STERLING HSB03611 Hot-Water Unit Heater | Montreal, Laval, Longueuil, South Shore & North Shore
The Sterling HSB03611 is a 26,100 BTU/h horizontal hot-water unit heater, a rating measured with 200°F water, to be chosen according to the actual temperature of your electric boiler or air-to-water heat pump.
Model numberHSB03611
514 316-2973 · sales@airgreen.ca
Quick facts
The right unit heater is chosen with your water temperature
Water temperature decides the output
The Sterling HSB03611 is a horizontal hot-water unit heater, mid-sized in the HS series. The manufacturer publishes 26,100 BTU/h under specific conditions: 200°F entering water, 60°F entering air and a 20°F drop between the water inlet and outlet. These conditions matter, because the heat a coil releases depends on the difference between the water temperature and the air temperature.
An electric boiler set high comes close to the rating. An air-to-water heat pump, on the other hand, generally works with cooler water. Sterling publishes the factors to apply: 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F, 0.429 at 120°F and 0.286 at 100°F. We apply the one that matches your installation before recommending this model, or a neighbouring size such as the HSB02411 or the HSB04811.
Which spaces it suits
A craftsperson’s workshop on the ground floor of a plex, the showroom of a small business, the maintenance garage of a rental building: the HSB03611 targets spaces that need a solid heat supply, delivered from the ceiling. It blows 550 CFM, or 480 CFM at reduced speed, where Sterling publishes 23,500 BTU/h. The air outlet comes with horizontal louvers as standard.
On the loop side, it needs 2.7 GPM with a 20°F drop, for a pressure drop of 0.09 ft H2O. Its 25 W motor runs on 115 V, single phase, 60 Hz; it is single speed, totally enclosed with thermal overload protection. The coil is rated up to 150 PSI (1,034 kPa) or 320°F (160°C) on hot water, and also accepts a propylene glycol solution, for which Sterling publishes correction factors.
What AirGreen does
We start by reading the supply temperature of your electric boiler or air-to-water heat pump, then calculating the space’s heat loss. If the HSB03611 fits, our technicians hang it by rods from the connections provided, properly level. They connect it to the loop with isolation valves and air purging, make the 115 V electrical connection and install the control. Start-up includes checking the water flow and the temperature drop between inlet and outlet.
AirGreen is a family business established in Montreal for more than fifteen years. Our RBQ licence 5645-9605-01 covers ventilation, refrigeration and electrical work. We work in Montreal, Laval, Longueuil, the North Shore and the South Shore.
Get a calculation made for your building
The on-site estimate is free. You then receive a written quote stating the water temperature used and the resulting corrected output, with financing available.
A solid heat supply, delivered from the ceiling
The HSB03611 blows 550 CFM of air warmed by the water from your system. It suits commercial or work spaces where a baseboard is not enough and the floor has to stay clear.
- Craftsperson’s workshop on the ground floor of a plex
- Showroom or back shop of a small business
- Maintenance garage of a rental building
- Building heated by an air-to-water heat pump, sized at the actual water temperature
Specifications
From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.
What to know before installing
- With an air-to-water heat pump, check the planned water temperature: Sterling applies a factor of 0.571 at 140°F and 0.286 at 100°F to the 200°F rating.
- Water flow to plan for: 2.7 GPM with a 20°F drop. The circulator must supply it in addition to the loop’s other circuits.
- 115 V, single-phase, 60 Hz power supply at the location.
- Pipe connection size and dimensions are not in the verified data: we confirm them with Sterling before ordering.
Manufacturer documents
Explore the range
Hot-water unit heatersSee allSame brand
STERLINGSee all
Frequently asked questions
I am told the water will be 120°F: what output should I expect?
Sterling applies a factor of 0.429 at 120°F to the 26,100 BTU/h rating measured at 200°F. We do that calculation with you and compare it with the space’s heat loss.
How do I choose between the HSB02411, HSB03611 and HSB04811?
They are neighbouring sizes in the same series. The choice is made on the output corrected to your water temperature, compared with the heat loss, not on the model number.
How much water has to circulate?
2.7 GPM with a 20°F drop. The coil’s pressure drop is then 0.09 ft H2O.
Can the coil handle my loop’s pressure?
Sterling rates it up to 150 PSI (1,034 kPa) or 320°F (160°C) on hot water, and factory tests it at 200 psig (1,379 kPa) under water.
An HSB03611 chosen for your water, installed by AirGreen
Tell us about your project: we check the sizing, confirm availability and send you a quote. Or let our technicians install it for you.
Specifications from the manufacturer’s documentation, checked on October 19, 2026.