THERMO 2000 VoltMax SCR VOLTSCR60036P3 Commercial Electric Boiler | 36 kW - 600V 3 Phase

In stock

The 600 V three-phase VoltMax 36 is a 36 kW commercial electric boiler that connects to the 600 V distribution of institutional and commercial buildings, at a current of 34.6 A.

Model numberVOLTSCR60036P3

36 kW122,832 BTU/h
34.6 Aat 600 V three phase
50 to 200 °Fwater setpoint range
600 V · three phaseFrench / English displayOutdoor sensor included
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberVOLTSCR60036P3
ManufacturerThermo 2000
Output36 kW (122,832 BTU/h)
Power supply600 V, three phase, 60 Hz
Current34.6 A
Setpoint range50 °F to 200 °F
Thermo 2000 warrantyTank 10 years · components 2 years

A 36 kW electric boiler on 600 V to replace the one in your school, offices or community centre

The VoltMax 36 at a glance

The VoltMax is Thermo 2000’s commercial and institutional electric boiler. This 36 kW model runs on 600 V three phase, a common voltage in Québec’s commercial and institutional buildings. It produces 122,832 BTU/h, draws 34.6 A and belongs to the series’ configuration A (22.5 to 90 kW).

Like the other SCR models, it modulates its output from 0 to 100% through solid-state relays, in addition to relay stages. Thermo 2000 points out that this modulation limits the building’s peak power demand.

Replacing a boiler at the end of its life

In a school, a community centre or an office building, the original electric boiler often reaches the end of its life while the hot water loop, radiators and floors remain in good condition. The VoltMax 36 takes its place: it connects to the existing loop through its 1 1/2 in NPT side connections and heats the water to a setpoint adjustable from 50 °F to 200 °F.

The mechanical room of an institutional building is rarely spacious. The VoltMax’s vertical design needs only 3 in of clearance on the sides and at the back, none at the floor, 24 in in front and 32 in above. The unit weighs 310 lb (141 kg): we plan its route to the room, doors and stairs included.

The Schneider Electric controller is made for all staff: 3 in backlit LCD, alarm codes, display in French or English, in °C or °F. The included outdoor sensor adjusts the water to the weather. The Ethernet port provides a web page and email alarms, and the controller communicates over BACnet IP or MS-TP with a building management system.

What installation by AirGreen covers

The on-site estimate is free in Montreal, Laval, Longueuil, on the North Shore and on the South Shore. We survey the boiler in place, the 600 V supply, and the condition of the loop, circulator and expansion tank, since these two parts are not supplied with the VoltMax. The written quote describes the removal of the old unit, the installation of the new boiler and the parts to replace.

On the day of the work, we drain the loop, remove the old boiler, set the VoltMax in place and connect it. We pipe the discharge of the factory-installed relief valve, mount the outdoor sensor and make the electrical connection. The loop is then filled and purged, and the controller is programmed with your maintenance lead.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 in ventilation, refrigeration and electrical work. Thermo 2000 covers the tank for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years.

Let’s prepare the replacement

To replace your building’s boiler with a 36 kW VoltMax on 600 V, ask for a free estimate. You receive a written quote, and financing is available.

01 · What it is for

Replacing an electric boiler in a 600 V building

In a school, a community centre or an office building supplied at 600 V, the VoltMax 36 takes over from an electric boiler at the end of its life: it heats the water of the existing loop and sends it back to the radiators, floors or coils.

  • Schools, community centres and institutional buildings on 600 V
  • Replacing an end-of-life electric boiler on an existing loop
  • Cramped mechanical rooms, thanks to the small side clearances
  • Buildings where several people read the controller, in French or English
34.6 A on 600 VThe current Thermo 2000 publishes for this model on a 600 V three-phase distribution.
Bilingual display3 in backlit LCD, alarm codes, °C or °F, in French or English.
SCR modulation from 0 to 100%Output follows the demand; according to the manufacturer, this limits peak power demand.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerThermo 2000
Manufacturer designationVoltMax 36, SCR series (VOLTMAX SCR 36-600-3 PH)
TypeCommercial hot water electric boiler
Output36 kW
Output in BTU/h122,832 BTU/h
Power supply600 VAC, 60 Hz, three phase
Current34.6 A
ModulationSCR from 0 to 100% (solid-state relay) plus relay stages
Setpoint range50 °F to 200 °F (10 °C to 93 °C)
Water volume11 US gal (41.6 L)
Water connections1 1/2 in male NPT, 4 side connections
Relief valve and drain3/4 in female NPT
ControllerSchneider Electric, 3 in backlit LCD, alarm codes, °C/°F, French/English
CommunicationBACnet IP / MS-TP; Ethernet port with web page and email alarms
External controlSetpoint and output by 0-10 Vdc signal
Outdoor sensorIncluded (outdoor reset)
Domestic hot water2nd setpoint for an indirect water heater; pump contact with or without DHW priority
Low water cut-offOptional up to 60 kW (standard above)
ClearancesSides 3 in, back 3 in, front 24 in, top 32 in, floor 0
Weight310 lb (141 kg)
ConfigurationA (22.5 to 90 kW)
Manufacturer warrantyThermo 2000: 10 years on the tank (limited warranty, closed-loop heating); 2 years on electrical and mechanical components (parts and accessories)
StandardsCSA C22.2 No. 165-92, UL 834, CSA B-51-14, ASME Section IV (H), CRN
Model numberVOLTSCR60036P3
03 · Before installing

What to know before installing

  • 600 V three-phase, 60 Hz supply, for a current of 34.6 A. The electrician sizes the protection and conductors from that value.
  • For a replacement, we check the condition of the loop and of the existing circulator and expansion tank: these two parts are not supplied with the boiler.
  • Clearances: 24 in in front and 32 in above, 3 in on the sides and at the back, none at the floor.
  • The unit weighs 310 lb (141 kg): we plan its route to the mechanical room, doors and stairs included.
  • Low water cut-off: optional on this size, standard above 60 kW.
In the box
  • Schneider Electric controller with backlit display
  • Outdoor temperature sensor
  • Control ON/OFF switch
  • Control and power fuses and breakers
  • SCR relays
  • 2 limit controls, one automatic, one manual
  • Factory-installed relief valve
  • Drain valve
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Electric boilers
See all
Same brand
THERMO 2000
See all
06 · Questions

Frequently asked questions

Can the VoltMax replace our electric boiler without redoing the loop?

In many cases, yes: it connects to the existing loop through its 1 1/2 in NPT connections. We first check the output needed, the condition of the loop and the 600 V supply during the free estimate.

Does the controller display in French?

Yes. Thermo 2000 lists a display in French or English, in °C or °F, with alarm codes on a 3 in backlit screen.

What water temperature can it supply?

The setpoint ranges from 50 °F to 200 °F (10 °C to 93 °C). With the included outdoor sensor, the controller lowers or raises the water temperature with the weather.

Can maintenance staff be alerted to an alarm?

Yes. The controller’s Ethernet port provides a web page and email alarms, and the controller communicates over BACnet IP or MS-TP with a building management system.

What warranty does Thermo 2000 offer?

The tank is covered for 10 years (limited warranty, closed-loop heating) and the electrical and mechanical components for 2 years, parts and accessories.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A 36 kW VoltMax on 600 V, installed by AirGreen

Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.

RBQ 5645-9605-01Ventilation, refrigeration and electrical
Free estimateon site, for any installation
Quote in 24 hby phone or email
Bouchervilleshowroom

Specifications from the manufacturer’s documentation, checked on October 19, 2026.