AirGreen
The free on-site estimate lets us check the 600 V service, the loop and the planned sequence. We then give you a written quote specifying the boiler and the components to add, including the circulator and expansion tank, which Thermo 2000 does not supply.
Our crews install the boiler, connect the piping to the 1 1/2 in NPT side connections, wire the 600 V supply and the control wiring, then fill and purge the loop. Commissioning is done with the engineer or the management system integrator when the building has one.
Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years. AirGreen is a family business established in Montreal for more than fifteen years and holds RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work.
Your commercial project
In Montreal, Laval, Longueuil, on the North Shore or on the South Shore, ask for your free estimate: the quote is in writing, and financing is available.
Hot water for coils and the building’s sequence
In a building whose air handling units have hot-water coils, the boiler has to respond to the control sequence. The 600 V VoltMax SCR 90 takes its setpoint or output from a 0-10 Vdc signal or over BACnet, and can also run on its own controller.
- Buildings with hot-water coils in their air handling units
- Clinics, shopping centres and office buildings on 600 V three-phase
- Projects where an engineer defines the heating control sequence
- Replacing a 600 V commercial electric boiler
Specifications
From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.
What to know before installing
- 600 V three-phase, 60 Hz power supply: 86.6 A according to Thermo 2000. We check the service before quoting.
- The control sequence (0-10 Vdc signal or BACnet) is defined with the building’s engineer or integrator before commissioning.
- The circulator and expansion tank are not among the components Thermo 2000 supplies.
- Clearances: 3 in on the sides and back, 24 in in front, 32 in above, 0 at the floor.
- Thermo 2000 warranty: 10 years on the tank (limited warranty, closed-loop heating), 2 years on electrical and mechanical components.
- Schneider Electric controller
- Outdoor temperature sensor
- ON/OFF control switch
- Control and power fuses and breakers
- SCR relays
- Two limit controls, automatic and manual reset
- Factory-installed relief valve
- Drain valve
- Low-water cut-off (standard above 60 kW)
Manufacturer documents
Explore the range
Electric boilersSee allSame brand
THERMO 2000See all
Frequently asked questions
Can the building system control the boiler?
Yes, in two ways: a 0-10 Vdc signal that sets the setpoint or output, or BACnet IP or MS-TP communication. We set up the boiler according to the sequence specified by the engineer or integrator.
Is it suitable for the hot-water coils of an air handling unit?
Yes, that is one of the uses of a hot-water boiler like the VoltMax SCR. Its setpoint adjusts from 50 °F to 200 °F, and the loop is sized for the coils in place.
Can it run without a management system?
Yes. Its Schneider Electric controller handles the setpoint, outdoor reset (sensor included) and schedules on its own.
What current does it draw on 600 V?
86.6 A on 600 V three-phase, 60 Hz, according to Thermo 2000.
Can you install it?
Yes. We install and connect the boiler, wire the 600 V supply and the control wiring, then commission it, with the integrator where applicable.
A 600 V VoltMax SCR 90, installed by AirGreen
Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.
Specifications from the manufacturer’s documentation, checked on October 19, 2026.