STERLING HSB04811 Hot-Water Unit Heater | Montreal, Laval, Longueuil, South Shore & North Shore

In stock

Sterling HSB04811 unit heater: 34,800 BTU/h with 200°F water and 750 CFM of air, to heat the warehouse or workshop of a building that already has an electric boiler.

Model numberHSB04811

34,800 BTU/hwith 200°F water (60°F air)
750 CFMairflow
1/20 HPenclosed 115 V motor
115 V · single phaseCeiling mountingOutput depends on water temperature
Ask for a quote

514 316-2973 · sales@airgreen.ca

Quick facts

Model numberHSB04811
ManufacturerSterling
Output (200°F water)34,800 BTU/h
Airflow750 CFM
Water flow3.5 GPM
Motor1/20 HP, 115 V
MountingHung by rods

Heat the warehouse with the boiler that already heats your offices

What the Sterling HSB04811 is

Many commercial buildings have an electric boiler for the offices and a poorly heated warehouse or workshop at the back. The Sterling HSB04811 lets you extend the hot-water loop that far. It is a horizontal unit heater: water flows through a coil, a propeller fan blows air across it, and the heat comes down from the ceiling to the work area. Because it hangs, it leaves the floor free for shelving, carts and pallets.

Sterling publishes 34,800 BTU/h with 200°F entering water, 60°F entering air and a 20°F drop. Airflow is 750 CFM, with an outlet velocity of 550 FPM. This size is the first in the series with the 1/20 HP motor: a single-speed 115 V motor, totally enclosed with thermal overload protection.

The technical points we check

  • Water temperature. The rating applies at 200°F. Sterling publishes the factors to apply below that: 0.857 at 180°F, 0.715 at 160°F, 0.571 at 140°F, 0.429 at 120°F.
  • Flow and circulator. The unit needs 3.5 GPM with a 20°F drop, for a pressure drop of 0.12 ft H2O. If you add several unit heaters, the circulator and the boiler must cover them all.
  • Loop fluid. Hot water or a propylene glycol solution: Sterling publishes correction factors for glycol.
  • Structure. The unit hangs by rods from the connections provided and must be level.
  • Electrical. 115 V, single phase, 60 Hz.

The coil is rated up to 150 PSI (1,034 kPa) or 320°F (160°C) on hot water and factory tested at 200 psig (1,379 kPa) under water, which suits the closed loops of the commercial buildings we serve.

Installation by AirGreen

After a visit and a heat-loss calculation for the warehouse, we propose the number of units and their location. Our technicians hang them, connect them to the loop with isolation valves and air purging, make the electrical connection and install the controls. Each unit can have its own control, so the warehouse can be kept at a different temperature from the offices. We finish with start-up and a check of the flows.

AirGreen is a family business established in Montreal for more than fifteen years, holding RBQ licence 5645-9605-01 (ventilation, refrigeration and electrical). We work in Montreal, Laval, Longueuil, the South Shore and the North Shore.

Let’s plan your warehouse

Ask for a free on-site estimate. You will receive a written quote detailing the number of unit heaters, the water temperature used and the work on the loop. Financing is available.

01 · What it is for

Heating the warehouse area of a commercial building

In a building where an electric boiler already heats the offices, the HSB04811 extends the hot-water loop to the warehouse or workshop and blows 750 CFM of warmed air there, from the ceiling.

  • Storage area of a service business
  • Repair shop attached to offices
  • Renovated industrial condo heated by an electric boiler
  • Adding one or more units to an existing loop
750 CFMAirflow published by Sterling, with a 550 FPM outlet velocity and 630 CFM at reduced speed.
34,800 BTU/h at 200°FRating with 200°F entering water, 60°F entering air and a 20°F drop; 31,300 BTU/h at reduced speed.
Enclosed 1/20 HP motorSingle-speed 115 V motor, totally enclosed, with thermal overload protection, according to the manufacturer.
02 · Specifications

Specifications

From the manufacturer’s documentation. A value the manufacturer does not publish is not listed.

ManufacturerSterling
TypeHorizontal hot-water unit heater, propeller fan
Catalogue designationHS-48
CoilStandard, header type (B)
Hot-water output34,800 BTU/h (200°F entering water, 60°F entering air, 20°F drop)
Output at reduced speed31,300 BTU/h (same conditions)
Airflow750 CFM (630 CFM at reduced speed)
Outlet air velocity550 FPM
Water flow3.5 GPM (20°F drop)
Water pressure drop0.12 ft H2O
Correction factors (60°F entering air)180°F water: 0.857 · 160°F: 0.715 · 140°F: 0.571 · 120°F: 0.429 · 100°F: 0.286
Motor1/20 HP, single speed, totally enclosed with thermal overload protection
Power supply115 V, single phase, 60 Hz
Coil rating (hot water)Up to 150 PSI (1,034 kPa) or 320°F (160°C)
Factory test200 psig (1,379 kPa), under water
Air outletHorizontal louvers, standard
MountingHorizontal, hung by rods from the connections provided on the unit, level
Heat-transfer fluidHot water or propylene glycol solution (correction factors published by Sterling)
ListingETL
StandardsCSA C22.2, UL 1995, UL 60335-2-40
Model numberHSB04811
03 · Before installing

What to know before installing

  • The rating is measured at 200°F. Sterling applies a factor of 0.715 at 160°F, 0.571 at 140°F and 0.429 at 120°F: we calculate with your boiler’s temperature.
  • Each unit needs 3.5 GPM with a 20°F drop. With several unit heaters, the boiler and the circulator must cover them all.
  • Plan for a 115 V, single-phase, 60 Hz supply per unit or per circuit, depending on the electrical design chosen.
  • The structure must carry the unit hung by rods, level. Weight, dimensions and connections are confirmed with the manufacturer before ordering.
04 · Documents

Manufacturer documents

05 · See also

Explore the range

Same category
Hot-water unit heaters
See all
Same brand
STERLING
See all
06 · Questions

Frequently asked questions

Can several HSB04811 units go on the same loop?

Yes, if the boiler and the circulator are sufficient. Each unit needs 3.5 GPM with a 20°F drop, for a pressure drop of 0.12 ft H2O; we size the loop accordingly.

What output do you get with 160°F water?

Sterling applies a factor of 0.715 at 160°F to the 34,800 BTU/h rating measured at 200°F. We give you that calculation with the quote.

Which motor does this unit have?

A 1/20 HP, 115 V, single-speed motor. According to Sterling, motors under 1/3 HP in this series are totally enclosed with thermal overload protection.

What does the reduced-speed rating mean?

Sterling publishes 31,300 BTU/h and 630 CFM with the fan slowed down. Since the standard motor is single speed, we check with the manufacturer what that operation requires before planning it.

AirGreen · Montréal, Laval, Longueuil, South Shore, North Shore

A warehouse heated by your hot-water loop, installed by AirGreen